Queens · Block 9662 · Lot 20 · 11435

80-20 134 Street

2 floors · 91 apartments · 142,000 sq ft · built 1992 · class N2 · owner of record: Nyc Department Of Homeless Services

45open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
Overdueto Annual property registration

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 8 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 62 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 62 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 62 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 78 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 142,000 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 183 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 183 days
Annual filing
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

OverdueNo current registration found
Energy audit and retro-commissioning (2032) Likely applies
Local Law 87 · Calendar year 2032
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 9662). Agency page

Dec 31, 2032
in 2254 days
Next due 2032
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-06-12 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (37)
IssuedViolationHearingBalance
Sep 24, 2025Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING. OBSERVED EMERGENCY EXITS DOORS NON SELF CLOSING. LOCATED ON THE EAST AND WEST WINGS OF THE BUILDING ON THE 1ST FLOOR. POTENTIAL FIRE HAZARD., REPAIR/REPLACE DOOR
#39161481K
Oct 20, 2025
POP/IN-VIO
$0
Nov 23, 2022Construction CLASS - 2
FAILURE TO COMPLY WITH COMMISSIONERS REQUEST FOR CERTIFICATE OF CORRECTION FOR VIOLATION #39049047H
#39074424Z
Dec 8, 2022
POP/IN-VIO
$0
Nov 23, 2022Construction CLASS - 2
FAILURE TO COMPLY WITH COMMISSIONERS REQUEST FOR CERTIFICATE OF CORRECTION FOR VIOLATION #39049048J
#39074425K
Dec 8, 2022
POP/IN-VIO
$0
Dec 15, 2021Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING. OBSERVED AT BASEMENT LEVEL,EXIT DOORS ON STAIRCASE#A,G&I,DOORS DO NOT CLOSE AUTOMATICALLY DUE TO DOOR LEAVES OVERLAPPING THE FRAME,EXCESSIVE CORROSION AND OTHER FAILURE. ALSO,EXIT DO
#35636015Y
Apr 5, 2022
POP/IN-VIO
$0
Oct 8, 2021Boilers CLASS - 2
FOUND HB SMITH WATER BOILER SERIAL# 162620 NOT REGISTERED REGISTER THE BOILER AND SUBMIT A CERTIFICATE OF CORRECTION
#39049048J
Oct 15, 2021
POP/IN-VIO
$0
Oct 8, 2021Boilers CLASS - 2
FOUND HB SMITH WATER BOILER SERIAL# 101875 NOT REGISTERED REGISTER THE BOILER AND SUBMIT A CERTIFICATE OF CORRECTION
#39049047H
Oct 15, 2021
POP/IN-VIO
$0
Jan 4, 2021Boilers CLASS - 2
REGISTER THE BOILER AND SUBMIT A CERTIFICATE OF CORRECTION.
#39034183K
Jan 22, 2021
POP/IN-VIO
$0
Jan 4, 2021Boilers CLASS - 2
CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION.
#39034185Y
Jan 22, 2021
POP/IN-VIO
$0
Jan 4, 2021Boilers CLASS - 2
COMBUSTION AIR INTAKE SCREEN CLOGGING. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION.
#39034184M
Jan 22, 2021
POP/IN-VIO
$0
Jan 4, 2021Boilers CLASS - 2
REGISTER THE BOILER AND SUBMIT A CERTIFICATE OF CORRECTION
#39034186X
Jan 22, 2021
POP/IN-VIO
$0
Feb 25, 2020Boilers CLASS - 2
FOUND 1 HB SMITH 28A-12 GAS FIRED HOT WATER BOILER NOT REGISTERED. REGISTER BOILER
#39018341R
Mar 16, 2020
POP/IN-VIO
$0
Feb 25, 2020Boilers CLASS - 2
FOUND 1 HB SMITH 28HE-12 GAS FIRED HOT WATER BOILER NOT REGISTERED. REGISTER BOILER
