Queens · Block 10819 · Lot 1 · 11423

92-41 190 Street

6 floors · 324 apartments · 316,540 sq ft · built 1952 · class D1 · owner of record: Rdh Crystal Gardens Llc

414open violations
$16,875ECB/OATH penalties owed
63HPD class C (immediately hazardous)
62dto Bedbug annual filing

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 62 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 62 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 78 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 316,540 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 183 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 183 days
Annual filing
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

Sep 1, 2027
in 306 days
Registered through 2027-09-01
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 427 days
Next cycle year 2027
Energy audit and retro-commissioning (2029) Likely applies
Local Law 87 · Calendar year 2029
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 10819). Agency page

Dec 31, 2029
in 1158 days
Next due 2029
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-02 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (30) · $16,875 owed
IssuedViolationHearingBalance
Sep 29, 2026Elevators CLASS - 1
NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTALL DLM A
#39205979J
Dec 8, 2026
PENDING
$3,125
Sep 15, 2026Elevators CLASS - 1
NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTALL DLM A
#39204081Z
Nov 24, 2026
PENDING
$1,250
Feb 20, 2026Elevators CLASS - 1
CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION,NO (DLM) DOOR LOCK MONITORING INSTALLED ON ELEVATOR CONTOLLER AS MANDATED BY
#39177925Z
Jun 16, 2026
DEFAULT
$6,250
Jan 14, 2026Construction CLASS - 2
IN GARAGE AT SPOT # 14, CONCRETE SPALLING EXPOSING REBAR,ALSO NOTED COLUMN HAS HAIRLINE VERTICAL CRACK., REPAIR AND/OR REPLACE
#39173778J
Apr 28, 2026
DEFAULT
$6,250
Sep 9, 2025Elevators CLASS - 1
THE ONLY ELEVATOR IN BUILDING (OR SECTION OF BUILDING) OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. REMEDY: RESTORE TO SERVICE IMM
#39159649M
Dec 23, 2025
DEFAULT
$0
Jun 30, 2025Elevators CLASS - 1
: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY
#39152302L
Oct 14, 2025
IN VIOLATION
$0
Feb 27, 2025Elevators CLASS - 1
NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTALL DLM A
#39139768R
May 6, 2025
DEFAULT
$0
Oct 30, 2024Elevators CLASS - 1
DLM NOT WORKING. REPAIR. PROVIDE ACCESS TO MACHINE ROOM.
#39128972K
Feb 11, 2025
IN VIOLATION
$0
Jun 3, 2024Elevators CLASS - 1
NO DLM INSTALLED ON THIS CONTROLLER AS MANDATED. BY CODE A-17.1 SECTION 3.10.12 OF THE NTCBC 2014 CODE. REPAIR RETURN WALL LARGE GAP BETWEEN CAR DOOR AND THE RETURN WALL.
#39115842J
Aug 13, 2024
IN VIOLATION
$0
Apr 29, 2024Elevators CLASS - 1
NO DLM INSTALLED ON THIS CONTROLLER AS MANDATED BY CODE A-17.1 OF THE NYCBC 2014 CODE SECTION 3.10.12 . RECURRING CONDITION VIOLATION NUMBERS ( 39107652Z , 39104258R , 39094132P ). DAMAGE VISION PANEL GLASS 5TH
#39112966H
Jul 9, 2024
DEFAULT
$0
Mar 4, 2024Elevators CLASS - 1
DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). NO DLM INSTALLED ON THIS CONTROLLER AS MANDATED BY CODE A-17.1 OF THE NYCBC 2014 CODE SECTION 3.10.12. RECURRING CONDITION VIOLATION NUMBERS 39094132
#39107652Z
Jun 18, 2024
IN VIOLATION
$0
Jan 25, 2024Elevators CLASS - 1
