4 floors · 52,100 sq ft · built 1921 · class N9 · owner of record: 599 Ralph Avenue Deve
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Gas piping inspection (2026 cycle) Likely applies Local Law 152 · During 2026 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 16 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2026 in 67 days | Due this year |
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 67 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 52,100 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 188 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 188 days | Annual filing |
| Energy audit and retro-commissioning (2035) Likely applies Local Law 87 · Calendar year 2035 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 1475). Agency page | Dec 31, 2035 in 3354 days | Next due 2035 |
| Annual boiler inspection (5 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-05-13 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Apr 30, 2026 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIOONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT. OF BUILDINGS FOR VIOLATION #39134996X, FILE A CERTIFICATE OF CORRECTION #39186702X | Jul 8, 2026 DEFAULT | $0 |
| Nov 7, 2025 | Elevators CLASS - 1 CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B. EIR@BUILDINGS.NYC.GOV. FOR A REINSPECTION. CLASS 2 #39166304M | Dec 10, 2026 DEFAULT | $1,280 |
| Jan 9, 2025 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED UNPERMITTED PLASTIC ACCESS PANEL. ACCESS PANEL NO FIRE RATED. HOLE PENET #39134996X | Oct 29, 2026 | $2,530 |
| Jan 9, 2025 | Construction CLASS - 2 I OBSERVED IN THE 5TH FLOOR BOILER ROOM AT THE POINT OF EGRESS LEADING TO THE FIFTH FLOOR ROOF NO REMOTE SHUT-DOWN FOR THE BOILERS AS REQUIRED IN MC 1006.8.1. PHOTOS TAKEN. (PLEASE NOTE A SWITCH IS REQUIRED AT #39135001N | Oct 29, 2026 | $1,280 |
| Nov 28, 2023 | Construction CLASS - 2 OBSERVED IN THE BOILER ROOM LOCATED ON 5TH FLOOR EXCESSIVE LEAK ON PUMP. AS PC 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATING CONDITION IN ACC #39100235X | Jul 29, 2024 IN VIOLATION | $0 |
| Jun 27, 2023 | Boilers CLASS - 3 FRONT BOILER JACKET NOT IN PLACE/DOMESTIC WATER RELIEF VALVES NOT PIPED DOWN;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION #39089214M | Feb 2, 2024 IN VIOLATION | $0 |
| Jun 27, 2023 | Boilers CLASS - 2 POOR FLAME FROM BURNERS/IGNITION CONTROL UNIT DEFECTIVE/FRONT BOILER JACKET NOT IN PLACE;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION #39089215Y | Feb 2, 2024 IN VIOLATION | $0 |
| Issued | Violation | Status |
|---|---|---|
| Aug 16, 1993 | LOCAL LAW 62/91 - BOILERS #26328 | DOB VIOLATION - ACTIVE |
| Aug 16, 1993 | LOCAL LAW 62/91 - BOILERS #26329 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Oct 23, 2023 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2018 Cat1 Test Affirmation of Correction | Active |
None open.
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 25, 2026, 3:09 PM ET. BBL 3014750004.