Brooklyn · Block 4067 · Lot 22 · 11208

998 Blake Avenue

3 floors · 20 apartments · 23,382 sq ft · built 1905 · class N9 · owner of record: Blake Holdings Llc

29open violations
$48,130ECB/OATH penalties owed
0HPD class C (immediately hazardous)
Overdueto Annual property registration

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

OverdueRegistration expired 2026-09-01
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 68 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 68 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 84 days
Annual
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 5 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1164 days
Next cycle year 2029

Open violations

ECB / OATH (12) · $48,130 owed
IssuedViolationHearingBalance
Oct 9, 2026Construction CLASS - 2
ATOI IN THE WATER HEATER ROOM (4) FOUR WATER HEATERS WERE OBSERVED TO HAVE THE FRESH AIR INTAKE VENT PIPING COMPLETELY DISCONNECTED. THIS IS CONTRARY TO MC 802.10 - VENT CONNECTORS SHALL BE SECURELY FASTENED AN
#39207504P
Dec 16, 2026
PENDING
$1,250
Oct 9, 2026Elevators CLASS - 1
CLASS 1 C/U: 1. DOOR ZONE RESTRICTOR DEVICE FOUND INOPERATIVE AS PER CODE ASME A17.1/CSA B44 - SECTION 2.26.5. ELEVATOR CAR DOOR CAN BE OPENED WHEN THE CAR IS NOT WITHIN THE DESIGNATED DOOR ZONE, CREATING AN UN
#39207505R
Dec 16, 2026
PENDING
$1,250
Feb 25, 2026Construction CLASS - 2
FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR VIOLATION #39135196M., FILE A CERTIFICATE OF CORRECTION
#39178268M
Jun 1, 2027
DEFAULT
$6,250
Feb 25, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER FOR VIOLATION # 39135192P .NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 2022 CODE). NO FIRESTOPPING OBSERVED AROUND CABLES COMING THROUGH P
#39178267K
Jun 1, 2027
DEFAULT
$25,000
Oct 24, 2025Boilers CLASS - 3
@CELLAR AO SMITH HOT WATER HEATER#1 HAS CORRODED SAFETY VALVE PIPE+#3 HWH IS INOPERABLE+ALL HWH'S ARE MISSING CONDENSATE NEUTRALIZER+GAS METER ROOM FRESH AIR HAS BROKEN FIRE DAMPER+OUTSIDE INLET IS MISSING GRAT
#39164718N
Jan 7, 2026
ADMIT/IN-VIO
$0
Oct 22, 2025Construction CLASS - 2
OBSERVED ON THE FIRST FLOOR IN THE KITCHEN NO TRAP UNDER SINK WHICH CONTRARY CODE SECTION PC 1002.1, REPAIR AND/OR REPLACE
#39164374Z
Jan 7, 2026
ADMIT/IN-VIO
$0
Jan 29, 2025Construction CLASS - 2
FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39097339X ISSUED ON 10/18/2023, AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1 RCNY 102-01(D)(2). AN ACCEPTABLE CERT
#37033095N
Oct 22, 2026
DEFAULT
$6,250
Jan 10, 2025Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOOR AT GAS METER ROOM IN BASEMENT. POTENTIAL FIRE HAZARD., REPAIR/REPLACE DOOR
#39135193R
Apr 20, 2026
IN VIOLATION
$0
Jan 10, 2025Unknown CLASS - 1
I OBSERVED IN THE ELEVATOR MOTOR DISCONNECT THE IMPROPER FUSING OF THE CONDUCTORS, ALL FUSES SHALL BE OF THE SAME AMPERAGE AND TYPE., PROVIDE PROTECTION AGAINST OVERCURRENT; PROPERLY COORDINATE FUSES.
#39135196M
Apr 20, 2026
IN VIOLATION
$4,800
Jan 10, 2025Unknown CLASS - 2
I OBSERVED IN THE ELEVATOR MOTOR ROOM THE UNPERMITTED USE OF FLEXIBLE CORDS AS PERMANENT WIRING AS EC 400.8 THIS IS NOT ALLOWED. ALSO NOTED IN THE THIRD FLOOR BATHROOM ON THE "B" SIDE BATHROOM A IMPROPERLY WIRE
#39135195K
Apr 20, 2026
IN VIOLATION
$800
Jan 10, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETERATIONS IN JANITOR ROOM ON 3RD FLOOR, ELECTRIC ROOM AND IT ON
#39135192P
Dec 14, 2026
PENDING
$2,530
Oct 18, 2023Construction CLASS - 2
SPRINKLER HEADS ON THE 1ST AND 3RD FLOOR OBSTRUCTED BY CEILING. AS PER 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATING CONDITION IN ACCORDANCE
#39097339X
Dec 27, 2023
STIPULATION/IN-VIO
$0
DOB (0)

None open.

DOB NOW Safety (17)
IssuedViolationStatus
Sep 18, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle B (premises is in Community District 5)
Active
Sep 18, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle B (premises is in Community District 5)
Active
Sep 18, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle B (premises is in Community District 5)
Active
Sep 18, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle B (premises is in Community District 5)
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Report
Active
Apr 5, 2019Elevators EVCAT1
Active
Sep 15, 2017Elevators EVCAT1
Active
Dec 1, 2016Elevators EVCAT1
Active
Jun 1, 2016Elevators EVCAT5
Active
Jun 10, 2015Elevators EVCAT1
Active
Oct 31, 2014Elevators EVCAT1
Active
Mar 31, 2014Elevators EVCAT1
Active
Oct 1, 2012Elevators EVCAT1
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 9, 2026ECBConstruction: ATOI IN THE WATER HEATER ROOM (4) FOUR WATER HEATERS WERE OBSERVED TO HAVE THE FRESH AIR INTAKE VENT PIPING COMPLETELY DISCONNECTED. THIS IS CONTRARY TO MC 802.10 - VENT CONNECTORS SHALL BE SECURELY FASTENED ANOpen
Oct 9, 2026ECBElevators: CLASS 1 C/U: 1. DOOR ZONE RESTRICTOR DEVICE FOUND INOPERATIVE AS PER CODE ASME A17.1/CSA B44 - SECTION 2.26.5. ELEVATOR CAR DOOR CAN BE OPENED WHEN THE CAR IS NOT WITHIN THE DESIGNATED DOOR ZONE, CREATING AN UNOpen