NO DLM INSTALLED ON THIS CONTROLLER. AS MANDATED BY NYCBC 2014 BUILDING CODE SECTION 3.10.12. RECURRING CONDITION FIRST VIOLATION NUMBER 39087052J. CLEARLY LABELED THE MAIN LINE AND CONTROLLER WITH THE CITY ID
#39104269M
Nov 12, 2024
DEFAULT
$0
Jan 24, 2024Elevators CLASS - 1
NO DLM INSTALLED ON THIS CONTROLLER . AS MANDATED BY CODE A17.1 SECTION 3.10.12 OF THE NYCBC CODE 2014 RECURRING CONDITION. FIRST VIOLATION NUMBER 39094132R ON 9/5/2023. GOVERNOR CABLE DEFECTIVE RUSTED.
#39104258R
Oct 29, 2024
IN VIOLATION
$0
Dec 20, 2023Elevators CLASS - 1
(05-A-10) CEASE USE ITEM. DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH/ DISABLED AND RENDERED INOPERATIVE. THIS IS A SAFETY DEVICE TO ENSURE ELEVATOR PASSENGERS' SAFETY. REPAIR RESTRICTOR AND CONTACT NYCDOB AT E
#39101924X
Mar 26, 2024
IN VIOLATION
$0
Nov 15, 2023Elevators CLASS - 1
DLM IS NOT WORKING. REPAIR DLM. LOBBY DOOR RUBBING. ADJUST LOBBY DOOR
#39099448Y
Jan 23, 2024
IN VIOLATION
$0
Sep 5, 2023Elevators CLASS - 1
NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTALL DLM A
#39094132P
Dec 12, 2023
IN VIOLATION
$0
May 24, 2023Elevators CLASS - 1
NO DLM INSTALLED ON THIS CONTROLLER AS MANDATED BY NYCBC 2014 CODE SECTION 3.10.12 K3.
#39087052J
Aug 1, 2023
IN VIOLATION
$0
Sep 12, 2022Elevators CLASS - 1
DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO FIREMANS' SERVICE PRESENT IN CONTROLLER. INSTALL FIREMANS' SERVICE SO DLM IS IN COMPLIANCE WITH SECTION 3.10.12 OF APPENDIX K3. ADJUST LEVELING.
#39069836Z
Nov 1, 2022
ADMIT/IN-VIO
$0
Jul 12, 2022Elevators CLASS - 1
DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). 5TH FLOOR DOOR LOCK DEFECTIVE DOOR INTERLOCK CAN BE OPEN WITH OUT THE ELEVATOR AT THE LANDING FALL HAZARD (CU). PROVIDE DLM AS PER A17.1 OF THE NYCBC
#39065621N
Aug 30, 2022
ADMIT/IN-VIO
$0
Apr 30, 2021Elevators CLASS - 1
42M7 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3/10/12 OF APPENDIX (K3) OF THE 2014 NYC BC.THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGERS SAFETY.REMEMDY:FILE APPLICATION,INSTALL
#38274040J
Aug 10, 2021
IN VIOLATION
$0
Apr 26, 2021Elevators CLASS - 1
CEASE USE ITEMS : IN CAR STOP SWITCH INOPERATIVE , REPAIR / ZONE LOCK INOPERATIVE , REPLACE UNIT / NON CEASE USE ITEM NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 O
#39040037N
Jun 15, 2021
IN VIOLATION
$0
Jan 22, 2019Construction CLASS - 3
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: APART MENT 3-0 WINDOWS HAS BUILDED UP CONDENSATION AROUND ALL THE WINDOWS THROUGHOUT ENTIRE APARTMENT. SOME WINDOWS HAS ICICLES. ALSO LEADING TO
#35375426X
Apr 2, 2019
ADMIT/IN-VIO
$0
Mar 13, 2018Construction CLASS - 1
5A10,8V1-5A10)DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH DISABLED AND RENDERED INOPERATIVE. THIS IS A SAFETY DEVICE TO ENSURE ELEVATOR PASSENGERS SAFETY. REPAIR RESTRICTOR AND CONTACT NYCDOB AT EIR@BUILDINGS.N
#38262033N
May 1, 2018
IN VIOLATION
$0
Dec 14, 2017Elevators CLASS - 1
05A10,08V01,40G11-05A10)RESTRICTOR IS NOT OPERATIVE. THIS IS A SAFETY DEVICE. 08V01)PROVIDE ADJUSTMENT FOR LEVEL. 40G11)REPLACE FUSE.
#38259987R
Jan 30, 2018
IN VIOLATION
$0
Nov 10, 2014Elevators CLASS - 2
10H11,59O02,16J01,21D10,05I11,39I11,08V01. 39I11-CAR TOP SHACKLE SPRINGS DAMAGED; 16J01-ADJUST HOISTWAY DOORS FOR SMOTH CLOSE; 21D10-INTERLOCK KEEPERS UNSECURED ON HOISTWAY DOOR; 05I11-CAR DOOR VISION GLASS DAM
#38233474X
Dec 30, 2014
