3 floors · 14,000 sq ft · built 1960 · class M1 · owner of record: Congregation Zemach David Dchasidei Squa Re
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 58 days | Keep the report on file (not filed with DOB) |
| Annual boiler inspection (1 boiler) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2023-02-15 (Accepted). Agency page | Dec 31, 2026 in 58 days | 1 of 1 without an accepted 2026 report yet |
| Gas piping inspection (2028 cycle) Likely applies Local Law 152 · During 2028 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 1 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2028 in 789 days | Next cycle year 2028 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Sep 22, 2025 | Construction CLASS - 1 UNLAWFUL ACTS.FAILURE TO COMPLY WITH COMMISSIONER'S ORDER FOR SUMMONS 35568428K.FAILURE TO OBTAIN PERMITS.REM:COMPLY WITH THE COMMISSIONER'SORDER. #35693550R | Nov 26, 2025 DEFAULT | $25,000 |
| Feb 25, 2025 | Construction CLASS - 1 FAILURE TO COMPLY AND CERTIFY CORRECTIONS FOR UNDERLINE VIOLATION # 35542963R WORK WITHOUT A PERMIT, COMPLY WITH COMMISSIONER'S ORDER #39139550Y | May 7, 2025 DEFAULT | $6,250 |
| Apr 27, 2022 | Boilers CLASS - 2 EXPOSED WIRES,SEAL BASE OF CHIMNEY,SEAL HOLES IN BOILER ROOM CORRECT VIOLATIONS & SEND IN CERTIFICATE OF CORRECTION #39061175Y | Aug 31, 2022 DEFAULT | $3,125 |
| Jan 31, 2022 | Construction CLASS - 1 FAILURE TO COMPLY W/COMMISSIONER'S ORDER CONTAINED IN SUMMONS/V35542963R ISSUED12/22/20&TO FILE C/C PURSUANT TO28-201.1&1RCNY102-01.NO PERMIT OR APP FILE TO COLLECT VIOLATING CONDITION FOR WORK W/O PERMIT COMPL #35568428K | Jun 15, 2022 IN VIOLATION | $2,500 |
| Nov 20, 2021 | Construction CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35542963R ISSUED ON 12/22/20 & TO FILE A CERT OF CORRECTION PURSUANT TO 28-201.1 & 1RCNY 102-01. REMEDY: COMPLY W/COMM'S ORDER &/OR FILE A CERT OF C #35565954R | Apr 27, 2022 IN VIOLATION | $1,250 |
| Sep 27, 2021 | Construction CLASS - 1 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35542963R ISSUED ON 12/22/20 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01.FOR WORK WITHOUT A PERMI #35563068N | Feb 9, 2022 DEFAULT | $6,250 |
| Aug 9, 2021 | Construction CLASS - 1 FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35542963K ISSUED ON 12/22/20 & TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 & 1RCNY 102-01.FOR WORK W/OUT A PERMIT.ERECTE #35534546X | Dec 22, 2021 DEFAULT | $12,500 |
| May 13, 2021 | Construction CLASS - 1 FAILURE TO COMPLY W/COMMISSIONER'S ORDER CONTAINED IN SUMMONS/V35542963R ISSUED12/22/20&TO FILE C/C PURSUANT TO28-201.1&1RCNY102-01.WORK W/OPERMIT.NOTED:VERT EXT OF LEGAL 2STY BLDG.ALSO INSTALLED WATER&WASTE LI #35530335H | Sep 22, 2021 IN VIOLATION | $2,500 |
| Dec 22, 2020 | Construction CLASS - 2 ALTERED/CHANGED BLDG OCCUPIED W/O VALID CERT OF OCCUPANCY AS PER 28-118.3.1/28-118.3.2 NOTED:AH(1)JOB#300660416 APPROVED8/11/97 NO PERMITS ISSUED OR NEW COFO ISSUED UNDER THIS APPLICATION NOW OBSERVED 3RDFL/ENT #35542964Z | May 5, 2021 DEFAULT | $6,250 |
| Dec 22, 2020 | Construction CLASS - 1 WORK W/O PERMIT NOTED:OBSERVED ERECTED VERTICAL 3RDSTY EXTENSION TO LEGAL 2STYBLDG @3RDSTY/FL ERECTED FULL HEIGHT PARTITIONS CREATING ROOMS INSTALLED WATER&WASTE LINES FOR VARIOUS BATHROOM (TOILETS)/SINKS THRUO #35542963R | May 5, 2021 IN VIOLATION | $2,500 |
| Aug 3, 2020 | Construction CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#39004209M ISSUED ON 06/17/19 & TO FILE A CERT OF CORRECTION PURSUANT TO 28-201.1 & 1RCNY 102-01(D)(2). AN ACCEPTIBLE CERTIFICATE HAS NOT YET BEEN FI #37020077R | Mar 10, 2021 IN VIOLATION | $1,250 |
