Bronx · Block 2612 · Lot 29 · 10456

580 East 169 Street

1 floors · 2,400 sq ft · built 1999 · class Z9 · owner of record: Bronx-Lebanon Hosptlctr

6open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
774dto Gas piping inspection (2028 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 43 days
Keep the report on file (not filed with DOB)
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 774 days
Next cycle year 2028
Annual boiler inspection (3 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-02-04 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (4)
IssuedViolationHearingBalance
Feb 27, 2007Boilers Non-Hazardous
50 FULTON V.T. BOILER, 10HP,NB81798, GAS,1998.50-THE STEAM PRESSURE GAUGE HAS A DIAL RANGE OF 0-200PSI. THE SAFETY VALUE IS SET AT 150PSI. INSTALL A REPLACEMENT STEAM PRESSURE GAUGE TO RECORD 0-300PSI FOR CODE
#32053238H
Sep 7, 2007
IN VIOLATION
$0
Feb 24, 2007Boilers Non-Hazardous
50 FULTON V.T. BOILER,10HP,NB81790, GAS 1998.50-THE STEAM PRESSURE GAUGE HAS A DIAL RANGE OF 0-200PSI. THE SAFETY VALUE IS SET AT 150PSI. INSTALL A REPLACEMENT STEAM PRESSURE GAUGE TO RECORD 0-300PSI FOR CODE
#32053239J
Sep 7, 2007
IN VIOLATION
$0
Feb 24, 2007Boilers Non-Hazardous
50. FULTON V.T. BOILER,10HP,NB81769, GAS 1998.50-THE STEAM PRESSURE GAUGE HAS A DIDE RANGE OF 0-200 PSI. THE SAFETY VALVE IS SET AT 150PSIINSTALL A REPLACEMENT STEAM PRESSURE GAUGE TO RECORD 0-300PSI FOR CODE
#32053240R
Sep 7, 2007
IN VIOLATION
$0
Mar 8, 2004Boilers Non-Hazardous
50 FULTON H.P BOILER 1998 ISC NATL BD # 81790 50-REPLACE THE UNDERATEDBALL VALVE ON THE FEED WATER LINE ALL VALVES MUST BE RATED FOR 1.25 T IMES THE MAXIMUM BLOWABLE WORKING PRESSURE OF THE BOILER
#32044311K
Nov 26, 2004
IN VIOLATION
$0
DOB (0)

None open.

DOB NOW Safety (2)
IssuedViolationStatus
Dec 15, 2025Boiler FTC-BE-EXT-HP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for HP Device
Active
Oct 25, 2024Boiler FTC-BE-INT-HP
Violation Issued-Failure To File 2023 Internal Inspection Affirmation of Correction for HP Device
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 18, 2026, 6:09 AM ET. BBL 2026120029.