ADMIT/IN-VIO
$0
Nov 20, 2013Construction CLASS - 2
OCCUPANCY CONTRARY TO THAT ALLOWED BY THE BLDG DEPT RECORDS. PREMISES FILE JOB PERMIT #410204363 TO LEGALIZE LAUNDRY ROOM FOR USE BY BLDG TENANTS ONLY. AT TIME OF INSPECTION OBSERVED THE LAUNDRY ROOM TO OCCUPIE
#35067859R
Jan 28, 2014
IN VIOLATION
$0
May 8, 2007Zoning Non-Hazardous
ILLEGAL USE IN A RESIDENTIAL ZONING DISTRICT.R5-COMMERCIAL LAUNDROMA/PRIVATELY MAINTAINED OPERATING FROM BASEMENT LEVEL EXTENSION INSTALLED AT SOUTH COURTYARD OF DWELLING.REMEDY:DISCONTINUE ILLEGAL USE.
#34578355L
Jul 21, 2009
IN VIOLATION
$0
Oct 30, 2004Construction Non-Hazardous
OCCUPANCY CONTRARY TO CERTIFICATE OF OCCUPANCY #Q79891 WHICH INDICATESBASEMENT TO BE OCCUPIED AS GARAGE, STORAGE, BOILER ROOM, TWO PROF. OFFICES AND 5 APT'S APT. BASEMENT FRONT ON WOODHULL AVE IS NOW OCCUPIED
#34457306Y
Mar 29, 2005
IN VIOLATION
$0
Nov 22, 2000Local Law Non-Hazardous
FAILURE TO PROVIDE ELEVATOR LANDING SIGN FOR ELEVATOR BANK ON FLOOR 2-6.FAILURE TO PROVIDE 3-INCH HIGH ALPHABETIC LETTER OF IDENTIFICATION FOR ELEVATOR BANK AND FOR OPEN STAIR ON FLOOR 1-6.FAILURE TO PROVIDE 3
#34260953L
Jul 5, 2005
IN VIOLATION
$0
Aug 24, 1993Elevators Non-Hazardous
74M,75#,17I,15L,62L. 74 PROVIDE NYC DEVICE #AS REQUIRED. 75 CONDUCT A 5YR. TEST PROPERLY TAG GOVERNOR AND FILE FORM ELEV.3 . 17 CAR DOOR 2ND - 6 FLR. HOISTWAY DOORS. 15 4FLR. DOOR STICKING IN OPEN POSITION.
#38036233M
Nov 9, 1993
WRITTEN OFF
$0
DOB (94)
IssuedViolationStatus
Jan 14, 2026CONSTRUCTION
FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED AT GARAGE LEVEL AREAS OF SPALLING CONCRETE EXPOSING REBAR, AREAS MISSING CONCRETE FINISH AND VERTICAL CRACKS ON COLUMNS.
#26-00174
DOB VIOLATION - ACTIVE
Dec 1, 2024FAILURE TO POST ENERGY GRADE/SCORE
FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
#2401809
DOB VIOLATION - ACTIVE
Feb 21, 2024FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00082
DOB VIOLATION - ACTIVE
Oct 4, 2023FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#02350
DOB VIOLATION - ACTIVE
Oct 4, 2023FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#02349
DOB VIOLATION - ACTIVE
Feb 22, 2022NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
#01654
DOB VIOLATION - ACTIVE
Dec 17, 2021NON-RESIDENTIAL ELEVATOR PERIODIC INSPECTION/TEST
FAILURE TO PERFORM CATEGORY 5 INSPECTION
#00864
DOB VIOLATION - ACTIVE
Dec 17, 2021NON-RESIDENTIAL ELEVATOR PERIODIC INSPECTION/TEST
FAILURE TO PERFORM CATEGORY 5 INSPECTION
#00868
DOB VIOLATION - ACTIVE
Dec 17, 2021NON-RESIDENTIAL ELEVATOR PERIODIC INSPECTION/TEST
FAILURE TO PERFORM CATEGORY 5 INSPECTION
#00867
DOB VIOLATION - ACTIVE
Dec 17, 2021NON-RESIDENTIAL ELEVATOR PERIODIC INSPECTION/TEST
FAILURE TO PERFORM CATEGORY 5 INSPECTION
#00869
DOB VIOLATION - ACTIVE
Dec 17, 2021NON-RESIDENTIAL ELEVATOR PERIODIC INSPECTION/TEST
FAILURE TO PERFORM CATEGORY 5 INSPECTION
#00866
DOB VIOLATION - ACTIVE
Dec 17, 2021NON-RESIDENTIAL ELEVATOR PERIODIC INSPECTION/TEST
FAILURE TO PERFORM CATEGORY 5 INSPECTION
#00865
DOB VIOLATION - ACTIVE
Jul 21, 2021FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00574
DOB VIOLATION - ACTIVE
Jul 21, 2021FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00573
DOB VIOLATION - ACTIVE
Nov 8, 2019LOW PRESSURE BOILER
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
#15338
DOB VIOLATION - ACTIVE
Oct 17, 2019ELEVATOR

