Queens · Block 9155 · Lot 25 · 11417

90-15 Sutter Avenue

4 floors · 105,880 sq ft · built 1926 · class W1 · owner of record: Nyc Department Of Education

38open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
189dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 68 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 105,880 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 189 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 189 days
Annual filing
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 10 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 799 days
Next cycle year 2028
Energy audit and retro-commissioning (2035) Likely applies
Local Law 87 · Calendar year 2035
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 9155). Agency page

Dec 31, 2035
in 3355 days
Next due 2035
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-02-19 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (23)
IssuedViolationHearingBalance
Apr 23, 2026Construction CLASS - 2
REISSUED ECB#35692038N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT THE ROOF TOP OLD SCHOOL MASONRY AIR VENT SHAFT HAS MISSING CAP/COVER.REM:REPAIR AND/OR REPLACE.
#35732387P
May 26, 2026
POP/IN-VIO
$0
Apr 23, 2026Construction CLASS - 2
REISSUED ECB#35692033Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT THE ROOF TOP OLD SCHOOL MINI SPLIT CONDENSER WITH NO BRACKET,DAMAGE OR PROPER SUPPORT.REM:REPAIR AND/OR REPLACE.
#35732391H
May 26, 2026
POP/IN-VIO
$0
Apr 23, 2026Construction CLASS - 2
REISSUED ECB#35692035M EXIT DOORS NOT SELF CLOSING.NOTED EXIT DOORS NOT SELF CLOSING AT EXITS#6,#8,#14,#17.REM:REPAIR AND/OR REPLACE.
#35732390X
May 26, 2026
POP/IN-VIO
$0
Apr 23, 2026Construction CLASS - 2
REISSUED ECB#35692037L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT CELLAR BOILER ROOM WATER LEADING THROUGH AIR VENT SHAFT WITH MISSING CAP/COVER AT THE ROOF LEVEL.REM:REPAIR AND/OR REPLACE.
#35732388R
May 26, 2026
POP/IN-VIO
$0
Apr 23, 2026Construction CLASS - 2
REISSUED ECB#35692036J FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED SMOKE DOORS NOT CLOSING PROPERTY AT:4TH FLOOR CORRIDOR BYROOM#456;2ND FLOOR STAIR A,1ST FLOOR STAIR A AND B.REM:REPAIR AND/OR R
#35732389Z
May 26, 2026
POP/IN-VIO
$0
Apr 8, 2025Construction CLASS - 2
REISSUE #35672992L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT ROOFTOP, MASONRY AIR VENT SHAFT IS MISSING CAP/COVER. REMEDY: REPAIR AND/OR REPLACE.
#35692038N
May 16, 2025
POP/IN-VIO
$0
Apr 8, 2025Construction CLASS - 2
REISSUE #35678948L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT CELLAR BOILER ROOM, WATER LEAKING THROUGH AIR VENT SHAFTWITH MISSING COVER AT ROOF LEVEL. REMEDY: REPAIR AND/OR REPLACE.
#35692037L
May 16, 2025
POP/IN-VIO
$0
Apr 8, 2025Construction CLASS - 2
REISSUE #35682600M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED INTERIOR FPSC DOORS NOT CLOSING PROPERLY: 4TH FL CORRIDOR SMOKE DOOR BY RM #456, 2ND FL STAIR A, 1ST FL STAIR A AND B, EAST SMALL
#35692036J
May 16, 2025
POP/IN-VIO
$0
Apr 8, 2025Construction CLASS - 2
REISSUE #35682601H. EXIT DOOR NOT SELF-CLOSING. NOTED EXTERIOR DOORS AT EXIT #6,8, 14 AND 17 NOT OPENING OR CLOSING PROPERLY WHEN TESTED. CORRODED SADDLES AND RUBBING ON FRAMES. REMEDY: REPAIR/REPLACE DOOR.
#35692035H
May 16, 2025
POP/IN-VIO
$0
Apr 8, 2025Construction CLASS - 2
REISSUE #35682603H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT TOP ROOF, ADJACENT TO MINI SHAFT, MINI SPLIT CONDENSOR IS LOOSE WITH NO BROCHET, DUNNAGE OR PROPER SUPPORT PAD FOR THE UNIT TO
#35692033Y
May 16, 2025
POP/IN-VIO
$0
Apr 25, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT TOP ROOF LEVEL ADJACENT TO SHAFT A MINI SPLIT CORDERSOR UNIT IS LOOSE NO DAMAGE OR PROPER SUPPORT PROVIDED FOR THE UNIT TO SIT ON.REM:REPAIR AND/OR
#35682603H
Jul 2, 2024
POP/IN-VIO
$0
Apr 25, 2024Construction CLASS - 2
REISSUE #35672992L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT OLD BUILDING/TOP ROOF, MASONRY AIR VENT SHAFT IS MISSINGCAP 1 COVER, ALLOWING ELEMENTS AND DEBRIS TO ENTER THE SHAFTWAY. REMED
#35678947J
Aug 20, 2024
POP/IN-VIO
$0
Apr 25, 2024Construction CLASS - 2
EXIT DOOR NOT SELF CLOSING.NOTED EXTERIOR EXIT DOORS AT EXITS#14 IN AUDITORIUM EXIT#6 IN GYM & EXIT#8 NOT CLOSING OR OPENING PROPERLY DUE TORUSTED SADDLES & RUBBING OR FRAME.REM:REPAIR AND/OR REPLACE DOOR.
#35682601Y
Jul 2, 2024
POP/IN-VIO
$0
Apr 25, 2024Construction CLASS - 2
REISSUE #35672991J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT CELLAR LEVEL BOILER ROOM, NOTED WATER LEAK THROUGH AIR VENT SHAFT WITH MISSING COVER AT ROOF LEVEL. ADDITIONALLY WATER PENETRATION D
#35678948L
Aug 20, 2024
POP/IN-VIO
$0
Apr 25, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED THE PROOF SELF CLOSING INTERIOR DOORS NOT CLOSING PROPERLY.AT 4TH FL SMOKE DOORSBY RM#456,2ND FL STAIR B & A AND SMOKE DOOR BY RM 256.AT 1ST FL STAIR
#35682600M
Jul 2, 2024
POP/IN-VIO
$0
Jun 8, 2023Construction CLASS - 2
REISSUE #35650869Z FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: AT CELLAR AIR VENT DIRECT FROM CELLAR TO ROOF LEAK CAUSED BY MISSING CAP ON AIR SHAFT VENT. REMEDY: REPAIR AND/OR REPLACE
#35672991J
Sep 27, 2023
POP/IN-VIO
$0
Jun 8, 2023Construction CLASS - 2
REISSUE #35650868R FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: AT ROOFTOP CLAY-MASONRY AIR VENT SHAFT MISSING A CAPS/COVER. REMEDY: REPAIR/AND OR REPLACE
#35672992L
Sep 27, 2023
POP/IN-VIO
$0
Apr 20, 2022Construction CLASS - 2
REISSUE#35495281K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED AT(CELLAR)BOILER ROOM,WATER LEAK COMING FROM THE AIR VENT SHAFTWAY WHERE THE CAP/COVER IS MISSING(ROOF LEVEL).PHOTO'S TAKEN
#35650869Z
Jul 26, 2022
POP/IN-VIO
$0
Apr 20, 2022Construction CLASS - 2
REISSUE#35495278J FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED AT ROOF LEVEL,MASONRY AIR SHAFT IS MISSING THE VENT CAP/COVER ALLOWING ELEMENTS FROM WEATHER & DEBRIS TO ENTER THE SHAFTWAY
#35650868R
Jul 26, 2022
POP/IN-VIO
$0
Apr 28, 2020Construction CLASS - 2
REISSUE #35381496M FAILURE TO MAINATIN BUIDLING IN CODE COMPLIANT MANNER NOTED WATER PENETRATING INTO THE CELLARS BOILER ROOM THROUGH THE ROOD AIR VENT SHAFTWAY REPAIR AND OR REPLACE
#35495281K
Aug 18, 2020
POP/IN-VIO
$0
Apr 28, 2020Construction CLASS - 2
REISSUE #35381493R FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER AT ROOF MASONRY AIR SHAFT IS MISSING ITS VENT CAP ALSO A/C UNIT CONDENDER HAVE NO DUNNAGE SITTING ROOF TOP PEBBLE REPAIR AND OR REPLACE
#35495278J
Aug 18, 2020
POP/IN-VIO
$0
Apr 15, 2019Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT CELLAR, BOILER ROOM, WATER LEAK THROUGH ROOF AIR VENT. REMEDY: REPAIR AND/OR REPLACE
#35381496M
Jul 16, 2019
POP/IN-VIO
$0
Apr 15, 2019Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT OLD WING NEXT TO THE BULKHEAD MASONRY SHAFT MISSING AIR VENT CAP. ALSO A/C CONDENSER MISSING DONNAGE. REMEDY: COMPLY WITH NOTICE OF VIOLATION
#35381493R
Jul 16, 2019
POP/IN-VIO
$0
DOB (0)

