Brooklyn · Block 1041 · Lot 1 · 11215

535 4 Avenue

12 floors · 148 apartments · 116,530 sq ft · built 2015 · class D7 · owner of record: Xyz Properties Inc

5open violations
$3,125ECB/OATH penalties owed
0HPD class C (immediately hazardous)
Overdueto Annual property registration

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

OverdueRegistration expired 2026-09-01
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 67 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 67 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 67 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 83 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 116,530 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 188 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 188 days
Annual filing
Facade inspection report (Cycle 10C) Applies
Local Law 11 / FISP · Feb 21, 2027 to Feb 21, 2029
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 1, 2 or 3 are in sub-cycle 10C. Agency page

Feb 21, 2029
in 850 days
Filing window not open yet
Energy audit and retro-commissioning (2031) Likely applies
Local Law 87 · Calendar year 2031
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 1041). Agency page

Dec 31, 2031
in 1893 days
Next due 2031

Open violations

ECB / OATH (6) · $3,125 owed
IssuedViolationHearingBalance
Sep 4, 2026Elevators CLASS - 2
CLASS 2 ITEMS: FIRE-HAT SIGNAL LIGHT LITED LAMP MISSING FROM THE CAR OPERATING PANEL ASME A17.1 2.27.3.1.6(H). CAR ALARM BELL WORKS INTERMITTENTLY ASME A17.1 2.27. MAINTENANCE LOG BOOK NOT UPDATED ASME A17.1 8.
#39203139H
Nov 18, 2026
PENDING
$625
Jul 13, 2026Elevators CLASS - 2
CLASS 2 RTS: FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER AS PER BC 3001.2 & 27-987. UPON INSPECTION, THE DEVICE FOUND OUT OF SERVICE, CREATING A NON-COMPLIANT CONDITION AS PER 1 RCNY 11-02, WHICH RE
#39195932X
Oct 28, 2026
PENDING
$625
Oct 24, 2025Elevators CLASS - 2
CLASS 2: EMERGENCY PHONE INOPERATIVE, PROVIDE 2 WAY COMMUNICATION, PROPERLY SECURE TOP OF CAR JUNCTION BOX COVER. BEND DOWN FIRE TABS ON HOISTWAY DOORS RETAINERS (GIBS). CLEAN ENTIRE PIT AREA. TOP OF CAR ROLLER
#39164696L
Jan 7, 2026
IN VIOLATION
$625
Oct 24, 2025Construction CLASS - 2
OBSERVED ON THE ROOF GAS LINE HAS VISIBLE RUSTED AND IS NOT BEING PROTECTED. FIRST FLOOR PVC PIPING ON WASTE LINE. IN BASEMENT SPRINKLER HEADS OBSTRUCTED, TOILETS SEATS IN THE BATHROOMS ARE NOT OPEN END. NO TRA
#39164733L
Jan 7, 2026
IN VIOLATION
$1,250
Dec 12, 2024Unknown CLASS - 2
I OBSERVED IN THE ELECTRICAL CLOSETS THROUGHOUT THE BUILDING THE FAILURE TO PROPERLY SECURE THE BX CABLING PASSING THROUGH THE FLOOR. I NOTED THE CABLES HANGING WITHOUT BEING SECURELY FASTENED. PHOTOS TAKEN., S
#39132726R
Apr 2, 2025
IN VIOLATION
$0
Dec 12, 2024Unknown CLASS - 2
I OBSERVED IN THE ELEVATOR MOTOR ROOM THE EMT CONDUITS PASSING THROUGH THE CONCRETE FLOOR WITHOUT PROTECTION FROM DETERIORATING AGENTS (THE CONCRETE).; EC 110.11, COMPLY WITH EC CODE; USE ONLY AS PERMITTED.
#39132725P
Sep 19, 2025
IN VIOLATION
$0
DOB (1)
IssuedViolationStatus
Aug 16, 1993LOCAL LAW 62/91 - BOILERS

#21437
DOB VIOLATION - ACTIVE
DOB NOW Safety (0)

None open.

HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Sep 23, 2026DOB SafetyParking Structures: Failure to file parking structures compliance report by 12/31/2025 as required per 1 RCNY 103-13Closed
Sep 4, 2026ECBElevators: CLASS 2 ITEMS: FIRE-HAT SIGNAL LIGHT LITED LAMP MISSING FROM THE CAR OPERATING PANEL ASME A17.1 2.27.3.1.6(H). CAR ALARM BELL WORKS INTERMITTENTLY ASME A17.1 2.27. MAINTENANCE LOG BOOK NOT UPDATED ASME A17.1 8.Open
Jul 13, 2026ECBElevators: CLASS 2 RTS: FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER AS PER BC 3001.2 & 27-987. UPON INSPECTION, THE DEVICE FOUND OUT OF SERVICE, CREATING A NON-COMPLIANT CONDITION AS PER 1 RCNY 11-02, WHICH REOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 25, 2026, 12:28 AM ET. BBL 3010410001.

Look up another building