#39018342Z
Mar 16, 2020
POP/IN-VIO
$0
Sep 24, 2019Boilers CLASS - 2
FOUND UNREGISTERED HB SMITH MDL# 28A-12 BOILER. REGISTER BOILER AND SUBMIT A CERTIFICATE OF CORRECTION.
#39010015P
Oct 4, 2019
POP/IN-VIO
$0
Sep 24, 2019Boilers CLASS - 2
FOUND UNREGISTERED HB SMITH MDL# 28HE-12 BOILER. REGISTER BOILER AND SUBMIT A CERTIFICATE OF CORRECTION.
#39010014N
Oct 4, 2019
POP/IN-VIO
$0
May 7, 2019Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING, NOTED:@WWEST SECTION, @CELLAR LVL, 4 OF 4 EMERGENCY EXIT DOORS NOT SELF CLOSING. EMERGENCY EXIT DOORS LOCATED INTHE CHILD CARE AREA.REM: REPAIR/REPLACE DOORS.
#35381172X
Jul 23, 2019
POP/IN-VIO
$0
May 7, 2019Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.@ EAST SECTION,@RD STY CORRIDOR & 3RD STY STAIRWELL, WATER PENETRATION @ CEILING.PLASTER @CEILING FLAKING ANF FALLING DIRECTLY ONTO TENANT WALKWAY.REM:
#35381171Y
Jul 23, 2019
POP/IN-VIO
$0
Feb 6, 2019Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER 712.3; 27-345. NOTED AT CELLAR LEVEL, OBSERVED SEVERAL HOLES IN CEILING AND WALLS IN SEVERAL AREAS THROUGHOUT CELLAR ELIMINATING FIRE
#35386410P
Feb 25, 2019
POP/IN-VIO
$0
Jul 10, 2018Boilers CLASS - 2
36)FOUND 2-HB SMITH BOILERS NOT REGISTERED AND PERMIT EXPIRED. REGISTER BOILERS.
#32096029L
Oct 9, 2018
POP/IN-VIO
$0
Jul 14, 2017Unknown CLASS - 2
UNSAFE/UNAPPROVED/UNSUITABLE ELECTRICAL EQUIPMENT, MATERIALS,APPARATUSDEVICES,APPLIANCES OR WIRING IN USE. OBSERVED RECEPTACLES THROUGHOUT CORRIDORS NOT CHILD PROOF OR JUMPER RESISTANT.EXHAUST FAN K-92 DEFECTI
#35272264K
Dec 19, 2017
POP/IN-VIO
$0
Jun 7, 2017Boilers CLASS - 2
36,32A,50,A 36 FOUND HB SMITH BOILER NOT REGISTERED. 50A FRESH AIR L OUVER CLOGGED NO AIR REGISTER THE BOILER AND CORRECT ALL VIOLATING CONDITIONS,SUBMIT THE CERTIFICATE OF CORRECTION.
#32088645P
Sep 5, 2017
POP/IN-VIO
$0
Jun 7, 2017Boilers CLASS - 2
36,32A,50A 36,FOUND HB SMITH GAS FIRED BOILER NOT REGISTERED 50A NO STORAGE IN BOILER ROOM.REGISTER THE BOILER AND CORRECT VIOLATING CONDITION,SUBMIT THE CERTIFICATE OF CORRECTION.
#32088644N
Sep 5, 2017
POP/IN-VIO
$0
Jan 24, 2017Construction CLASS - 1
ALTERED BLG OCCUPIED W/O A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1, 28-118.3.2 NOTE: TCO#400047141 EXPIRED 6-7-1994, BLDG FULLY OCCUPIED AT TIME OF INSPECTION. RMDY:OBTAIN A VALID CERTIFICATE OF OCCUPA
#35225636K
Mar 28, 2017
POP/IN-VIO
$0
Feb 16, 2016Construction CLASS - 2
EXIT DOOR NOT SELF CLOSING.NOTE:EXIT #10, THE DOOR HAS AN INOPERATIVE DOOR CLOSER AND REMAINS OPEN AFTER EXITING. REM:COMPLY W/CODE, REPAIR DOOR CLOSER.
#35170914X
Apr 5, 2016
POP/IN-VIO
$0
Jun 27, 2015Boilers CLASS - 2
B251/34A/50A/50B/ 50A-MANUAL RESET LOW WATER CUT OFF MISSING. 50B-COVERS MISSING ON CONTROLS.
#32075196X
Aug 18, 2015
POP/IN-VIO
$0
Jun 27, 2015Construction CLASS - 1
B101/ WORK WITHOUT PERMIT. H.B. SMITH 28A-12 BOILER. POWER FLAME CR3-G25.
#32075199L
Aug 18, 2015
POP/IN-VIO
$0
Jun 27, 2015Boilers CLASS - 1
B154/32A/34A/50A/50B/50C/ 50A-SHUT DOWN CEASE USE BOILER LEAKING FRONT SECTION. 50B-EXPOSED WIRES. 50C-JACKET OFF. 50C-MISSING COVERS - DO NOT OPERATE BOILER UNTIL ALL HAZARDOUS CONDITIONS ARE IMMEDIATELY COR
#32075197H
Aug 18, 2015
POP/IN-VIO
$0
Mar 9, 2015Unknown CLASS - 2
