4 floors · 74,800 sq ft · built 1927 · class W1 · owner of record: Nyc Department Of Education
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 66 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 74,800 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 187 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 187 days | Annual filing |
| Gas piping inspection (2027 cycle) Likely applies Local Law 152 · During 2027 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 11 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2027 in 431 days | Next cycle year 2027 |
| Energy audit and retro-commissioning (2034) Likely applies Local Law 87 · Calendar year 2034 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 4444). Agency page | Dec 31, 2034 in 2988 days | Next due 2034 |
| Annual boiler inspection (2 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-05-01 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Apr 20, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: MISSING WIRE MESH GLASS PANEL IN STAIRWELL E EXIT 10 3RD FLOOR TO 2ND FLOOR AND CRACKED GLASS UPPER VISION PANEL IN SMALL CAFETERIA AREA SPACE OBSER #35732681X | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 20, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FIRE RATED SMOKE DOORS AND CLASSROOM DOOR NOT SELF-CLOSING DUE TO BINDING, MISSING AND/OR FAULTY HARDWARE ON SMOKE DOOR. AT EAST ENTRANCE AND SMOKE #35732683J | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 20, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROBIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). NOTED: INSTALLATION ON PERMANENT DOOR KICK STOPS ON FIRE RATED CLASSROOMS 412, 400 AND 1 #35732682H | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 20, 2026 | Construction CLASS - 2 REISSUE ON ECB#35720685P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EMERGENCY EXIT DISCHARGES AND EXIT SIGNS NOT #35732680Y | Jul 10, 2026 POP/IN-VIO | $0 |
| Apr 20, 2026 | Construction CLASS - 2 REISSUE ON ECB#35720686R EXIT DOOR NOT SELF-CLOSING.NOTED:EXTERIOR EMERGENCY EXIT DOORS NOT SELF-CLOSING PROPERLY DUE TO BINDING,MISSING ANDOR FAULTY HARDWARE ON 1ST FLOOR EXIT 5,1ST FLOOR EXIT 7 AND 1ST FLOOR #35732678P | Jul 10, 2026 POP/IN-VIO | $0 |
| Apr 20, 2026 | Construction CLASS - 2 REISSUE ON ECB #35720684N. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FIRE RATED CLASSROOM AND SMOKE DOORS NOT SELF-CLOSING PROPERLY DUE TO BINDING, MISSING AND/OR FAULTY HARDWARE ON CLASSROO #35732679R | Jun 12, 2026 POP/IN-VIO | $0 |
| Jun 17, 2025 | Construction CLASS - 2 EXIT DOOR NOT SELF-CLOSING PROPERLY AT THE TIME OF INSPECTION. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 1ST FLOOR EXIT-7, 8, 10, EXIT-11, AT 3RD FLOOR GYM 1 EXIT DOOR, 1ST FL STAIR "A" 1 EXIT DOOR, 1ST F #35720686R | Jul 11, 2025 POP/IN-VIO | $0 |
| Jun 17, 2025 | Construction CLASS - 2 REISSUE 335692278M DATE OF ISSUE: 10-01-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 4TH FL. ROOM, 400B, 405, 408, 410, 419, 422, 425, AND THIRD F #35720684N | Jul 11, 2025 POP/IN-VIO | $0 |
| Jun 17, 2025 | Construction CLASS - 2 REISSUE #35693377K DATE OF ISSUE: 10-01-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGESAND PUBLIC CORRIDORS PER BC 1006.1; 27-381 AT 1ST FL. CAFETERIA 2 EMER #35720685P | Jul 11, 2025 POP/IN-VIO | $0 |
| Oct 1, 2024 | Construction CLASS - 2 REISSUE #35676302N. OBSERVED AT 1 FLOOR SMOKE EXIT 7, 8, 10 AND EXIT 11 DOORS ARE NOT CLOSING CORRECTLY. REMEDY: REPAIR/REPLACE DOOR. #35692275R | Nov 1, 2024 POP/IN-VIO | $0 |
| Oct 1, 2024 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED AT 4 FLOOR 400B, 405, 408, 410, 419, 422, 425, 427 3FL. 305, 307, FL. 203, 225, 288, 1FL. 123 AND 127 DOORS ARE NOT CLOSING CORRECTLY. REMEDY: REP #35692278M | Nov 1, 2024 POP/IN-VIO | $0 |
| Oct 1, 2024 | Construction CLASS - 2 REISSUE #35676301L. OBSERVED AT 4 FLOOR BY ROOM 402, 400, 3FL. GYM, 1FL. AUDITORIUM AND STAGE RIGHT EMERGENCY LIGHTS ARE NOT LIGHTING. REMEDY: REPAIR/REPLACE LIGHTING. #35692277K | Nov 1, 2024 POP/IN-VIO | $0 |
| Jun 30, 2023 | Construction CLASS - 2 REISSUE #35665112Z DATE OF ISSUE:07.20.2022 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT VARIOUS LOCATIONS THROUGH ENTIRE BUILDING OBSERVED SEVERAL CLAS #35676300J | Nov 3, 2023 POP/IN-VIO | $0 |
| Jun 30, 2023 | Construction CLASS - 2 EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION. AT THE TIME OF INSPECTION OBSERVED THAT AT 3RD FLOOR GYM ONE EXIT DOOR, AT 1ST FLOOR STAIR "A" ONE EXIT DOOR, 1ST FLOOR EXIT-8 (INSIDE) ONE EXIT DO #35676302N | Nov 3, 2023 POP/IN-VIO | $0 |
| Jun 30, 2023 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381. AT THE TIME OF INSPECTION OBSERVED THAT AT 3RD FL GYM 4 EMERGENCY EXIT LI #35676301L | Nov 3, 2023 POP/IN-VIO | $0 |
| Jul 20, 2022 | Construction CLASS - 2 RE-ISSUE #35591726Y-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT VARIOUS LOCATIONS THROUGHOUT ENTIRE BUILDING OBSERVED SEVERAL CLASSROOM DOORS WITH DEFECTIVE/MISSING DOOR CLOSERS #427 #425 #40 #35665112Z | Oct 21, 2022 POP/IN-VIO | $0 |
| Aug 23, 2021 | Construction CLASS - 2 RE-ISSUED #35498570K FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNERNOTED:AT 4TH FL DOOR #427,425,419,417,415,413;AT 3RD FL ENTIRE DOORS AT 2ND FL ENTIRE DOORS;AT 1ST FL ROOM #125,121,122,123 & 125 MISSING/B #35591726Y | Nov 19, 2021 POP/IN-VIO | $0 |
| Jun 16, 2020 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED OBSERVED CLASSROOM DOORS ST 4TH FLOOR ROOM 427,425,419,417,415,413,311,405,403,401,402,3RD FLOOR ROOM 301,302,303,307,313,315,317,319,319,322,326,325, #35498570K | Oct 2, 2020 POP/IN-VIO | $0 |
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2025 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION #07141 | DOB VIOLATION - ACTIVE |
| Nov 14, 2025 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION #07142 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2025 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Nov 14, 2025 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Jan 31, 2025 | Gas Piping - LL152 FTF-PL-PER Cycle 1, Sub-cycle D (premises is in Community District 11) | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2018 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device | Active |
None open.