#9027/662234
DOB VIOLATION - ACTIVE
Oct 17, 2019ELEVATOR

#9027/662237
DOB VIOLATION - ACTIVE
Feb 16, 2019FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#00792
DOB VIOLATION - ACTIVE
Nov 8, 2018ELEVATOR

#9027/640165
DOB VIOLATION - ACTIVE
Nov 8, 2018ELEVATOR

#9027/640164
DOB VIOLATION - ACTIVE
Nov 8, 2018ELEVATOR

#9027/640167
DOB VIOLATION - ACTIVE
Jun 13, 2018FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00487
DOB VIOLATION - ACTIVE
Mar 7, 2018FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00625
DOB VIOLATION - ACTIVE
Jan 3, 2017(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
#07509
DOB VIOLATION - ACTIVE
Jan 3, 2017(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
#07510
DOB VIOLATION - ACTIVE
Jan 3, 2017(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
#07508
DOB VIOLATION - ACTIVE
Nov 2, 2015FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#00687
DOB VIOLATION - ACTIVE
Aug 2, 2015FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#00993
DOB VIOLATION - ACTIVE
May 2, 2015FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#01468
DOB VIOLATION - ACTIVE
Jun 6, 2014FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#01485
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#07407
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#07411
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#07410
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#07406
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#07409
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#07408
DOB VIOLATION - ACTIVE
May 15, 2014LOW PRESSURE BOILER
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2012 INSPECTION REPORT
#17652
DOB VIOLATION - ACTIVE
May 15, 2014LOW PRESSURE BOILER
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2012 INSPECTION REPORT
#20513
DOB VIOLATION - ACTIVE
Mar 31, 2014ELEVATOR ANNUAL INSPECTION / TEST
VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
#05256
DOB VIOLATION - ACTIVE
Jun 3, 2013FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#01709
DOB VIOLATION - ACTIVE
Jan 31, 2013NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 7A TECHNICAL REPORT BY 02/21/2012
#01458
DOB VIOLATION - ACTIVE
May 3, 2012FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#03173
DOB VIOLATION - ACTIVE
Jan 1, 2012FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#02864
DOB VIOLATION - ACTIVE
Dec 13, 2011ELEVATOR ANNUAL INSPECTION / TEST
VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
#04515
DOB VIOLATION - ACTIVE
Dec 13, 2011ELEVATOR ANNUAL INSPECTION / TEST
VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
#04514
DOB VIOLATION - ACTIVE
Dec 13, 2011ELEVATOR ANNUAL INSPECTION / TEST
VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
#04516
DOB VIOLATION - ACTIVE
Oct 8, 2010ELEVATOR ANNUAL INSPECTION / TEST

