4 floors · 161,280 sq ft · built 1920 · class W1 · owner of record: Nyc Department Of Education
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Gas piping inspection (2026 cycle) Likely applies Local Law 152 · During 2026 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2026 in 64 days | Due this year |
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 64 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 161,280 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 185 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 185 days | Annual filing |
| Energy audit and retro-commissioning (2029) Likely applies Local Law 87 · Calendar year 2029 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 369). Agency page | Dec 31, 2029 in 1160 days | Next due 2029 |
| Annual boiler inspection (3 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-09-14 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Apr 6, 2026 | Construction CLASS - 2 28-301.1. REISSUE: 35672602R-FAILURE TO PROVIDE VENTILATION TO GAS METER RM. PER 115.6(1968 CODE), FGC APPENDIX E(E4)(2014) CELLAR LEVEL GASMETER RM HAS NO VENTILATION. REMEDY: COMPLY WITH CODE. #35727317N | May 12, 2026 POP/IN-VIO | $0 |
| Apr 6, 2026 | Construction CLASS - 2 REISSUE: 35693217N-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. FRONT ENTRANCE MARBLE STEPS HAVE CRACKS, CHIPS, CREATES A TRIPPINGHAZARD. REMEDY: COMPLY WITH CODE. #35727316L | May 12, 2026 POP/IN-VIO | $0 |
| Apr 6, 2026 | Construction CLASS - 2 REISSUE: 35693218P-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. SCHOOL CLASSROOMS HAVE WINDOWS THAT ARE VERY FOGGY AND NOT VISIBLEAND WON'T OPEN. REMEDY: COMPLY WITH CODE. #35727315J | May 12, 2026 POP/IN-VIO | $0 |
| Apr 24, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT VERY HEAVILY TRAFFICED MAIN ENTRY THERE ARE CRACKS, CHIPS, LOOSE MARBLE STEP TREADS. THIS CREATES A TRIPPING HAZARD. SAME CONDITION EXISTS AT OTH #35693217N | May 19, 2025 POP/IN-VIO | $0 |
| Apr 24, 2025 | Construction CLASS - 2 28-301.1. RE-ISSUE #35672602R, #35677295Z. FAILURE TO PROVIDE NATURAL OR MECHANICAL VENTILATION TO THE GAS METER ROOM AND ILLEGAL STORAGE OFCOMBUSTIBLE MATERIALS IN THE GAS METER ROOM. REMEDY: PROVIDE VENTILATI #35693215J | May 19, 2025 POP/IN-VIO | $0 |
| Apr 24, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE ARE SEVERAL; THROUGH OUT THE SCHOOL WINDOWS THAT DON'T WORK AND/OR HAVE VERY BAD OR NO VISIBLITY. CAN'T OPEN, DON'T STAY OPEN, SLAM DOOR CLOSE #35693218P | May 19, 2025 POP/IN-VIO | $0 |
| Jun 20, 2024 | Construction CLASS - 2 28-301.1 REISSUED ECB #35672602R. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM. AT TIME OF INSPECTION OBSERVED IN CELLARS GAS METER ROOMNO VENTILATION. REMEDY: COMPLY WITH NOTICE OF VIOLATION. #35677294R | Aug 21, 2024 POP/IN-VIO | $0 |
