Queens · Block 2732 · Lot 18 · 11378

60-02 60 Lane

4 floors · 120,278 sq ft · built 1931 · class W1 · owner of record: Nyc Department Of Education

25open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
186dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 65 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 120,278 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 186 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 186 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 5 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1161 days
Next cycle year 2029
Energy audit and retro-commissioning (2032) Likely applies
Local Law 87 · Calendar year 2032
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2732). Agency page

Dec 31, 2032
in 2257 days
Next due 2032
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-03-12 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (10)
IssuedViolationHearingBalance
Mar 6, 2026Construction CLASS - 2
REISSUE#35691695Z ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-28-118.3.2.NOTED:NO COFO OR BUILDING TEMP#034208 EXPIRED 3/13/2023-NO NEW ONE ON FILE.REM:OBTAIN VA
#35729035Y
Mar 23, 2026
POP/IN-VIO
$0
Mar 6, 2026Construction CLASS - 2
REISSUE#35691693P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EMERGENCY LIGHTS NOT WORKING WHEN CHECKED,#'S 1,2,4
#35729037H
Mar 23, 2026
POP/IN-VIO
$0
Mar 6, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:INTERIOR SMOKE DOORS DO NOT SELF-CLOSE AT,4TH FLR-GYM BOTH ENTRANCE DOORS,3RD-GYM ENTRANCE DOOR ON THE RIGHT.CLASSROOM DOORS DO NOT SELF-CLOSE PROPERL
#35729038J
Mar 23, 2026
POP/IN-VIO
$0
Feb 20, 2025Construction CLASS - 2
REISSUE#35677213X ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1 & 28-118.3.2.NO COFO OR BUILDING TEMP 034208 EXP 3-13-2023 NO NEW ONE ON FILE.REM:OBTAIN A VALID CO
#35691695Z
Apr 29, 2025
POP/IN-VIO
$0
Feb 20, 2025Construction CLASS - 2
REISSUE#35677212Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.EMERGENCY LIGHTS NOT WORKING WHEN CHECKED.REM:REPAIR AND/
#35691693P
Apr 29, 2025
POP/IN-VIO
$0
Mar 5, 2024Construction CLASS - 2
ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-28-118.3.2.NOTED:TEMP CO#034908 EXPIRED ON 03/13/2023.NO RENEWAL ON FILE.BUILDING FULLY OCCUPIED WITH STUDENTS,TEACHE
#35677213X
May 2, 2024
POP/IN-VIO
$0
Mar 5, 2024Construction CLASS - 2
REISSUE#35665591P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EXISTING EMERGENCY LIGHTS NOT OPERATIVE WHEN TESTED
#35677212Y
May 2, 2024
POP/IN-VIO
$0
Jan 20, 2023Construction CLASS - 2
REISSUE #35577342Y FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1-27. 1-27-381. AT AUDITORIUM & LUNCH ROOM NOT WORKING WHEN TESTED.REME
#35665591P
May 9, 2023
POP/IN-VIO
$0
Jan 25, 2022Construction CLASS - 2
REISSUE #35577386X FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER ILLUMINATION FOR EXITS.EXIT DISCHARGE & PUBLIC CORRIDORS PER BC100601;27-381. IN AD&O UNIT 13A & 13B NOT WORKING & LUNCH ROOM UNIT 20F 20K
#35577342Y
May 3, 2022
POP/IN-VIO
$0
Jun 4, 2021Construction CLASS - 2
FAILURE TO MAINTAIN BUILDIG IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1-27-381 AT 1ST FLOOR LUNCH ROOM 3 PLACE EACH PLACE 3 LIGHTS EXIT LIGHT NO 20F 20K 20
#35577386X
Jun 16, 2021
POP/IN-VIO
$0
DOB (0)

None open.

DOB NOW Safety (15)
IssuedViolationStatus
Sep 18, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle B (premises is in Community District 5)
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2018 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 27, 2026, 7:15 AM ET. BBL 4027320018.