Manhattan · Block 303 · Lot 25 · 10002

61 Chrystie Street

11 floors · 40,529 sq ft · built 2006 · class H3 · owner of record: Lbw Enterprises, Llc.

15open violations
$54,350ECB/OATH penalties owed
0HPD class C (immediately hazardous)
168dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 47 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 40,529 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 168 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 168 days
Annual filing
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 778 days
Next cycle year 2028
Facade inspection report (Cycle 10C) Applies
Local Law 11 / FISP · Feb 21, 2027 to Feb 21, 2029
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 1, 2 or 3 are in sub-cycle 10C. DOB facade records for this building show $32,000 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2029
in 830 days
Filing window not open yet
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-05-01 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (8) · $54,350 owed
IssuedViolationHearingBalance
Jul 24, 2026Elevators CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11
#39197629M
Apr 15, 2027
PENDING
$6,250
Jun 25, 2026Elevators CLASS - 1
FAILURE TO MAINTAIN DEVICE IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE ONLY DEVICE IN THE SECTION OF THE BUILDING IS FOUND TO BE OUT OF SERVICE, CREATING
#39193779J
Aug 2, 2027
DEFAULT
$6,250
Apr 24, 2026Construction CLASS - 2
AT TIME OF INSPECTION, OBSERVED THE HVAC SYSTEM IN 1ST LOBBY, 11 AND 12 FLOOR HALL WAY IS NOT FUNCTIONAL, NOT THROWING OUT COLD AIR NOR GIVING OUT HEAT, BUILDING MAINTENANCE MANAGER TURNED IT ON WAITED FOR ABOU
#39185946H
Jul 2, 2026
DEFAULT
$6,250
Mar 30, 2026Unknown CLASS - 1
ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON 10TH, 7TH, 3RD FLS THAT THE ELECTRICAL CLOSET WAS TELEPHONE, WIFI, DATA EQUIPMENT INSTALLED. ALL ELECTRICAL CLOSETS/ RMS SH
#39183257N
Jun 11, 2026
DEFAULT
$6,000
Mar 30, 2026Unknown CLASS - 1
MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED IN THE MAIN ELECTRICAL RM IN SUB CELLAR THE SERVICE EQUIPMENT IS STARTING TO CORRODE DO TO STANDING WATER ON THE FLOOR. ALL LOCATIONS
#39183258P
Jun 11, 2026
DEFAULT
$4,000
Mar 30, 2026Unknown CLASS - 1
FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED IN THE MAIN ELECTRICAL RM IN THE SUB CELLAR THAT NO ELECTRODE GROUND WAS NOT INSTALLED. POTENTIAL FOR SHOCK AND LOST OF GROU
#39183259R
Jun 11, 2026
DEFAULT
$24,000
Mar 11, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. AT TIME OF INSPECTION OBSERVED AC UNIT INSTALLED INTO WALL, AND HOLE PENETRATION
#39141060Y
May 15, 2025
IN VIOLATION
$0
Jan 29, 2019Unknown CLASS - 2
400.8 USE OF FLEXIBLE CARDS AS PERMANENT WIRING. OBSERVED THROUGHOUT STAIRWELL FROM ROOF TOP AREA TO MECHANICAL CHASEWAY ON 11THFLOOR THE INSTALLATION OF FLEXIBLE RUBBER CUBES FROM A.C SPLIT SYSTEM
#35383928X
Apr 11, 2019
STIPULATION/IN-VIO
$1,600
DOB (0)

None open.

DOB NOW Safety (9)
IssuedViolationStatus
Jan 8, 2026Gas Piping - LL152 FTF-PL-PER
Cycle 2, Sub-cycle A (premises is in Community District 3)
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Nov 25, 2024Parking Structures FTF-PS-INITL
Failure to file sub cycle 1A compliance report by 12/31/2023
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Sep 11, 2024Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Report
Active
Sep 11, 2024Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Report
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Jul 24, 2026ECBElevators: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11Open

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 14, 2026, 1:27 PM ET. BBL 1003030025.