Bronx · Block 2568 · Lot 68 · 10454

711 East 140 Street

5 floors · 42,798 sq ft · built 1931 · class HR · owner of record: Jackson Avenue Development Llc

12open violations
$10,250ECB/OATH penalties owed
3HPD class C (immediately hazardous)
43dto Annual boiler inspection (7 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 43 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (7 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-02-05 (Accepted). Agency page

Dec 31, 2026
in 43 days
3 of 7 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 42,798 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 164 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 164 days
Annual filing
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 1 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 774 days
Next cycle year 2028

Open violations

ECB / OATH (6) · $10,250 owed
IssuedViolationHearingBalance
Oct 26, 2026Unknown CLASS - 2
FAILURE TO PROTECT CONDUCTOR(S) AGAINST OVERCURRENT PER EC. OBSERVED IN THE ELEVATOR MACHINE ROOM LOCATED ON THE ROOF THE SERVICE SW FOR THE ELEVATOR THE OVERCURRENT PROTECTION IS INCORRECT AT 125 AMPS. WIRE RA
#39209381N
Jan 15, 2027
PENDING
$2,400
Oct 26, 2026Unknown CLASS - 1
MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED THAT THE GENERATOR IS IN OPERATIONAL AT TIME OF INSPECTION ALSO THE SHUTDOWN SWITCH IS NOT REACHABLE FOR EMERGENCY USE. GENERATOR MUS
#39209382P
Jan 15, 2027
PENDING
$1,600
Oct 26, 2026Construction CLASS - 1
AT TIME OF INSPECTION, I OBSERVED TWO FIRE DOORS CUT, WITH HOLE OPENINGS AND COVERED WITH VENTS. IN CASE OF A FIRE, THESE OPENINGS WILL CAUSE THE FIRE TO SPREAD INTO THE ADJACENT ROOMS., REPAIR AND/REPLACE; INS
#39209388X
Jan 15, 2027
PENDING
$2,500
Oct 26, 2026Construction CLASS - 1
ATOI OBSERVED GAS PIPING GOING THROUGH A ROOM HOUSING THE FIRE PUMP. THIS IS CONTRARY TO 913.2.1 - ADDRESSES RESTRICTIONS ON GAS PIPING, GAS EQUIPMENT, AND OTHER SPECIFIED EQUIPMENT WITHIN SPACES HOUSING FIRE P
#39209383R
Jan 15, 2027
PENDING
$2,500
Oct 26, 2026Elevators CLASS - 1
CLASS 1 C/U: DOOR ZONE RESTRICTOR INOPERATIVE, CREATING A RISK OF CAR DOORS OPENING OUTSIDE THE DESIGNATED DOOR ZONE AND PASSENGERS FALLING INTO THE HOISTWAY. AS PER APPLICABLE ASME A17.1/CSA B44 REQUIREMENTS.
#39209422K
Jan 15, 2027
PENDING
$1,250
Nov 20, 2025Construction CLASS - 2
OBSERVED IN BASEMENT GAS LINE IN THE FIRE PUMP ROOM. ALSO FAILURE TO PROVIDE AN UPDATED SPRINKLER TEST WHICH CONTRARY TO CODE SECTIONS FGC 403 (3) AND BC 101.4.5, REPAIR AND/OR REPLACE
#39167692H
May 29, 2026
IN VIOLATION
$0
DOB (1)
IssuedViolationStatus
Jan 13, 1997LOCAL LAW 10/81 - ELEVATOR

#02004
DOB VIOLATION - ACTIVE
DOB NOW Safety (2)
IssuedViolationStatus
Jan 8, 2026Gas Piping - LL152 FTF-PL-PER
Cycle 2, Sub-cycle A (premises is in Community District 1)
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
HPD (3) · C 3 · B 0 · A 0
IssuedClassViolationCorrect by
Oct 30, 2020CApt 112 · § 27-2056.8 ADM CODE -CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT ... IN THE ENTIRE APARTMENT LOCATED AT APT 112, 1st STORY, 1st APARTMENT FROM WEST AT NORTHNov 3, 2020
Oct 30, 2020C§ 27-2056.4 ADM CODE- CORRECT FAILURE TO NOTIFY OCCUPANTS AND/OR TO INVESTIGATE LEAD-BASED PAINT HAZARDS.Nov 3, 2020
Jul 8, 2020C§ 27-2056.4(H) AND 27-2056.17 ADM CODE -CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.Jul 12, 2020

Issued in the last 120 days

DateSourceWhatNow
Oct 26, 2026ECBUnknown: FAILURE TO PROTECT CONDUCTOR(S) AGAINST OVERCURRENT PER EC. OBSERVED IN THE ELEVATOR MACHINE ROOM LOCATED ON THE ROOF THE SERVICE SW FOR THE ELEVATOR THE OVERCURRENT PROTECTION IS INCORRECT AT 125 AMPS. WIRE RAOpen
Oct 26, 2026ECBUnknown: MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED THAT THE GENERATOR IS IN OPERATIONAL AT TIME OF INSPECTION ALSO THE SHUTDOWN SWITCH IS NOT REACHABLE FOR EMERGENCY USE. GENERATOR MUSOpen
Oct 26, 2026ECBConstruction: AT TIME OF INSPECTION, I OBSERVED TWO FIRE DOORS CUT, WITH HOLE OPENINGS AND COVERED WITH VENTS. IN CASE OF A FIRE, THESE OPENINGS WILL CAUSE THE FIRE TO SPREAD INTO THE ADJACENT ROOMS., REPAIR AND/REPLACE; INSOpen
Oct 26, 2026ECBConstruction: ATOI OBSERVED GAS PIPING GOING THROUGH A ROOM HOUSING THE FIRE PUMP. THIS IS CONTRARY TO 913.2.1 - ADDRESSES RESTRICTIONS ON GAS PIPING, GAS EQUIPMENT, AND OTHER SPECIFIED EQUIPMENT WITHIN SPACES HOUSING FIRE POpen
Oct 26, 2026ECBElevators: CLASS 1 C/U: DOOR ZONE RESTRICTOR INOPERATIVE, CREATING A RISK OF CAR DOORS OPENING OUTSIDE THE DESIGNATED DOOR ZONE AND PASSENGERS FALLING INTO THE HOISTWAY. AS PER APPLICABLE ASME A17.1/CSA B44 REQUIREMENTS.Open