Queens · Block 2879 · Lot 31 · 11373

55-20 Van Horn Street

4 floors · 110,880 sq ft · built 1931 · class W1 · owner of record: Nyc Department Of Education

46open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
44dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 44 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 44 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 110,880 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 165 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 165 days
Annual filing
Energy audit and retro-commissioning (2029) Likely applies
Local Law 87 · Calendar year 2029
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2879). Agency page

Dec 31, 2029
in 1140 days
Next due 2029
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-03-03 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (15)
IssuedViolationHearingBalance
Apr 9, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED DEFECTIVERED FENCE AT REAR. REMEDY: REPAIR AND/OR REPLACE.
#35732189Y
May 13, 2026
POP/IN-VIO
$0
Apr 9, 2026Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING. NOTED EXIT DOORS #4, #5, #8 NOT SELF-CLOSING. REMEDY: REPAIR/REPLACE DOOR.
#35732188M
May 13, 2026
POP/IN-VIO
$0
Apr 9, 2026Construction CLASS - 2
REISSUED ECB #35720048M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 3RD FLOOR CORRIDOR BY ROOM #327 FLOOR TILES CRACKED, LOOSE AND BULGING. REMEDY: REPAIR AND/OR REPLACE.
#35732184P
May 13, 2026
POP/IN-VIO
$0
Apr 9, 2026Construction CLASS - 2
REISSUE ECB #35720049Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED ILLEGAL STORAGE AT ELECTRICAL ROOMS ON EACH FLOOR AT NEWSCHOOL AND AT ELECTRICAL ROOMS ON EACH FLOOR AT NEW SCHOOL AND AT ELEC
#35732183N
May 13, 2026
POP/IN-VIO
$0
Apr 9, 2026Construction CLASS - 2
REISSUED ECB #35720046Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORSPER BC 1006.1; 27-381. NOTED EMERGENCY LIGHTS NOT WORKING AT OLD AND N
#35732186Z
May 13, 2026
POP/IN-VIO
$0
Apr 9, 2026Construction CLASS - 2
REISSUED ECB #35720047K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED PARAPET WALL GUARD RAILS MISSING PANEL. ALSO SEVERAL SECTIONS OF THE GUARD RAILS LOOSE DUE TO MISSING BOLTS AT NEW SCHOOL. R
#35732185R
May 13, 2026
POP/IN-VIO
$0
Apr 9, 2026Construction CLASS - 2
REISSUED ECB #35720044P. ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY WITHOUT A VALID CERTIFICATE OF OCCUPANCYAS PER 28-118.3.1; 28-118.3.2. NOTED BUILDING OCCUPIED BY STUDENTS WIT
#35732187K
May 13, 2026
POP/IN-VIO
$0
May 28, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT NEW SIDE ROOF, PARAPET WALL GUARD RAILS MISSING PANEL, ALSO SEVERAL SECTIONS OF THE GUARD RAILS ARE LOOSE DUE TO MISSING BOLTS. POSES FALLING HAZARD. RE
#35720047K
Jul 9, 2025
POP/IN-VIO
$0
May 28, 2025Construction CLASS - 1
REISSUE #35677531L. ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-28-118-3.2. TEMP C OF O #402043374T042 EXPIRED ON -5/27/21. BUILDING WAS OCCUPIED BY STUDENTS, TE
#35720044P
Jul 9, 2025
POP/IN-VIO
$0
May 28, 2025Construction CLASS - 2
REISSUE #35677528K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. EMERGENCY LIGHTS NOT WORKING THROUGHOUT NEW SIDE DU
#35720046Z
Jul 9, 2025
POP/IN-VIO
$0
May 28, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER, AT 3RD FL CORRIDOR BY RM #327, FLOOR TILES ARE CRACKED, LOOSE AND BULGING, CREATING TRIPPING HAZARD. REMEDY: REPAIR AND/OR REPLACE.
#35720048M
Jul 9, 2025
POP/IN-VIO
$0
May 28, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED ILLEGAL STORAGE AT CARDBOARD BOXES INSIDE 1ST FL STAIR J. AT CELLAR ELECTRIC METER ROOM ILLEGAL STORAGE OF MISC. ITEMS BINS, VACUUMS, FLOOR BUFFERS,
#35720049Y
Jul 9, 2025
POP/IN-VIO
$0
Jun 3, 2024Construction CLASS - 1
ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID C OF O AS PER 28-118.3.1-28-118.3.2. NO C OF O TCO 102043374T042 EXP IN 2021 NO NEW C OF OON FILE. REMEDY: OBTAIN VALID C OF O OR DISCONTINUE ILLEGAL OCCUPANCY.
#35677531L
Aug 20, 2024
POP/IN-VIO
$0
Jun 3, 2024Construction CLASS - 2
REISSUE 35672794K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXIT DISCARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. 1ST FLOOR CORRIDOR EMG LIGHTS NOT WORK AND BY EXIT 7 NOT WOR
#35677528K
Aug 20, 2024
POP/IN-VIO
$0
Jul 11, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. ILLUMINATION FOR EXIT, EXIT DISCHARGES, AND PUBLIC CORRIDORS PER 1006.1;27-381. AT TIME OF INSPECTION OBSERVED AT 1ST FLOOR CORRIDOR EMERGENCY LIGHTS ARE N
#35672794K
Sep 27, 2023
POP/IN-VIO
$0
DOB (1)
IssuedViolationStatus
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#29334
DOB VIOLATION - ACTIVE
DOB NOW Safety (30)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Oct 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle C (premises is in Community District 4)
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2018 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Report
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of CorrectionOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 17, 2026, 2:37 PM ET. BBL 4028790031.