Manhattan · Block 1078 · Lot 23 · 10019

501 West 49 Street

8 floors · 159,996 sq ft · built 1959 · class H3 · owner of record: Piccadilly Hotel Co.,

72open violations
$39,375ECB/OATH penalties owed
2HPD class C (immediately hazardous)
45dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 45 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 45 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 159,996 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 166 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 166 days
Annual filing
Facade inspection report (Cycle 10B) Applies
Local Law 11 / FISP · Feb 21, 2026 to Feb 21, 2028
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 0, 7 or 8 are in sub-cycle 10B. DOB facade records for this building show $224,000 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2028
in 462 days
No Cycle 10 report on record yet
Energy audit and retro-commissioning (2028) Likely applies
Local Law 87 · Calendar year 2028
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 1078). Agency page

Dec 31, 2028
in 776 days
Next due 2028
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-10-05 (Pre-Filing-Pending Payment). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (37) · $39,375 owed
IssuedViolationHearingBalance
Oct 6, 2026Construction CLASS - 2
ATOI OBSERVED IN BALLROOM ON GROUND LEVEL SINK NOT VENTED PROPERLY USING STUDOR VENT. PER PC 910.1 INDIVIDUAL VENT PERMITTED. EACH TRAP AND TRAPPED FIXTURE IS PERMITTED TO BE PROVIDED WITH AN INDIVIDUAL VENT. T
#39206974P
Dec 10, 2026
PENDING
$1,250
Oct 6, 2026Construction CLASS - 2
MC 504.10 RIGID METAL DUCT WORK SHALL BE INSTALLED WITHIN THE SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE CONSTRUCTED OF SHEET STEEL. THE COMMON DUCTWORK DUCTS SHALL NOT BE CONNECTED OR INSTALLED WITH SH
#39206975R
Dec 10, 2026
PENDING
$3,125
Dec 10, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION#39076386X ISSUED ON 12/27/2022 AND #39088289M ISSUED ON 06/12/2023 FOR FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, FILE A CERTIFICATE OF CORR
#39169976Z
Feb 19, 2026
IN VIOLATION
$1,250
Dec 10, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION# 39099754M ISSUED ON 11/20/2023 FOR FAILURE TO OBEY A VACATE ORDER FROM THE COMMISSIONER( VACATE ORDER RESCINDED ON 09/11/2024), FILE A CERTIFICATE OF C
#39169978M
Mar 19, 2026
IN VIOLATION
$1,250
Dec 10, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION# 39099579Y ISSUED ON 11/16/2023 FOR FAILURE TO OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDINGS DEPARTMENT RECORDS.(LICEN
#39169979Y
Mar 19, 2026
IN VIOLATION
$1,250
Dec 10, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION# 37025534X ISSUED ON 10/11/2023 FOR UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER(ENGINEER REPORT ACCEPTED M00907410 ON 07/01/2024), FILE A
#39169977K
Feb 19, 2026
IN VIOLATION
$1,250
Dec 3, 2025Construction CLASS - 1
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION VIOLATION # 39125550R ISSUED ON 09/23/2024 FOR ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY., COMPLY WITH EC
#39169185M
Aug 31, 2026
IN VIOLATION
$500
Dec 3, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION VIOLATION # 39125552K ISSUED ON 09/23/2024 FOR FAILURE TO GROUND ELECTRICAL SYSTEMS., FILE A CERTIFICATE OF CORRECTION
#39169184K
Aug 31, 2026
