Brooklyn · Block 4690 · Lot 1 · 11212

9323 Church Avenue

1 floors · 6,000 sq ft · built 1931 · class K1 · owner of record: Church Property Realty Corp.

7open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
408dto Gas piping inspection (2027 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 43 days
Keep the report on file (not filed with DOB)
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 17 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 408 days
Next cycle year 2027

Open violations

ECB / OATH (5)
IssuedViolationHearingBalance
Apr 6, 2022Boilers CLASS - 2
HOT WATER HEATER FLUE PIPE CORRODEDÝMUST INSTALL BVENT FLUE MATERIAL¨/LOOSE METAL FLANGE@CHIMNEY/CHIMNEY BASE 1/2 FULL/OPEN CEILING EXPOSED WOOD/NO COMBUSTION AIR/EXPOSED WIRES/DEBRIS/UNUSED OIL TANKS NOT LEGAL
#39059705J
Sep 7, 2022
IN VIOLATION
$0
Jul 21, 2006Boilers Hazardous
50AB/50CD/50EB4B FUCTON V.T. BOIL,10HP,NB57008,09L,1989,50A-BURN OUT COMBUST CHAMBER SEAL @LOWER HANHOLE.50B-OIL BURNER MALFUNCTION.SMOKE& OIL FUMES@BURNER FAN MOTOR 51-HAZARD OPERATE CONDITION OIL SEAL UNTIL.
#32051673N
Sep 18, 2006
WRITTEN OFF
$0
Jan 29, 2005Boilers Non-Hazardous
50A/50B/50C/50D FULTON VT BOILER 10HP NB57008 OIL,1989 50A)COMBUSTION CHAMBER SLEEVES DESERIORATED AROUND HANDHOLE OPENING REPLACE SCEEVES &SEAL 50B)IMPROPER ARRANGMENT OF THE BLOWDOWN VALVES 50C)BASEMENT
#32047047Y
Mar 14, 2005
WRITTEN OFF
$0
Feb 21, 2003Boilers Non-Hazardous
B4A/50A/50B/50C/50B/50D/50E/38/16/BQ9/36/32A. 50A NO DRAFTSTAT IN PLACE ON THE FLUE PIPE. 50B NO DISCHARGE PIPE ON THE SAFTY VALVE. 50C NO ANTI- SIPHON DEVICE ON THE FUEL OIL SUPPLY PIPING. 50D. NO SECONDARY SH
#32041276K
May 5, 2003
WRITTEN OFF
$0
Jun 19, 1998Boilers Non-Hazardous
16- BOILER NUMBER/INSPECTION CARD NOT DISPLAYED.
#32015311H
Aug 31, 1998
WRITTEN OFF
$0
DOB (1)
IssuedViolationStatus
Aug 16, 1993LOCAL LAW 62/91 - BOILERS

#20748
DOB VIOLATION - ACTIVE
DOB NOW Safety (1)
IssuedViolationStatus
Jan 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle D (premises is in Community District 17)
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 18, 2026, 10:26 AM ET. BBL 3046900001.