| Feb 15, 2023 | Construction CLASS - 2 REISSUE #35655095R FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P 115.6(1968 CODE),FGC APPENDIX E(E4) (2014 CODE).NOTED:AT CELLAR LEVEL GAS METER ROOM HAS NOT MECHANICAL/NATURAL VENTILATION.REMEDY:COMPL #35672602R | Jun 7, 2023 POP/IN-VIO | $0 |
| Apr 25, 2022 | Construction CLASS - 2 RE-ISSUE #35553857R(4/28/21)FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE) FGC APPENDIX E(E4)(2014 CODE) AT CELLAR LEVEL GAS METER ROOM NO PROPER MECHANICAL/NATURAL VENTILATION.REMEDY:CO #35655095R | Oct 12, 2022 POP/IN-VIO | $0 |
| Apr 28, 2021 | Construction CLASS - 2 28-301 REISSUE25445122N FAILURE TO PROVIDE VENTILATION TO GAS METER RMPER P115.6(1968CODE).F6C APPENDIXE(E4)(2014CODE).@CELLAR LEVEL;GAS METER RM W/O MECHANICAL OR NATURAL VENTILATION ATOI.COMPLY W/NOTICE OF V. #35553857R | Sep 22, 2021 POP/IN-VIO | $0 |
| Apr 30, 2020 | Construction CLASS - 2 SEC. 28-301.1 REISSUE#35423379X FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P 115.6(1968 CODE),FGC APPENDIX E(EH)(2014 CODE).NOTED:AT CELLAR LEVEL IN THE GAS METER ROOM THERE'S NO FRESH AIR VENTILATION #35495122N | Oct 14, 2020 POP/IN-VIO | $0 |
| May 20, 2019 | Construction CLASS - 2 28-301.1 REISSUE #35326497M NOTED: THERE IS NO FRESH AIR VENTILATION IN THE GAS METER ROOM. REMEDY: COMPLY WITH NOTICE OF VIOLATION #35423379X | Sep 23, 2019 POP/IN-VIO | $0 |
| Apr 11, 2018 | Construction CLASS - 2 28-301.1 REISSUE 35260149R FAILURE TO PROVIDE VENTILATION TO GAS METERROOM PER P 115.6 (1968 CODE), FGC APPENDIX E (E4) (2014 CODE) NOTED: THERE IS NO FRESH AIR VENTILATION IN GAS METER ROOM. RMDY: COMPLY WITH #35326497M | Jul 2, 2018 POP/IN-VIO | $0 |
| May 3, 2017 | Construction CLASS - 2 SEC. 27-766 RE-ISSUE#35213659P FAILURE TO PROVIDE FRESH AIR VENTILATION IN THE GAS METER ROOM. REMEDY: COMPLY W/CODE/PROVIDE OR INSTALL. #35260149R | Aug 14, 2017 POP/IN-VIO | $0 |
| Sep 30, 2016 | Construction CLASS - 2 REISSUE 35128242M FRESH AIR IN GAS METER ROOM RS 16/P115.4 AND 6/TPPN 1 OF 1994, NO FRESH AIR VENT/INLET IN THE GAS ROOM. RMDY: ADD FRESH AIR VENTS. #35213659P | Feb 6, 2017 POP/IN-VIO | $0 |
| May 5, 2015 | Unknown CLASS - 2 REISSUE#35102058H.NOTE:FAILURE TO PROVIDE FRESH AIR VENTILATION IN THEGAS METER RM/REM:COMPLY W/THE NOTICE OF VIO. #35128242N | Aug 3, 2015 POP/IN-VIO | $0 |
| Jul 17, 2014 | Unknown CLASS - 2 27-766 REISSUE 34954522X. FRESH AIR IN GAS METER ROOM. FAILURE TO PROVIDE VENTILATION IN GAS METER ROOM. RMDY: PROVIDE VENTILATION. #35102058H | Sep 29, 2014 POP/IN-VIO | $0 |
| May 31, 2012 | Unknown CLASS - 2 REISSUE 34926546M GAS METER ROOM HAS NO FRESH AIR VENTILATION REM: PROVIDE VENTILATION #34954522X | Aug 13, 2012 POP/IN-VIO | $0 |
| Aug 25, 2011 | Unknown CLASS - 2 SEC. 27-766 NO FRESH AIR VENT AT CELLAR GAS METER ROOM, NO FRASH AIR VENTILATION. REMEDY : PROVIDE FRESH AIR VENT #34926546M | Oct 17, 2011 POP/IN-VIO | $0 |
None open.
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device | Active |
None open.
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 28, 2026, 5:40 PM ET. BBL 3003690001.