7open violations
$5,000ECB/OATH penalties owed
0HPD class C (immediately hazardous)
66dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 66 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 66 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 39,780 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 187 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 187 days
Annual filing
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $180,000 in late-filing or failure-to-file penalties. Agency page

On fileCycle 10 filing on record: SAFE (2026-07-16)

Open violations

ECB / OATH (4) · $5,000 owed
IssuedViolationHearingBalance
Sep 11, 2026Construction CLASS - 1
ATOI OBSERVED A WATER HEATER INSTALLED WITHOUT ANY PERMITS FILE ON BIS OR DOBNOW CONTRARY TO PC 106.1 PLUMBING WORK INCLUDING WATER HEATER INSTALLATIONS AND PLUMBING SYSTEM ALTERATIONS, REQUIRES PERMITS., OBTAI
#39203871Z
Nov 25, 2026
PENDING
$2,500
Sep 11, 2026Construction CLASS - 1
ATOI OBSERVED GAS METER BEING HOUSED IN THE FIRE PUMP ROOM WHICH IS CONTRARY TO BC 913.2.1 GAS PIPING, GAS CONSUMPTION DEVICES, GAS METERS OR ANY OTHER GAS EQUIPMENT AND FUEL STORAGE OR FUEL CONSUMING APPLIANCE
#39203872K
Nov 25, 2026
PENDING
$2,500
Sep 16, 2025Construction CLASS - 2
OBSERVED ON 9TH FLOOR STANDPIPE VALVE USING A PLASTIC CAP, SPRINKLER HEAD PAINTED, AND THROUGHOUT THE BUILDING SPRINKLER HEAD CAPS PAINTED TO CEILING. ON 5TH FLOOR RAN OUT MULTIPLE HOSES FOR WASHING MACHINE AND
#39160576Z
Nov 26, 2025
DEFAULT
$0
Sep 16, 2025Construction CLASS - 2
OBSERVED IN THE BASEMENT EJECTOR PUMP IMPROPERLY INSTALLED USING FERNCO COUPLING AND NO COVER PLATE. ALSO FIRE PUMP IS IN THE SAME ROOM AS THE GAS LINE WHICH IS CONTRARY TO CODE SECTIONS PC 605.9 AND FGC 404.3
#39160577K
Nov 26, 2025
DEFAULT
$0
DOB (0)

None open.

DOB NOW Safety (3)
IssuedViolationStatus
Oct 14, 2026AEUHAZ FTC-AEU-HAZ
Active
Oct 14, 2026AEUHAZ FTC-AEU-HAZ
Active
Oct 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle C (premises is in Community District 6)
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 14, 2026DOB SafetyAEUHAZ: Open
Oct 14, 2026DOB SafetyAEUHAZ: Open
Sep 11, 2026ECBConstruction: ATOI OBSERVED A WATER HEATER INSTALLED WITHOUT ANY PERMITS FILE ON BIS OR DOBNOW CONTRARY TO PC 106.1 PLUMBING WORK INCLUDING WATER HEATER INSTALLATIONS AND PLUMBING SYSTEM ALTERATIONS, REQUIRES PERMITS., OBTAIOpen
Sep 11, 2026ECBConstruction: ATOI OBSERVED GAS METER BEING HOUSED IN THE FIRE PUMP ROOM WHICH IS CONTRARY TO BC 913.2.1 GAS PIPING, GAS CONSUMPTION DEVICES, GAS METERS OR ANY OTHER GAS EQUIPMENT AND FUEL STORAGE OR FUEL CONSUMING APPLIANCEOpen

Check the agency records