IN VIOLATION
$1,250
Dec 3, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION VIOLATION # 39125520X ISSUED ON 09/23/2024 FOR FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, FILE A CERTIFICATE OF CORRECTION
#39169183Z
Aug 31, 2026
IN VIOLATION
$1,250
Dec 3, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION # 39125522J ISSUED ON 09/23/2024 FOR FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE, FILE A CERTIFICATE O
#39169181P
Aug 31, 2026
IN VIOLATION
$1,250
Sep 5, 2025Construction CLASS - 2
OBSERVED ON THE GROUND ,2 AND 7 FLOOR SPRINKLER HEADS OBSTRUCTED BY CAPS PAINTED TO THE CELLING. AND SPRINKLER HEADS BURIED IN THE CELLING'S WHICH OBSTRUCTS THE SPRAY PATTERNS OF THE SPRINKLER HEAD IN THE BASEM
#39159388N
Nov 13, 2025
IN VIOLATION
$1,250
Sep 23, 2024Construction CLASS - 2
OBSERVED 2 PAINTED SPRINKLER HEADS,ONE IN THE GARAGE AND THE OTHER ONE IN THE LOBBY. ALSO SPRINKLER HEAD IN THE STORAGE ROOM LOCATED NEXT TO LAUNDRY ROOM IS TO CLOSE TO THE OVERHEAD LIGHT. AS PER 102.3 OF THE P
#39125531L
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Construction CLASS - 1
OBSERVED EXCESSIVE HOLE PENETRATIONS LOCATED THROUGHOUT THE BUILDING., PROVIDE/MAINTAIN FIRE STOPPING
#39125521H
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Unknown CLASS - 2
I OBSERVED IN THE GARAGE (EAST SIDE) THE ELECTRICAL PANEL WITH A MAKESHIFT COVER THAT ALLOWS ACCESS TO THE ENERGIZED PARTS OF THE PANEL TO UNAUTHORIZED PERSONNEL. PHOTOS TAKEN., COMPLY WITH EC; INSTALL COVER FO
#39125551Z
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Unknown CLASS - 1
I OBSERVED IN THE BASEMENT GARAGE AREA (EAST SIDE) THE ELECTRICAL WATER MAIN GROUND CONDUCTOR DETACHED FROM THE WATER PIPE AS REQUIRED TO PROVIDE GROUNDING FOR THE BUILDING ELECTRICAL SYSTEM. ALSO NOTED THE WAT
#39125552K
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). OBSERV
#39125522J
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Unknown CLASS - 2
I OBSERVED THE INSTALLATION OF TWO DISCONNECTS LABELED A.C. 1&2 AND BRANCH CIRCUIT WIRING, CIRCUIT BREAKER PANELS IN THE STORAGE AREA NEAR THE LAUNDRY ROOM AND WALL MOUNTED EMERGENCY LIGHTING THROUGHOUT THE HAL
#39125548H
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Unknown CLASS - 1
I OBSERVED IN THE BASEMENT ELECTRICAL ROOM AND THE ROOM NEXT TO THE LAUNDRY ROOM, BREAKER ENCLOSURE AND THE ELECTRICAL PANELS MADE INACCESSIBLE BY BUILDING MATERIALS SHELVING AND BY THE INSTALLATION ITSELF. PHO
#39125550R
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Elevators CLASS - 1
DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL THE D.O.B. ELEVATOR DIVISION AT (212) 393-2144 FOR A REINSPECTION.CWT GUIDES WORN. REP
#39125507L
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Construction CLASS - 1
OBSERVED HORIZONTAL CRACK IN WALL ABOUT 5FT LONG. LOCATED BETWEEN 8E AND 7E STAIRWAY., REPAIR AND/REPLACE
#39125520X
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Elevators CLASS - 1
CONROLLER FUSE BYPASSED. CORRECT AND REPLACE. CLASS 2 ITEMS:IN-CAR COMMUNICATION INOPERATIVE. ADJUST CAR DOOR TO BE FULLY OPEN.
#39125506J
Jan 9, 2025
IN VIOLATION
$0
Sep 23, 2024Unknown CLASS - 2
I OBSERVED FAILURE TO PROVIDE GFCI OUTLETS/ OR PROTECTION IN THE MECHANICAL ROOMS THROUGHOUT THE BUILDING AS PER EC., INSTALL GFC1 PROTECTION; PROVIDE GFCI PROTECTION AS REQUIRED.
