Brooklyn · Block 5064 · Lot 7 · 11226

769 Flatbush Avenue

1 floors · 1,700 sq ft · built 1925 · class K1 · owner of record: Kim, Hee Soon

4open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
66dto Annual boiler inspection (2 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 66 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-24 (Accepted). Agency page

Dec 31, 2026
in 66 days
1 of 2 without an accepted 2026 report yet
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 14 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 431 days
Next cycle year 2027

Open violations

ECB / OATH (4)
IssuedViolationHearingBalance
May 12, 2016Unknown CLASS - 2
ELECTRICAL WORK W/O A PERMIT. BRANCH CIRCUIT WIRING NEW LIGHT FIXTURES,OUTLET RECEPTACLES INSTALLED INSIDE OF THE COMMERCIAL SPACE W/O AN ELECTRICAL PERMIT. REMEDY: OBTAIN PERMIT.
#35159797Z
Oct 31, 2016
IN VIOLATION
$0
Aug 31, 2009Boilers CLASS - 2
32A50A50B50C50D. 50A CHIMNEY/BOILER/FLU PIPE SOOTED UP. 50B CHIMNEY CLEAN OUT SEALED. 50C SAFETY RELEIF VALVE MUST PIPED DOWN 6"-8" FROM GROUND LEVEL. 50D NO TEST TEE AND VALVE ON STEAM GAUGE.
#32066860K
Oct 26, 2009
IN VIOLATION
$0
Apr 26, 2008Boilers Non-Hazardous
SEC 50A, 50B. FUCTON V.T. BOILER, 10HP, NB36530, OIL,1979 AROUND BOILER. OIL BURNER SERVICE REQUIRED FOR COMPLIANCE. 50B-EVIDENCE OF PARTICULATE ACCUMULATION IN BOILER COMBUSTION CHAMBER.VACUUM BOILER AT CLEAN
#32056409R
Jul 28, 2008
IN VIOLATION
$0
Aug 1, 2006Boilers Non-Hazardous
50A, 50B, 50C, 44B, 44C. FUCTON V.J BOILER HP STEAM, NB 36530, OIL 1979 50A- SECONDARY LOW WATER CUT OFF MANUAL RESET SWITCH MISSING. 50B-NODRAIN LINE ON THE GAUGE GLASS ASSEMBLY. 50C-SECONDARY SCREW TYPE VALVE
#32051155N
Sep 25, 2006
STIPULATION/IN-VIO
$0
DOB (0)

None open.

DOB NOW Safety (0)

None open.

HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 26, 2026, 8:41 PM ET. BBL 3050640007.

Look up another building