Manhattan · Block 857 · Lot 17 · 10016

62 Madison Avenue

11 floors · 24,608 sq ft · built 1903 · class HB · owner of record: Mave Hotel Investors Llc

38open violations
$14,138ECB/OATH penalties owed
0HPD class C (immediately hazardous)
61dto Annual boiler inspection (1 boiler)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 61 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2022-12-05 (Accepted). Agency page

Dec 31, 2026
in 61 days
1 of 1 without an accepted 2026 report yet
Facade inspection report (Cycle 10B) Applies
Local Law 11 / FISP · Feb 21, 2026 to Feb 21, 2028
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 0, 7 or 8 are in sub-cycle 10B. DOB facade records for this building show $1,081,200 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2028
in 478 days
No Cycle 10 report on record yet
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 5 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1157 days
Next cycle year 2029

Open violations

ECB / OATH (15) · $14,138 owed
IssuedViolationHearingBalance
Apr 11, 2024Local Law CLASS - 2
FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8B AND 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #902386. AGG2 HISTORY OF NONCOMP
#37027520Y
Sep 19, 2024
IN VIOLATION
$6,250
Oct 19, 2022Local Law CLASS - 2
FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITIONS OF EXTERIOR WALL & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #802386.AGG1:PRIOR NOV 37021418K UNDER 28-3
#37022908H
Mar 9, 2023
IN VIOLATION
$3,125
Jun 1, 2021Local Law CLASS - 2
FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#802386. AGG1: PRIOR NOV#37013758R UNDER
#37021418K
Dec 1, 2022
IN VIOLATION
$1,250
Jan 12, 2021Boilers CLASS - 2
BOILER SHORT CYCLING COLD WATER SUPPLY IN WRONG LOCATION-2ND LWCO IN WRONG LOCATION-MANUAL RESET AQUASTAT IN WRONG LOCATION-NO ACCESS TO BASE OF CHIMNEY FOR CLEANING+INSPECTION-FRESH AIR LOUVER SCREEN 1/2 CLOGG
#39034728L
Jul 1, 2021
IN VIOLATION
$625
Mar 15, 2020Elevators CLASS - 1
97X10 DEVICE OUT OF SERVICE.NO ELEVATOR SERVICE IN THE BUILDING.
#38272899N
Aug 31, 2020
ADMIT/IN-VIO
$0
Oct 15, 2018Local Law CLASS - 2
FAILURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL# 802386. REMEDY: SUBMIT REQUIRED TECHNICAL REPORT
#37013758R
Jul 11, 2019
IN VIOLATION
$0
May 30, 2018Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED IN THE CELLAR IN A ROOM CONTAINING A GAS METER AND A CLOSING DOOR, SEVERAL PIECES OF I.T. AND ELECTRONIC EQUIPMENT. THIS IS PROHIBITED BYAPPENDIX
#35331946P
Dec 20, 2018
IN VIOLATION
$0
May 30, 2018Unknown CLASS - 1
UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS MATERIALS DEVICES APPLIANCES OR WIRING IN USE. OBSERVED THROUGHOUT THE BUILDING HALLWAYS RECEPTACLE OUTLETS NOT DESIGNED OR MADE TO BE TAMPER RESISTAN
#35334318H
Sep 27, 2018
IN VIOLATION
$0
May 30, 2018Unknown CLASS - 2
SEC. 400.8 USE OF FLEXIBLE CORD AS A PERMANENT WIRING METHOD OBSERVED THE INSTALLATION & CONNECTION OF RUBBER TYPE CORD TO BOILER ROOM VENTILATION THIS CORD IS INSTALLED THROUGH A CONCRETE TYPE BLACK WALL.
#35334319J
Sep 27, 2018
IN VIOLATION
$400
May 30, 2018Unknown CLASS - 2
FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTER(GFCI)PROTECTION OBSERVED IN ELEVATOR METER ROOM A DEFECTIVE GFCI OUTLETS,NO GFCI PROVIDED ABOVE DTHK IN EMPLYEE BREAK ROOM. REMEDY: COMPLY W/CODE/PROVIDE GFCI
#35334317X
Sep 27, 2018
IN VIOLATION
$2,400
Apr 11, 2018Boilers CLASS - 2
15,3,24B,50. FOUND A/O SMITH BOILER (H) STAMPED TO HAVE FLUE IN WRONG #50 GAUGE, IMPROPERLY SUPPORTED AND NOT FIRE DATED OUTSIDE BOILER ROOM #24 () REMOTE BOILER SWITCH OUTSIDE DOOR; 15-HOLES IN CEILING ROOM
#32096326H
May 31, 2018
STIPULATION/IN-VIO
$88
Apr 17, 2017Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 4/17/17 AT ABOVE ADDRESS NO SPRINKLER GAUGES ON ANY OF THE FLOORS AS PER 7.8.7(NFPA)& ALSO NO SPRINKLER CONTROL VALVES ISOLATING ANY OF THE FLOORS
#35252972N
Nov 9, 2017
IN VIOLATION
$0
Apr 17, 2017Unknown CLASS - 2
SEC. 320.30 ARMORED CABLES NOT PROPERLY SUPPORTED. AT THE TIME OF MY INSPECTION I OBSERVED ARMORED CABLES THROUGHOUT BASEMENT AREA HANGING &UNSUPPORTED OT STRAPPED TO EXISTING PIPES W/PLASTIC ZIP TIES THIS OS I
#35253016H
Aug 10, 2017
WRITTEN OFF
$0
Apr 17, 2017Plumbing CLASS - 1
SEC: FGC 411.1.6. UNIONS BEFORE APPLIANCE VALVE OBSERVED ON 4/17/17 @ ABOVE ADDRESS UNIONS INSTALLED ON GAS PIPE IN BSMT. ALSO FUTURE GAS CONNECTION EXIST IN BASEMENT AS PER FGC 408.2. PHOTOS TAKEN. REM: COMPLY
#35253311K
Jun 16, 2017
IN VIOLATION
$0
Nov 7, 2016Plumbing CLASS - 1
MISC VIOLATION.OBSERVED ON GAS LINE.144 BLK UNION ON GAS LINE.INSTALLED DOWN STREAM OF GAS APPLIANCES.GAS METER LOCATION-PHOTO TAKEN.REM:COMPLY WITH NOTICE OF VIOLATION.
#35208053Y
Dec 23, 2016
IN VIOLATION
$0
DOB (6)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#02743
DOB VIOLATION - ACTIVE
Sep 23, 2024LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
#02742
DOB VIOLATION - ACTIVE
Jun 30, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
#09211
DOB VIOLATION - ACTIVE
Feb 22, 2023NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9B TECHNICAL REPORT BY 2/21/2023
#01356
DOB VIOLATION - ACTIVE
Sep 2, 2020FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00471
DOB VIOLATION - ACTIVE
Jan 13, 1997LOCAL LAW 10/81 - ELEVATOR

#00674
DOB VIOLATION - ACTIVE
DOB NOW Safety (19)
IssuedViolationStatus
Oct 2, 2026Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Report
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Report
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Report
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Report
Active
Sep 23, 2024Boiler LBLVIO
Violation Issued-Failure To File 2023 External Low Pressure Inspection Report
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Report
Active
Jun 30, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
Active
Feb 22, 2023Facades FISPNRF
CYCLE 9B NO REPORT FILED
Active
Sep 2, 2020AEUHAZ FTC-AEU-HAZ
Active
Jul 31, 2018Facades FISPNRF
FAILED TO FILE FISP CYCLE 8B TECHNICAL REPORT BY 02/21/2018
Active
HPD (1) · C 0 · B 0 · A 1
IssuedClassViolationCorrect by
Apr 29, 2026A(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.Aug 2, 2026

Issued in the last 120 days

DateSourceWhatNow
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 31, 2026, 12:10 AM ET. BBL 1008570017.