| Sep 10, 2019 | Construction CLASS - 1 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35401868J ISSUED ON 02/27/19 & TO FILE A C OF C PURSUANT TO 28-201.1 & 1RCNY 102-01. REMEDY: COMPLY W/COMM'S ORDER &/OR FILE A C OF C. #35428216Y | Jan 27, 2021 IN VIOLATION | $0 |
| Sep 10, 2019 | Construction CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35401763N ISSUED ON 02-27-19 & TO FILE A C OF C PURSUANT TO 28-201.1 & 1RCNY 102-01. REMEDY: COMPLY W/COMM'S ORDER &/OR FILE A C OF C. #35428215M | Sep 18, 2020 IN VIOLATION | $625 |
| Jul 16, 2019 | Construction CLASS - 1 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35401868J ISSUED ON 2/2719,AND TO FILE A CERT.OF CORRECTION PURSUANT TO 28.201.1 & 1RCNY 102-01.REM;COMPLY WITH COMMISSIONER'S ORD #35400689J | Nov 18, 2019 IN VIOLATION | $627 |
| Jul 16, 2019 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35401763N ISSUED ON 2/27/19,AND TO FILE A CERT.OF CORRECTIONPURSUANT TO 28.201.1 & 1RCNY 102-01REM;COMPLY WITH COMMISSIONER'S ORD #35400690R | Nov 18, 2019 IN VIOLATION | $647 |
| Jun 27, 2019 | Boilers CLASS - 2 THE BOILER FLUE IS INCORRECTLY SUPPORTED-THE FRONT FLAME SIGHT GLASS IS DEFECTIVE #39004699Y | Nov 22, 2019 IN VIOLATION | $316 |
| Jun 17, 2019 | Boilers CLASS - 2 FOUND PEERLESS BOILER MODEL SC/SCT -09 ACTIVE AND OPERATING WITH DEFECTS. MISSING SPILL SWITCH. MISSING FIRE DAMPER. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION. #39004209M | Aug 5, 2019 STIPULATION/IN-VIO | $316 |
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2025 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION #10588 | DOB VIOLATION - ACTIVE |
| Jun 26, 2019 | FAIL TO CERTIFY CLASS 1 FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION #00841 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2025 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2018 External Inspection Affirmation of Correction for LP Device | Active |
| Jun 26, 2019 | AEUHAZ FTC-AEU-HAZ | Active |
| Issued | Class | Violation | Correct by |
|---|---|---|---|
| Jun 25, 2008 | B | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE WOOD FLOOR AT PRIVATE HALLWAY 2ND STORY APARTMENT 2. | Jul 30, 2008 |
| Jun 25, 2008 | B | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING SWITCH PLATE COVER ON WALL IN FRONT ROOM, 2ND STORY APARTMENT 2. | Jul 30, 2008 |
| Jun 25, 2008 | B | SECTION 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF CONCEALED LEAK AT CEILING IN REAR ROOM AND PRIVATE HALLWAY, 2ND STORY APARTMENT 2. | Jul 30, 2008 |
| Jun 25, 2008 | B | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE COLD WATER FAUCET HANDLE AT WASHBASIN 2ND STORY APARTMENT 2, BATHROOM. | Jul 30, 2008 |
| Jun 25, 2008 | B | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE CASEMENT WINDOWS IN BATHROOM, 2ND STORY APT. 2. | Jul 30, 2008 |
| Jun 25, 2008 | B | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE SASH CHAINS AT NORTH WEST WINDOW IN KITCHEN, 2ND STORY APARTMENT 2. | Jul 30, 2008 |
| Jun 25, 2008 | B | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE FLOOR OF METAL CABINET AT KITCHEN SINK, 2ND STORY APARTMENT 2. | Jul 30, 2008 |
| Jun 25, 2008 | B | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE ELECTRIC WALL LIGHT SWITCH IN BOTH FRONT ROOMS, 2ND STORY APARTMENT 2. | Jul 30, 2008 |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)