None open.

DOB NOW Safety (12)
IssuedViolationStatus
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Report
Active
HPD (3) · C 0 · B 3 · A 0
IssuedClassViolationCorrect by
Aug 20, 2009BSECTION 27-2087 ADM CODE - DISCONTINUE USE OF ROOMS FOR LIVING, DISCONNECT PLUMBING FIXTURES WHERE ILLEGAL AND PROPERLY SEAL PIPE CONNECTIONS LEGAL FIXTURES MAY BE RETAINED. FOR INFORMATION CALL THE BOROUGH CODE ENFORCEMENT OFFICE - CELLAR THROUGHOUTSep 24, 2009
Aug 20, 2009BSECTION 27-2073 ADM CODE - DISCONTINUE UNLAWFUL COOKING SPACE OR FILE PLANS AND APPLICATION WITH THIS DEPARTMENT TO LEGALIZE SAME, IF LAWFULLY FEASIBLE CELLAR.Sep 24, 2009
Aug 20, 2009BSECTION 27-2010,2011,2012 ADMIN. CODE: CLEANSE AND DISINFECT TO THE SATISFACTION OF THIS DEPARTMENT AFTER REMOVING THE WATER AT CELLAR REARSep 24, 2009

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 24, 2026, 4:31 AM ET. BBL 4091550025.