FAILURE TO COMPLY W/COMMISSIONER'S ORDER TO FILE CERTIFICATE OF CORRECTION WITH DOB. OBSERVED ON MARCH 6 2015 2:40PM BOILER ROOM WATER PIPING NOT CORRECTED AS PER VIOL #35066861L. RMDY: FILE A CERTIFICATE OF CO
#35115183J
Apr 28, 2015
POP/IN-VIO
$0
Aug 20, 2014Unknown CLASS - 2
FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED: AT 1ST FLOOR MAIN ENTRY LARGE DESK IN PLACE OBSTRUCTING PASSAGE FLOW TO EXIT DOORS. REMEDY: REMOVE DESK.
#35108109X
Oct 28, 2014
POP/IN-VIO
$0
Aug 20, 2014Unknown CLASS - 2
WORK WITHOUT PERMIT. ILLEGAL WORK NOTED: AT CELLAR LEVEL ELEVATOR MACHINE ROOM SUB-DIVIDED TO CREATE STORAGE ROOM. REMEDY: OBTAIN PERMIT.
#35108107M
Oct 28, 2014
POP/IN-VIO
$0
Aug 20, 2014Unknown CLASS - 1
ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. NOTED: AT TIME OF INSPECTION, IN ELECTRICAL SERVICE ROOM USED AS STORAGE ROOM ALSO, MISC MATERIALS ARE BEING STORED IN FRONT OF, AROUN
#35073031H
Oct 28, 2014
POP/IN-VIO
$0
Aug 20, 2014Construction CLASS - 2
FAILURE TO MAINTAIN. NOTED: EXIT DOOR #8 STUCK SHUT. ALSO CORRIDOR DOORS NOT CLOSING PROPERLY WHEN RELEASED. ILLEGAL DOOR STOPS ON FPSC DOORS. REMEDY: COMPLY WITH CODE.
#35108105Z
Oct 28, 2014
POP/IN-VIO
$0
Aug 20, 2014Construction CLASS - 2
FAILURE TO MAINTAIN. NOTED: EAST SIDE CORRIDOR VENTILATION SYSTEM NOT OPERATIONAL AT TIME OF INSPECTION. REMEDY: REPAIR / REPLACE SYSTEM.
#35108108Y
Oct 28, 2014
POP/IN-VIO
$0
Aug 20, 2014Unknown CLASS - 1
UNAPPROVED, UNSAFE, UNSUITABLE, ELECTRICAL EQUIPMENT, MATERIALS, DEVICES, APPLIANCES OR WIRING IS IN USE. NOTED: THROUGHOUT ALL FLOORS, HALLS, HALLWAYS, CORRIDORS, STAIRWELLS & CLOSETS, EXIT LIGHTS, WALLPACKS,
#35073027P
Oct 28, 2014
POP/IN-VIO
$0
Aug 20, 2014Plumbing CLASS - 1
FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLER SYSTEM WHERE REQUIRED. DURING PHYSICAL INSPECTION I OBSERVED THAT THERE ARE NO SPRINKLERS PROVIDED FOR THE SUPPLY ROOM ON THE 1ST FLOOR CONTAINING FLAMABLE PR
#35066860J
Oct 28, 2014
POP/IN-VIO
$0
Aug 20, 2014Construction CLASS - 1
ALTERED BLDG OCCUPIED WITHOUT A VALID CERT OF OCCUPANCY AS PER 28-118.3.1, 28-118.3.2, TCO# 400047141 EXPIRED 9-7-1994, BLDG FULLY OCCUPIED AT TIME OF INSPECTION. REMEDY: OBTAIN VALID C OF O.
#35108106K
Oct 28, 2014
POP/IN-VIO
$0
Aug 20, 2014Plumbing CLASS - 2
USE OR INSTALLATION OF PLUMBING MATERIAL WHICH DO NOT COMPLY WITH RS-16. DURING PHYSICAL INSPECTION I OBSERVED A SECTION OF BLACK IRON PIPE CONNECTED TO THE BRASS DOMESTIC WATER LINE IN THE BOILER ROOM. BLACK
#35066861L
Oct 28, 2014
POP/IN-VIO
$0
Aug 20, 2014Unknown CLASS - 2
SPRINKLER SYSTEM IS NOT PROPERLY PAINTED. FAILURE TO PAINT DEDICATED SPRINKLER PIPING. DURING PHYSICAL INSPECTION I OBSERVED THAT THERE ARE SECTION OF THE DEDICATED OVERHREAD SPRINKLER MAIN SUPPLY LINE NOT PAI
#35066862N
Oct 28, 2014
POP/IN-VIO
$0
DOB (6)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#18883
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#18884
DOB VIOLATION - ACTIVE
Jul 1, 2021ELEVATOR

#9027/699920
DOB VIOLATION - ACTIVE
Jun 27, 2015BOILER

#062715B2408
VIOLATION UNSERVED ECB-WORK WITHOUT PERMIT-ACTIVE
Jan 13, 1997LOCAL LAW 10/81 - ELEVATOR

#04015
DOB VIOLATION - ACTIVE
Jun 28, 1993CONSTRUCTION

#09M10
VIOLATION UNSERVED ECB-WORK WITHOUT PERMIT-ACTIVE
DOB NOW Safety (2)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 30, 2026, 1:14 PM ET. BBL 4096620020.