4 floors · 144,180 sq ft · built 1966 · class W1 · owner of record: Nyc Department Of Education
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Gas piping inspection (2026 cycle) Likely applies Local Law 152 · During 2026 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 9 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2026 in 63 days | Due this year |
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 63 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 144,180 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 184 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 184 days | Annual filing |
| Energy audit and retro-commissioning (2027) Likely applies Local Law 87 · Calendar year 2027 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 9067). Agency page | Dec 31, 2027 in 428 days | Next due 2027 |
| Annual boiler inspection (3 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-02-19 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Mar 2, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: EMERGENCY LIGHT DID NOT WORK WHEN TESTED AT, CAFETERIA "4 LIGHTS #35728894H | Mar 17, 2026 POP/IN-VIO | $0 |
| Mar 2, 2026 | Construction CLASS - 2 RE-ISSUE #35691616L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: MORTAR CRACKING ABOVE EXP 1. ABOVE NOTED LETTERS. CRACKEDBRICK EXP 2 A FEW CORRIDORS DOWN FROM EXIT M3. REMEDY: REPAIR AND/OR R #35728892Y | Mar 17, 2026 POP/IN-VIO | $0 |
| Mar 2, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: IN ELECTRIC METER ROOM, FIRE STOPPING WAS MISSING AROUND PIPES. REMEDY: PROVIDE/MAINTAIN FIRE STOPPING. #35728895J | Mar 17, 2026 POP/IN-VIO | $0 |
| Mar 2, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORSMOKE DOORS DO NOT SELF-CLOSE PROPERLY AT, 4TH FLR-SMOKE DOOR NEAR RM #411, AND 427. 3RD FLR-SMOKE DOOR NEAR RM #328. 2MD FLR-STAIRCASE "G". #35728893X | Mar 17, 2026 POP/IN-VIO | $0 |
| Mar 19, 2025 | Construction CLASS - 2 REISSUE#35679009H FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.MORTAR CRACKING AND FALLING AND ABOVE GRASS EXP 1 ABOVE NOTED LETTERS,CRACKED BRICK EXP 2 A FEW CORRIDOR DOWN FROM EXIT M3.REM:REPAIR AND/ #35691616L | Jul 8, 2025 POP/IN-VIO | $0 |
| Aug 13, 2024 | Boilers CLASS - 2 FEDERAL BOILER MODEL-NYPS2125. BTU-7,875,000. BOILER NOT REGISTERED. MISSING LADDER AND PLATFORM AT BOILERS. CORRECT VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION. #39121705Y | Aug 29, 2024 POP/IN-VIO | $0 |
| Aug 13, 2024 | Boilers CLASS - 2 FEDERAL BOILER MODEL-NYPS2125. BTU-7,875,000. BOILER NOT REGISTERED. ALSO MISSING LADDER AND PLATFORM BY BOILER. CORRECT VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION. #39121706X | Aug 29, 2024 POP/IN-VIO | $0 |
| Aug 13, 2024 | Boilers CLASS - 2 FEDERAL BOILER MODEL-NYPS2125. BTU-7,875,000. BOILER NOT REGISTERED. ALSO MISSING LADDER AND PLATFORM BY BOILER. CORRECT VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION. #39121707H | Aug 29, 2024 POP/IN-VIO | $0 |
| Apr 9, 2024 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. MORTAR CRACKINGAND FALLING OUT ABOVE GRASS AREA AT EXP. 1 ABOVE METAL LETTER, BRICKS CRACKING BY WINDOW EXP. 2 A FEW WINDOWS DOWN FROM EXIT M3. CRACKING OF #35679009H | May 15, 2024 POP/IN-VIO | $0 |
| Sep 25, 2018 | Boilers CLASS - 2 36,50. FOUND FEDERAL NYPS 2125 STEAM BOILER NOT REGISTERED; 50-MISSING LADDER AND WORK PLATFORM. REGISTER BOILER AND CORRECT ALL VIOLATING CONDITIONS. AND SUBMIT A CERTIFICATE OF CORRECTION. #32096043H | Nov 27, 2018 POP/IN-VIO | $0 |
| Sep 25, 2018 | Boilers CLASS - 2 36,50. FOUND FEDERAL MOD #NYPS2125 STEAM BOILER NOT REGISTERED. 50- MISSING LADDER AND WORK PLATFORM. REGISTER BOILER AND CORRECT ALL VIOLATING CONDITIONS. SUBMIT A CERTIFICATE OF CORRECTION. #32096045L | Nov 27, 2018 POP/IN-VIO | $0 |
| Issued | Violation | Status |
|---|---|---|
| Aug 4, 2021 | ELEVATOR #9027/706582 | DOB VIOLATION - ACTIVE |
| Aug 4, 2021 | ELEVATOR #9027/706583 | DOB VIOLATION - ACTIVE |
| Jan 13, 1997 | LOCAL LAW 10/81 - ELEVATOR #03986 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Oct 2, 2026 | Elevators FTF-VT-CAT1-CO Violation Issued-Failure To File 2025 Cat1 Test Report | Active |
| Oct 10, 2025 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device | Active |
| Oct 23, 2023 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction | Active |
| Aug 25, 2023 | Elevators FTF-VT-PER-CO Violation Issued-Failure To File 2022 Periodic Inspection Report | Active |
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Oct 2, 2026 | DOB Safety | Elevators: Violation Issued-Failure To File 2025 Cat1 Test Report | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 29, 2026, 10:12 PM ET. BBL 4090670001.