Bronx · Block 2882 · Lot 130 · 10453

67 West 176 Street

class U6 · owner of record: Mta - Metro North

47open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
—no dated deadlines found

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

We couldn't find building attributes for this lot, so no deadlines are listed.

Open violations

ECB / OATH (9)
IssuedViolationHearingBalance
Jul 29, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVEDGAS METER ROOM BEING USED TO STORE MATERIAL-20 BAGS OF ICE MELT, 2 LADDERS, 5 BOXES(MISC), GARBAGE BINS. REMEDY: REPAIR MATERIAL.
#35734629H
Aug 21, 2026
POP/IN-VIO
$0
Jul 29, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). NOTED: SMOKE DOORSHAVE KICK-STOPS INSTALLED AT BOTTOM OF DOORS AT 3RD FLR-SMOKE DOORS NE
#35734628X
Aug 21, 2026
POP/IN-VIO
$0
Jul 29, 2026Construction CLASS - 2
RE-ISSUE #35725273L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE-STOPPING PER BC 712.3; 27-345. NOTED: IN BASEMENT AT ELECTRIC METER ROOM, THERE IS FIRE-STOPPING MISSING IN SEVERAL AREAS AROU
#35734625K
Aug 21, 2026
POP/IN-VIO
$0
Jul 29, 2026Construction CLASS - 2
RE-ISSUE #35725272J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED ON 4TH CAFETERIA SMOKE DOOR EXIT SWINGS IN AND SHOULD SWING OUT SINCE IT IS A EXIT. REMEDY: REPAIR AND/OR REPLACE.
#35734626M
Aug 21, 2026
POP/IN-VIO
$0
Jul 29, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORFPSC DOORS DO NOT SELF-CLOSE PROPERLY AT 3RD FLR-SMOKE DOOR NEAR STAIRCASE "E". CLASSROOM DOORS DO NOT SELF-CLOSE PROPERLY AT 4TH FLR RM #S-
#35734627Y
Aug 21, 2026
POP/IN-VIO
$0
Sep 4, 2025Construction CLASS - 2
REISSUE #35688855L-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRESTOPPING IN ELECTRICAL ROOM. REMEDY: COMPLY WITH CODE.
#35725273L
Oct 17, 2025
POP/IN-VIO
$0
Sep 4, 2025Construction CLASS - 2
REISSUE #35688856N-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: CAFE AT 4TH FLOOR HAS DOORS THAT OPEN AGAINST THE FLOW. REMEDY: COMPLY WITH CODE.
#35725272J
Oct 17, 2025
POP/IN-VIO
$0
Sep 23, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRESTOPPING PER BC 712.3;27-345.NOTED:AT CELLAR LEVEL-ELECTRICAL METER ROOM HAS PIPE LINES PENETRATING THROUGH THE WALL WITH OPENINGS THAT ARE MISSING F
#35688855L
Nov 29, 2024
POP/IN-VIO
$0
Sep 23, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED AT 4 FLR,THE IMPROVISED CAFETERIA RM.440/442 HAS EXISTING FIREPROOF SELF-CLOSING THAT ARE CURRENTLY SWINGING AGAINST THE FLOW OF EGRESS AND C
#35688856N
Nov 29, 2024
POP/IN-VIO
$0
DOB (12)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#06221
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#06222
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#06220
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#24483
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#31284
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#44101
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#31250
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#09280
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#09324
DOB VIOLATION - ACTIVE
Nov 8, 2019LOW PRESSURE BOILER
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
#04804
DOB VIOLATION - ACTIVE
Nov 8, 2019LOW PRESSURE BOILER
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
#04806
DOB VIOLATION - ACTIVE
Nov 8, 2019LOW PRESSURE BOILER
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
#04805
DOB VIOLATION - ACTIVE
DOB NOW Safety (26)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 8, 2019Boiler LBLVIO
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
Active
Nov 8, 2019Boiler LBLVIO
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
Active
Nov 8, 2019Boiler LBLVIO
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Jul 29, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVEDGAS METER ROOM BEING USED TO STORE MATERIAL-20 BAGS OF ICE MELT, 2 LADDERS, 5 BOXES(MISC), GARBAGE BINS. REMEDY: REPAIR MATERIAL.Open
Jul 29, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). NOTED: SMOKE DOORSHAVE KICK-STOPS INSTALLED AT BOTTOM OF DOORS AT 3RD FLR-SMOKE DOORS NEOpen
Jul 29, 2026ECBConstruction: RE-ISSUE #35725273L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE-STOPPING PER BC 712.3; 27-345. NOTED: IN BASEMENT AT ELECTRIC METER ROOM, THERE IS FIRE-STOPPING MISSING IN SEVERAL AREAS AROUOpen
Jul 29, 2026ECBConstruction: RE-ISSUE #35725272J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED ON 4TH CAFETERIA SMOKE DOOR EXIT SWINGS IN AND SHOULD SWING OUT SINCE IT IS A EXIT. REMEDY: REPAIR AND/OR REPLACE.Open
Jul 29, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORFPSC DOORS DO NOT SELF-CLOSE PROPERLY AT 3RD FLR-SMOKE DOOR NEAR STAIRCASE "E". CLASSROOM DOORS DO NOT SELF-CLOSE PROPERLY AT 4TH FLR RM #S-Open