#05590
DOB VIOLATION - ACTIVE
Oct 8, 2010ELEVATOR ANNUAL INSPECTION / TEST

#05589
DOB VIOLATION - ACTIVE
Oct 8, 2010ELEVATOR ANNUAL INSPECTION / TEST

#05591
DOB VIOLATION - ACTIVE
Oct 8, 2010ELEVATOR ANNUAL INSPECTION / TEST

#05592
DOB VIOLATION - ACTIVE
Sep 10, 2008ELEVATOR

#2203H241578
DOB VIOLATION - ACTIVE
Sep 10, 2008ELEVATOR

#2203H241580
DOB VIOLATION - ACTIVE
Sep 10, 2008ELEVATOR

#2203H241579
DOB VIOLATION - ACTIVE
Sep 10, 2008ELEVATOR

#1993H241437
DOB VIOLATION - ACTIVE
Sep 10, 2008ELEVATOR

#1993H241440
DOB VIOLATION - ACTIVE
Sep 10, 2008ELEVATOR

#1993H241438
DOB VIOLATION - ACTIVE
Aug 21, 2008CONSTRUCTION

#1202JNG
DOB VIOLATION - ACTIVE
Sep 10, 2007CONSTRUCTION

#1205GM
DOB VIOLATION - ACTIVE
Sep 1, 2007CONSTRUCTION

#1201MJ
DOB VIOLATION - ACTIVE
Oct 1, 2005LOCAL LAW 10/81 - ELEVATOR

#04587
DOB VIOLATION - ACTIVE

Showing 60 of 94. Full list on the agency site.

DOB NOW Safety (136)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Report
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Dec 1, 2024Energy Grade - LL33 FTP-EN-EGRDEA
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Feb 21, 2024AEUHAZ FTC-AEU-HAZ
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 4, 2023AEUHAZ FTC-AEU-HAZ
Active
Oct 4, 2023AEUHAZ FTC-AEU-HAZ
Active
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Report
Active

Showing 60 of 136. Full list on the agency site.