#39125549J
Jan 9, 2025
IN VIOLATION
$0
Apr 11, 2024Local Law CLASS - 2
FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #903344. REMEDY: SUBMIT ACCEPTABLE REQU
#37027875N
Jul 18, 2024
IN VIOLATION
$0
Feb 16, 2024Construction CLASS - 1
UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39076386X ISSUED ON 12/27/2022 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILUR
#39106239K
Apr 25, 2024
DEFAULT
$6,250
Dec 15, 2023Construction CLASS - 1
UNLAWFUL ACTS- FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS CONTAINED IN ECB# 39076386X ISSUED ON 12/27/2022 AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND RCNY102-01, COMPLY WITH COMM
#39101558P
Mar 21, 2024
DEFAULT
$6,250
Nov 20, 2023Construction CLASS - 1
UPON INSPECTION OBSERVED THE 1FLR. & CELLAR LEVEL ARE OCCUPIED AGAINST VACATE ORDER M171/2023, ISSUED ON 11/16/2023. CURRENTLY THERE IS APPROX. 31- VEHICLES PARKED AT 1FLR & APPROX. 84- VEHICLES PARKED AT CELLA
#39099754M
Jan 25, 2024
DEFAULT
$12,000
Oct 11, 2023Construction CLASS - 1
FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER IN DOB VIOLATION VIO23-01836,DATED 6/12/2023.RESPONDENT WAS REQUIRED TO SUBMIT AN ENGINEER'SREPORT CONCERNING STRUCTURALLY DEFICIENT CONDITIONS.AS OF 10/11/2023,A
#37025534X
Mar 28, 2024
IN VIOLATION
$0
Jun 12, 2023Construction CLASS - 1
OBSERVED SECTION OF CONCRETE MISSING AROUND STEEL BEAM IN CEILING AT VARIOUS LOCATIONS ALSO OBSERVED CONCRETE FLOOR FROM MIDDLE OF EXPOSURE 3 TO 4 WITH CAR AROUND THIS SECTION. UPON FURTHER INVESTIGATION OBSERV
#39088289M
Aug 17, 2023
IN VIOLATION
$0
Dec 27, 2022Construction CLASS - 1
AT EXPOSURE # 4, WEST SIDE,SECOND FLOOR, GLASS WINDOW BROKEN ON PEDESTRIAN SIDEWALK, REPAIR AND/REPLACE
#39076386X
Jun 22, 2023
IN VIOLATION
$0
Dec 27, 2022Construction CLASS - 2
OBSERVED: (EAST SIDE) AT ROOF LEVEL STAIR B (FRAME DAMAGE) & ELEVATOR RM, 4TH FL STAIR A, (WEST SIDE), AT PH CONFERENCE RM FRONT & BACK DOORS, EXIT DOOR FROM POOL LACKED, ROOF LEVEL EXIT DOOR AND ELEVATOR ROOM.
#39076387H
Jun 22, 2023
IN VIOLATION
$0
Dec 27, 2022Construction CLASS - 2
AT PH LEVEL,CONFERENCE ROOM CEILING DAMAGES, WEST SIDE, BOILER ROOM CEILING DAMAGES AND CMU WALLS CRACKED, OIL TANK RM BEAMS CRACKED AND EXPOSURE # 2 CORRIDOR ACCESS TO BOILER ROOM CEILING DAMAGES, REPAIR AND/O
#39076388J
Jun 22, 2023
IN VIOLATION
$0
Dec 27, 2022Construction CLASS - 2
OBSERVED: AT CELLAR LEVEL EAST & WEST SIDE ELECTRICAL/GAS METER RMS, WEST SIDE BOILER RM & SPRINKLER RM, LAUNDRY RM, AT ROOF LEVEL ELEVATOR MACHINE, PH ELECTRICAL CLOSET, SEVERAL OPENING THROUGH CEILING/WALLS A
#39076389L
Jun 22, 2023
IN VIOLATION
$0
Dec 27, 2022Construction CLASS - 2
-AT WEST SIDE, PH, CONFERENCE ROOM, 8TH FL CORRIDOR, 8TH FL STAIR E, 6TH FL CORRIDOR, 4TH/3RD CORRIDORS. EXISTING EMERGENCY LIGHTS WAS NO OPERATIONAL WHEN TESTED., REPAIR/REPLACE LIGHTING
#39076390Z
Jun 22, 2023
IN VIOLATION
$0
