Bronx · Block 4631 · Lot 75 · 10467

760 East Gun Hill Road

3 floors · 38,646 sq ft · built 1950 · class W2 · owner of record: R C Ch Immac Concepti

7open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
43dto Annual boiler inspection (2 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 43 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-10-06 (Accepted). Agency page

Dec 31, 2026
in 43 days
1 of 2 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 38,646 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 164 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 164 days
Annual filing
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 408 days
Next cycle year 2027

Open violations

ECB / OATH (2)
IssuedViolationHearingBalance
Apr 10, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT THE TIME OF INSPECTION, ON THE 2ND FLOOR STAIRCASE "A" DOOR ON THE RIGHT DOES NOT OPEN OR CLOSE. THE INTERIOR DOOE IS NOT OPERATIONAL. REMEDY: RE
#35727426M
May 8, 2026
POP/IN-VIO
$0
Apr 10, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE-STOPPING PER BC 712.3; 27-345. NOTED: IN ELECTRIC METER ROOM FIRE-STOPPING WAS MISSING AROUND PIPES GOING THRU "CMU" BLOCKS AND BRICKS WERE MISSING
#35727425K
May 8, 2026
POP/IN-VIO
$0
DOB (1)
IssuedViolationStatus
May 2, 2023FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#00670
DOB VIOLATION - ACTIVE
DOB NOW Safety (4)
IssuedViolationStatus
Jul 7, 2026GHG Emissions - LL97 FTF-EN-LL97320
Active
Jan 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle D (premises is in Community District 12)
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
May 2, 2023Benchmarking - LL84 FTF-EN-BENCH
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 18, 2026, 4:39 PM ET. BBL 2046310075.

Look up another building