2 floors · 2 apartments · 2,720 sq ft · built 1920 · class S2 · owner of record: Allremedy Llc
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Gas piping inspection (2026 cycle) Likely applies Local Law 152 · During 2026 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 9 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2026 in 63 days | Due this year |
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 63 days | Keep the report on file (not filed with DOB) |
| Annual property registration Check HPD registration · September 1 each year What this isResidential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page | Sep 1, 2027 in 307 days | Required only if the owner doesn't live there |
| Annual boiler inspection (1 boiler) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-10-02 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Sep 2, 2025 | Boilers CLASS - 2 WEILMCLAIN BOILER HEATING APT 2F HAS BOILER SAFETY VALVE IN HORIZONTAL POSITION+MANUAL RESET AQUASTAT INSTALLED IN SAFETY VALVE PIPING, MAINTAIN BOILER; CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTION #39159126N | Jul 31, 2026 DEFAULT | $6,250 |
| Sep 2, 2025 | Boilers CLASS - 2 WEILMCLAIN BOILER HEATING APT 2R HAS THE SAFETY VALVE IN HORIZONTAL POSITION+MANUAL RESET AQUASTAT INSTALLED IN SAFETY VALVE PIPING, MAINTAIN BOILER; CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTION #39159125L | Oct 13, 2026 IN VIOLATION | $1,250 |
| Sep 2, 2025 | Boilers CLASS - 2 SLANTFIN BOILER HAS A DEFECTIVE MOTORIZED FLUE DAMPER+DEFECTIVE SPILL SWITCH+IN GAS METER ROOM>HOLES IN CEILING+EXPOSED WIRES+STORAGE+NO FRESH AIR FROM OUTDOORS;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIO #39159124J | Oct 13, 2026 IN VIOLATION | $1,250 |
| Feb 27, 2024 | Construction CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39027268L ISSUED ON 8/21/2020, AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.202.1 AND 1RCNY 102-01(D)(2). AN ACCEPTABLE CERTIF #37026946R | May 21, 2024 DEFAULT | $6,250 |
| Aug 21, 2020 | Boilers CLASS - 2 FOUND SLANTFIN BOILER MODEL SE-105 WITH 105000 BTUS INSTALLED AND OPERATING. REGISTER BOILER AND CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION. #39027368L | Oct 6, 2020 STIPULATION/IN-VIO | $0 |
None open.
None open.
None open.
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 29, 2026, 6:26 AM ET. BBL 4090520037.