Dec 13, 2022Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED IN THE BOILER ROOM LOCATED IN THE BASEMENT/CELLAR 2 ACTIVE LEAKS ON THE O,S,&WYE VALUES AS PER 102.3 OF THE 2014 PLUMBING CODE,INSTALLATIONS BOTH E
#35657284P
Mar 2, 2023
DEFAULT
$0
Dec 13, 2022Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED IN LAUNDRY ROOM,GAS LEAK FOUND ON COMMERCIAL DRYER.AS PER 2022 FGC 102.3 INSTALLATIONS,BOTH NEW AND EXISTING AND PARTS THERE OF SHALL BE MAINTAINED
#35657283N
Mar 2, 2023
DEFAULT
$0
Apr 3, 2021Construction CLASS - 2
FAILURE TO MAINTAIN EXTERIOR BLDG FACADE OR APPURTENANCES.NOTE:AT TIMEOF INSPECTION,OBSERVED AT 1)EXP.#1,EAST ELEVATION;SPALLED-DEFECTED CONCRETE AT 1ST FL SLAB NEXT TO BRIDGE SECTION.(I)SEVERELY CRACKED CONCRE
#35548796X
Oct 17, 2022
DEFAULT
$0
Jan 30, 2021Construction CLASS - 1
OWNERS FAILURE TO REPAIR SWARMY CONDITION IN A TIMELY MANNER. ON 1-30-21 OBSERVED EXISTING CONDITION SWARMP AT WEST BUILDING CRACK AT CONCRETE COLUMN AT 1 FL CORNER OF EXPOSURE 1&EXPOSURE 2. OBSERVED AT EAST BL
#35549577K
Apr 15, 2021
ADMIT/IN-VIO
$0
DOB (14)
IssuedViolationStatus
Dec 11, 2024FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00276
DOB VIOLATION - ACTIVE
Dec 11, 2024FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00281
DOB VIOLATION - ACTIVE
Dec 11, 2024FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00280
DOB VIOLATION - ACTIVE
Dec 11, 2024FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00279
DOB VIOLATION - ACTIVE
Dec 11, 2024FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00278
DOB VIOLATION - ACTIVE
Dec 11, 2024FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00277
DOB VIOLATION - ACTIVE
Dec 11, 2024FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00275
DOB VIOLATION - ACTIVE
Dec 1, 2024FAILURE TO POST ENERGY GRADE/SCORE
FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
#2400264
DOB VIOLATION - ACTIVE
Nov 20, 2023CONSTRUCTION
FTM.ON 11/20/23,OBSRVD UNDERSIDE OF CELL/OR FRAMING FROM AMTRAK LINE IN STATE OF DISREPAIR.OBRSVD CRCKD/SPALLNG CONCRETE COVER@UNDERSIDE OF STEEL BEAMS,SPALLNG OF UNDERSIDE OF CNCRETE SLABS,&HEAVLY.OWNR TO ENGAGE NYS PE&ENDRSD CNTRCTR TO EVAL THE ENT PRKNG STRCTRE.OBTN PRMTS TO RPAIR NO LTR THAN 1/1
#FEU10401AK
DOB VIOLATION - ACTIVE
Oct 4, 2023FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00886
DOB VIOLATION - ACTIVE
Oct 4, 2023FAIL TO CERTIFY CLASS 1
FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
#00885
DOB VIOLATION - ACTIVE
Feb 22, 2023NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9B TECHNICAL REPORT BY 2/21/2023
#01863
DOB VIOLATION - ACTIVE
Dec 1, 2022FAILURE TO POST ENERGY GRADE/SCORE
FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
#2200246
DOB VIOLATION - ACTIVE
Dec 1, 2021FAILURE TO POST ENERGY GRADE/SCORE
FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
#2100556
DOB VIOLATION - ACTIVE
DOB NOW Safety (18)
IssuedViolationStatus
Nov 6, 2026GHG Emissions - LL97 FTF-EN-LL97320
FAILURE TO FILE AN ANNUAL BUILDINGS EMISSIONS REPORT AS REQUIRED BY AD CODE SEC. 28-320.3.7 IN ACCORDANCE WITH 1 RCNY § 103-14.