HPD (154) · C 63 · B 53 · A 38
IssuedClassViolationCorrect by
Oct 26, 2026CApt 6B · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''A-I''Nov 21, 2026
Oct 26, 2026CApt 6B · § 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING CONSISTING OF KICK DOWN DOOR STOPPER IN THE ENTRANCE LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''A-I''Nov 9, 2026
Jun 22, 2026CApt 6L · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6L, 6th STORY, 1st APARTMENT FROM WEST AT NORTHJul 18, 2026
Jun 4, 2026A§27-2104(B) HMC POST A PROPER NOTICE REGARDING RENT STABILIZATION LAW, IN A FORM APPROVED BY THE COMMISSIONER, IN A CONSPICUOUS LOCATION WITHIN THE COMMON AREA AT THE BUILDINGS ENTRANCE. FOR MORE INFORMATION ABOUT SIGNAGE REQUIREMENTS, PLEASE VISIT: HTTPS://WWW.NYC.GOV/SITE/HPD/SERVICES-AND-INFORMASep 7, 2026
Feb 11, 2026BApt 5B · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQFT AT EAST WALL IN THE BATHROOM LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 18296518 ISSUED 13-OCT-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017Mar 18, 2026
Jan 20, 2026C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH WEST SECTION,BLDG 91-30 AT COMPACTOR CLOSET, 6th STORYFeb 3, 2026
Jan 20, 2026C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE BULKHEAD DOOR TO ROOF FRAME,WEST SECTION,BLDG 91-30 AT PUBLIC HALL, 6th STORYFeb 3, 2026
Dec 5, 2025C§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING SELF-LOCKABLE PUSH BAR ASSEMBLY, BULKHEAD DOOR TO ROOF , 6th STORY, SECTION ''A-I'', AT SOUTHDec 11, 2025
Dec 4, 2025C§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING SELF LOCKABLE PUSH BAR ASSEMBLY ON BULKHEAD DOOR TO ROOF , SECTION ''A-I'', AT SOUTHDec 10, 2025
Nov 6, 2025CApt 4F · § 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF KEY OPERATED LOCK INSTALLED AT DOOR TO ROOM WITH FIRE ESCAPE WINDOW IN THE 4th ROOM FROM EAST AT SOUTH LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM WEST AT NORTHNov 12, 2025
Oct 14, 2025CApt 5B · § 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT APARTMENT ENTRANCE DOOR IN THE ENTRANCE LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM NORTH AT EASTOct 28, 2025
Oct 14, 2025BApt 5B · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQFT AT NORTH WALL IN THE BATHROOM LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM NORTH AT EASTNov 18, 2025
Oct 14, 2025CApt 5B · § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK ACTIVE LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM NORTH AT EASTOct 20, 2025
Jan 22, 2025C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH ASSEMBLY AT BUILDING ENTRANCE DOOR AT PUBLIC HALL, 1st STORYFeb 5, 2025
Jan 17, 2025BApt 1G · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THEN 10 SQ FEET AT THE CEILING IN THE KITCHEN LOCATED AT APT 1G, 1st STORY, 4th APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 17292390 ISSUED 18-SEP-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27Feb 21, 2025
Nov 29, 2024C§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF SELF LOCKABLE PANIC BAR INSTALLED ON WEST BULKHEAD DOOR TO ROOF AT PUBLIC HALL, 6th STORY, SECTION ''WEST''Dec 5, 2024
Oct 22, 2024C§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF AN UNACCEPTABLE ELECTROMAGNETIC LOCKING DEVICE INSTALLED AT BUILDING ENTRANCE DOOR AT PUBLIC HALL, 1st STORYOct 28, 2024
Oct 22, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR AND FRAME AT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 3rd STORYNov 5, 2024
Oct 22, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT FIRE DOOR SEPARATING NORTH AND SOUTH SECTIONS AT PUBLIC HALL, 6th STORYNov 5, 2024
Oct 22, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR AND FRAME AT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 6th STORYNov 5, 2024
Oct 22, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR AND FRAME AT FIRE DOOR SEPARATING NORTH AND SOUTH SECTIONS AT PUBLIC HALL, 4th STORYNov 5, 2024
Oct 22, 2024C§ 27-2005 ADM CODE FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS WEST 1 STACK AT NORTH BUILDING FRONT AT FIRE ESCAPEOct 28, 2024
Oct 22, 2024C§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF UNACCEPTABLE ELECTROMAGNETIC LOCKING DEVICE INSTALLED AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORYOct 28, 2024
Oct 8, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORYOct 22, 2024
Oct 8, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH COMPACTOR CLOSET DOOR AT PUBLIC HALL, 1st STORYOct 22, 2024
Sep 24, 2024C§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF AN UNACCEPTABLE ELECTROMAGNETIC LOCKING DEVICE INSTALLED AT FRONT ENTRANCE DOOR AT PUBLIC HALL, 1st STORYSep 30, 2024
Sep 19, 2024CApt 1G · § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM WEST AT NORTH WALL, NORTH WALL, SOUTH WALL, EAST WALL, WEST WALL, Oct 13, 2024
Sep 16, 2024C§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF PADLOCKABLE SLIDE BOLT INSTALLED METAL FENCE GATE TO BUILDING FRONTSep 22, 2024
Jul 30, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORYAug 13, 2024
Jul 15, 2024CApt 3H · § 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 3H, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''A-I''Jul 29, 2024
