Brooklyn · Block 1888 · Lot 34 · 11205

77 Clinton Avenue

5 floors · 112,452 sq ft · built 1968 · class W1 · owner of record: Clinton Assoc Of Kings Inc

45open violations
$6,250ECB/OATH penalties owed
0HPD class C (immediately hazardous)
184dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 63 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 112,452 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 184 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 184 days
Annual filing
Energy audit and retro-commissioning (2028) Likely applies
Local Law 87 · Calendar year 2028
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 1888). Agency page

Dec 31, 2028
in 794 days
Next due 2028
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 2 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1159 days
Next cycle year 2029
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-08-26 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (14) · $6,250 owed
IssuedViolationHearingBalance
Feb 2, 2026Construction CLASS - 2
REISSUE ECB #35693125X. EXIT DOOR NOTED: AT(1ST FL) CAFETERIA AND GYM DOOR NOT CHECK CLOSING WHEN TESTED. REMEDY: REPAIR/REPLACE DOOR.
#35724791R
Feb 13, 2026
POP/IN-VIO
$0
Feb 2, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS CORRIDORS PER BC 1006.1; 27-543. NOTED: AT(3RD FL) R321 LIBRARY WITH NO EMERGENC
#35724794M
Feb 13, 2026
POP/IN-VIO
$0
Feb 2, 2026Construction CLASS - 2
REISSUE ECB #35675023X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: AT(1ST FL) HALLWAY NEAR ELEVATOR/GYM AND CAFETERIA DOORS IN DISREPAIR/RACKETS. REMEDY: REPAIR AND/OR REPLACE.
#35724793K
Feb 13, 2026
POP/IN-VIO
$0
Feb 2, 2026Construction CLASS - 2
REISSUE ECB #35675024H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: AT(1ST FL) GYM AND RM 141 AUDITORIUM EMER
#35724792Z
Feb 13, 2026
POP/IN-VIO
$0
Mar 4, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 1ST FL HALLWAY SMOKE DOORS NEAR ELEVAT-GYM AND CAFETERIA DOORS ARE IN DISREPAIR/RACKED. REMEDY: REPAIR AND/OR REPLACE.
#35675023X
Apr 23, 2025
POP/IN-VIO
$0
Mar 4, 2025Construction CLASS - 2
EXIT DOOR NOT CLOSING NOTED: AT 1ST FL CAFETERIA DOOR CHECK/CLOSER NOTWORKING WHEN TESTED. REMEDY: REPAIR/REPLACE DOOR.
#35693125X
Apr 23, 2025
POP/IN-VIO
$0
Mar 4, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS. EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: AT 1ST FL GYM EMERGENCY LIGHTS NOT WORKING THROUGHOUT VARIOUSLY
#35675024H
Apr 23, 2025
POP/IN-VIO
$0
Jan 14, 2025Construction CLASS - 2
OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDINGS DEPARTMENT RECORDS: AT THE TIME OF INSPECTION, OBSERVED PENTHOUSE ON THE 6TH FLOOR DESIGNATED AS AN ACCESSORY ADMINISTRATIVE OFFIC
#39135470X
Mar 26, 2025
DEFAULT
$6,250
Mar 22, 2022Elevators CLASS - 1
CLASS 1 ITEM: PROVIDE DLM AS NOW REQUIRED BY CODE. CLASS 2 ITEMS: REPLACE GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. PROVIDE DESIGNATED LOBBY BRAILLE TAGS. INOPERATIVE CAR PHONE. MAIN LINE CAN BE OPENED WHEN
#39058595N
Jul 27, 2022
DEFAULT
$0
Mar 22, 2022Elevators CLASS - 1
CLASS 1 ITEM: PROVIDE DLM AS NOW REQUIRED BY CODE. CLASS 2 ITEMS: REPLACE GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. PROVIDE DESIGNATED LOBBY BRAILLE TAGS. UNREADABLE MAIN LINE FUSES.
#39058596P
Jul 27, 2022
DEFAULT
$0
Sep 5, 2012Construction CLASS - 2
27-766:REISSUE 34919539Z. NO FRESH AIR VENT IN GAS METER ROOM.
#34995997K
Oct 22, 2012
WRITTEN OFF
$0
Mar 15, 2010Boilers CLASS - 2
B254/ 34A/ 15/ 16/ 50A/ 50B/ 50C/ 50D/ 50E/ 38/ (50A) RATING PLATE ON SAFETY OR RELIEF VALUE MISSING (50B) BOILER ROOM NOT A STORAGE ROOM (50C) NO EMERGENCE FUEL CUT OFF SWITCH OUT SIDE OF BOILER ROOM FIRE DOOR
#32068141N
Mar 9, 2011
WRITTEN OFF
$0
Mar 15, 2010Construction CLASS - 3
B301,50A,B. 50A- WORK W/O A PERMIT 2P. 105.1. 50B- NO WORK PERMIT FILED W/DOB FOR THE REPLACEMENT BOILERS.
#32068252X
Feb 23, 2011
IN VIOLATION
$0
Mar 15, 2010Boilers CLASS - 2
B254/ 34A/ 15/ 16/ 50A/ 50B/ 50C/ 50D/ 38/ 50A BOILER ROOM NOT A STORAGE ROOM 50B NO EMERGENCE FUEL CUT OFF SWITCH OUT SIDE OF BOILER ROOM FIRE DOOR (50C) NO CLEAN OUT ON CHIMNEY OR FLUE PIPE (50D) CHIMNEY SUPP
#32068142P
Mar 9, 2011
IN VIOLATION
$0
DOB (10)
IssuedViolationStatus
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#41323
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#21578
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#41322
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#21579
DOB VIOLATION - ACTIVE
Aug 11, 2021ELEVATOR

#9027/706375
DOB VIOLATION - ACTIVE
Aug 11, 2021ELEVATOR

#9027/705699
DOB VIOLATION - ACTIVE
Jul 2, 2020ELEVATOR

#9027/682172
DOB VIOLATION - ACTIVE
Jul 2, 2020ELEVATOR

#9027/682171
DOB VIOLATION - ACTIVE
Sep 6, 2019(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
#09887
DOB VIOLATION - ACTIVE
Jan 26, 2018(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
#11450
DOB VIOLATION - ACTIVE
DOB NOW Safety (21)
IssuedViolationStatus
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
Sep 6, 2019Elevators ACC1
Active
Jan 26, 2018Elevators ACC1
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 29, 2026, 11:49 AM ET. BBL 3018880034.