Active
Dec 8, 2025GHG Emissions - LL97 FTF-EN-LL97320
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Dec 11, 2024AEUHAZ FTC-AEU-HAZ
Active
Dec 11, 2024AEUHAZ FTC-AEU-HAZ
Active
Dec 11, 2024AEUHAZ FTC-AEU-HAZ
Active
Dec 11, 2024AEUHAZ FTC-AEU-HAZ
Active
Dec 11, 2024AEUHAZ FTC-AEU-HAZ
Active
Dec 11, 2024AEUHAZ FTC-AEU-HAZ
Active
Dec 11, 2024AEUHAZ FTC-AEU-HAZ
Active
Dec 1, 2024Energy Grade - LL33 FTP-EN-EGRDEA
Active
Nov 25, 2024Parking Structures FTF-PS-INITL
Failure to file sub cycle 1A compliance report by 12/31/2023
Active
Oct 4, 2023AEUHAZ FTC-AEU-HAZ
Active
Oct 4, 2023AEUHAZ FTC-AEU-HAZ
Active
Feb 22, 2023Facades FISPNRF
CYCLE 9B NO REPORT FILED
Active
Dec 1, 2022Energy Grade - LL33 FTP-EN-EGRDEA
Active
Dec 1, 2021Energy Grade - LL33 FTP-EN-EGRDEA
Active
HPD (8) · C 2 · B 4 · A 2
IssuedClassViolationCorrect by
Mar 23, 2026B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORYApr 27, 2026
Mar 23, 2026A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING AT PUBLIC HALL, 1st STORYJun 26, 2026
Mar 23, 2026C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT FIRE DOOR LEADING TO TRASH ROOM AT NORTH AT PUBLIC HALL, 2nd STORY, SECTION ''WEST''Apr 6, 2026
May 15, 2025B§ 27-2021 ADM CODE PROVIDE SUFFICIENT, PROPER AND SEPARATE METAL RECEPTACLES FOR THE DEPOSIT OF GARBAGE, RUBBISH AND OTHER WASTE MATERIAL AND ARRANGE FOR COLLECTION AND DISPOSAL OF SUCH MATERIAL.Jun 19, 2025
Mar 23, 2023BApt 516 · § 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE 1st ROOM FROM NORTH LOCATED AT B-ROOM 516, 5th STORY, 7th B-ROOM FROM NORTH AT EAST , SECTION ''NORTH''Apr 27, 2023
Mar 23, 2023BApt 516 · § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE 1st ROOM FROM NORTH LOCATED AT B-ROOM 516, 5th STORY, 7th B-ROOM FROM NORTH AT EAST , SECTION ''NORTH''Apr 27, 2023
Feb 15, 2023AApt 635 · § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE 2nd ROOM FROM NORTH LOCATED AT B-ROOM 635, 6th STORY, 2nd B-ROOM FROM EAST AT SOUTHMay 21, 2023
Jan 23, 2023CApt 315 · § 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.Jan 27, 2023

Issued in the last 120 days

DateSourceWhatNow
Nov 6, 2026DOB SafetyGHG Emissions - LL97: FAILURE TO FILE AN ANNUAL BUILDINGS EMISSIONS REPORT AS REQUIRED BY AD CODE SEC. 28-320.3.7 IN ACCORDANCE WITH 1 RCNY § 103-14.Open
Oct 6, 2026ECBConstruction: ATOI OBSERVED IN BALLROOM ON GROUND LEVEL SINK NOT VENTED PROPERLY USING STUDOR VENT. PER PC 910.1 INDIVIDUAL VENT PERMITTED. EACH TRAP AND TRAPPED FIXTURE IS PERMITTED TO BE PROVIDED WITH AN INDIVIDUAL VENT. TOpen
Oct 6, 2026ECBConstruction: MC 504.10 RIGID METAL DUCT WORK SHALL BE INSTALLED WITHIN THE SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE CONSTRUCTED OF SHEET STEEL. THE COMMON DUCTWORK DUCTS SHALL NOT BE CONNECTED OR INSTALLED WITH SHOpen
Sep 2, 2026ECBBoilers: FOUND EASCO SM4-200 DUAL FUEL BOILER WITH LEAKING SAFETY RELIEF VALVE, AND SMOKE ALARM BULB ON BREECHING NOT OPERABLE.Closed

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)