Jul 15, 2024CApt 3H · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 3H, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''A-I''Aug 10, 2024
Jul 15, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 3rd STORY, SECTION ''A-I''Jul 29, 2024
Jul 15, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 1st STORY, SECTION ''A-I''Jul 29, 2024
Jul 5, 2024BApt 1G · § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR ,MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM NORTH AT EASTAug 9, 2024
Jul 5, 2024AApt 1G · § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AND CEILING IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM NORTH AT EASTOct 8, 2024
Jul 5, 2024BApt 1G · § 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM NORTH AT EASTAug 9, 2024
Jul 5, 2024AApt 1G · § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE BATHROOM LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM NORTH AT EASTOct 8, 2024
Jul 5, 2024CApt 1G · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM NORTH AT EASTJul 31, 2024
Jul 5, 2024CApt 1G · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM NORTH AT EASTJul 31, 2024
Mar 25, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES FIRE DOOR AT PUBLIC HALL, 2nd STORYApr 8, 2024
Mar 18, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH ASSEMBLY SET AT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 1st STORY, SECTION ''A-I''Apr 1, 2024
Mar 18, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH ASSEMBLY SET AT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 3rd STORY, SECTION ''A-I''Apr 1, 2024
Mar 18, 2024BApt 3H · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROXIMATELY 25 SQUARE FEET AT CEILING AND SOUTH WALL IN THE BATHROOM LOCATED AT APT 3H, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''A-I''Apr 22, 2024
Feb 5, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 5th STORYFeb 19, 2024
Feb 5, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT HOPPER AT COMPACTOR CLOSET AT PUBLIC HALL, 5th STORYFeb 19, 2024
Feb 5, 2024C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE FIRE DOOR AND FRAME SEPARATING EAST AND WEST SECTION AT PUBLIC HALL, 5th STORYFeb 19, 2024
Nov 30, 2023B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AT PUBLIC HALL, 6th STORYJan 4, 2024
Nov 30, 2023B§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL, 6th STORYJan 4, 2024
May 26, 2023C§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOCKING DEVICE AT BUILDING ENTRANCE DOOR AT PUBLIC HALL, 1st STORYJun 1, 2023
May 24, 2023C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGE BROKEN AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORYJun 7, 2023
May 24, 2023A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING AT PUBLIC HALL, 1st STORYAug 27, 2023
Feb 28, 2023CApt 3A · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... 20 SQUARE FEET AT WEST WALL, 4 SQUARE FEET AT NORTH WALL, 4 SQUARE FEET AT SOUTH WALL, 2 SQUARE FEET AT CEILING IN THE BATHROOM LOCATED AT APT 3A, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''190-25'', 1sMar 26, 2023
Feb 28, 2023CApt 3A · § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS XRF TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 AND IS PRESUMED LEAD PAINT AS SET FORTH IN (28 RCNY §11-07(b)) AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE-USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2) 1stMar 24, 2023
Oct 20, 2022BApt 1L · § 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES ... IN THE ENTIRE APARTMENT LOCATED AT APT 1L, 1st STORY, 2nd APARTMENT FROM SOUTH AT WESTNov 24, 2022
Jun 8, 2022C§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE MORTISE LOCK AT ENTRANCE DOOR TO BUILDINGJun 14, 2022
May 17, 2022BApt 4E · § 27-2056.7 AND 27-2056.17 ADM CODE -CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 4E, 4th STORY, 2nd APARTMENT FROM SOUTH AT WESTJun 21, 2022
May 12, 2022A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT EAST WALL AT PUBLIC HALL, 1st STORYAug 15, 2022
May 12, 2022A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT WEST WALL AT BULKHEAD AT PUBLIC HALL, SECTION AT SOUTHAug 15, 2022
May 12, 2022B§ 27-2005 ADM CODE FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS SECOND STACK FROM SOUTH AT WEST, AT BUILDING FRONTJun 16, 2022
May 12, 2022A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT NORTH WALL AT BULKHEAD , SECTION AT NORTHAug 15, 2022

Showing 60 of 154. Full list on the agency site.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 26, 2026HPD CHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''A-I''Open
Oct 26, 2026HPD C§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING CONSISTING OF KICK DOWN DOOR STOPPER IN THE ENTRANCE LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''A-I''Open
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test ReportOpen
Sep 29, 2026ECBElevators: NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTALL DLM AOpen
Sep 15, 2026ECBElevators: NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTALL DLM AOpen
Jul 22, 2026HPD C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE FRAME IN THE ENTRANCE LOCATED AT APT 6L, 6th STORY, 1st APARTMENT FROM SOUTH AT WESTClosed

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 30, 2026, 5:20 PM ET. BBL 4108190001.