Bronx · Block 2906 · Lot 93 · 10457

463 East 173 Street

3 floors · 54,700 sq ft · built 1945 · class E9 · owner of record: Tasma Llc

13open violations
$12,590ECB/OATH penalties owed
0HPD class C (immediately hazardous)
45dto Energy audit and retro-commissioning (2026)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 45 days
Keep the report on file (not filed with DOB)
Energy audit and retro-commissioning (2026) Likely applies
Local Law 87 · Calendar year 2026
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2906). Agency page

Dec 31, 2026
in 45 days
Due this year
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2024-01-17 (Accepted). Agency page

Dec 31, 2026
in 45 days
1 of 1 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 54,700 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 166 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 166 days
Annual filing
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 776 days
Next cycle year 2028

Open violations

ECB / OATH (14) · $12,590 owed
IssuedViolationHearingBalance
Dec 30, 2025Construction CLASS - 2
OBSERVED THROUGHOUT THE BUILDING OBSTRUCTED SPRINKLER HEADS , MISSING TRAP WRAP INSULATION UNDER BATHROOMS SINKS AND MISSING ESCUTCHEON PLATES FOR WATER LINES GOING TO TOILETS. SECOUND FLOOR BATHROOM OPEN WASTE
#39171903K
Jul 17, 2026
IN VIOLATION
$1,250
Dec 30, 2025Construction CLASS - 2
OBSERVED ON THE GROUND FLOOR: THE WATER METER AND SPRINKLER MAIN ARE LOCATED IN THE SAME ROOM AS THE ELECTRICAL SERVICE METER, AND THE DEDICATED SPRINKLER LINE IS CONNECTED TO THE DOMESTIC WATER LINE WHICH IS C
#39171904M
Apr 6, 2027
PENDING
$1,250
Apr 8, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED PAINTED SPRINKLER HEAD IN STAIRWELL B. LOCATED ON THE 2ND FLOOR. ALSO FALLEN PLASTER NEXT TO SPRINKLER PIPE., REPAIR AND/OR REPLACE
#39144221J
Oct 3, 2025
IN VIOLATION
$0
Apr 7, 2025Elevators CLASS - 2
CLASS 2 ITEM: HOIST ROPES SHOW SIGNS OF ROUGE. REPLACE.
#39144082Z
Jun 20, 2025
STIPULATION/IN-VIO
$315
Sep 5, 2023Unknown CLASS - 2
I OBSERVED IN THE LOBBY THE USE OF EXTENSION CORDS TO SUPPLY POWER FOR THE X-RAY SCANNER. AS PER EC 400.8 THE USE OF FLEXIBLE CORDS AS WIRING FOR PERMANENT FIXED EQUIPMENT IS NOT PERMITTED.; EC 400.8, COMPLY WI
#39094097Z
Mar 28, 2025
IN VIOLATION
$400
Sep 5, 2023Construction CLASS - 2
I OBSERVED ON THE 3RD FLOOR THE HOT WATER HEATER ROOM WITH NO REMOTE SHUT-DOWN AS REQUIRED IN MC 1006.8.1 FOR THE GAS FIRED SYSTEMS.; MC 1006.8.1, COMPLY WITH CODE
#39094099M
Oct 24, 2025
IN VIOLATION
$1,250
Sep 5, 2023Construction CLASS - 2
OBSERVED ON THE 3RD FLOOR IN THE WATER HEATER ROOM SPRINKLER HEAD IS OBSTRUCTED BY CEILING. AS PER 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERAT
#39094073Y
May 6, 2024
DEFAULT
$3,125
Apr 10, 2023Unknown CLASS - 2
I OBSERVED ON THE LOWER ROOF THE UNPERMITTED USE OF EMT IN AN OUTDOOR INSTALLATION, SUPPLYING POWER TO THE ROOF HVAC SYSTEMS. PHOTOS TAKEN., COMPLY WITH EC CODE; USE PROPER RACEWAYS.
#39083520N
Jun 16, 2023
DEFAULT
$1,250
Apr 10, 2023Boilers CLASS - 2
SAFETY VALVE IS LEAKING-BACK FLOW VALVE LEAKING AND FLOODING UP BOILER ROOM FLOOR-BALL VALVE ON HOT WATER PIPE TO MIXING VALVE IS LEAKING ON FLOOR.
#39083333H
Jan 26, 2024
IN VIOLATION
$625
Apr 10, 2023Construction CLASS - 2
SPRINKLER HEAD ON THE WATER HEATER ROOM LOCATED ON THE 3RD FLOOR IS OBSTRUCTED BY CEILING. AS PER102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATIN
#39083388P
Aug 4, 2023
IN VIOLATION
$0
Apr 10, 2023Construction CLASS - 2
I OBSERVED ON THE ROOFTOP BOILER ROOM ENTRANCE NO REMOTE SHUT-DOWN FOR THE FUEL BURNING SYSTEMS AS REQUIRED IN MC 1006.8.1. A REMOTE SHUT-DOWN SHALL BE INSTALLED FOR ALL THE GAS FIRED SYSTEMS AT THE IMMEDIATE P
#39083519X
Jan 2, 2024
DEFAULT
$3,125
Jun 7, 2001Construction Non-Hazardous
WORK WITHOUT A PERMIT. <NOTED>CONSTRUCTIONS OF CONCRETE WALLS AT THE FRONT AND SIDE (E.173ST) OF PROPERTY APPROX 70'X70'X23' HIGH. REMEDY:OBTAIN APPROVALS AND PERMIT IF FEASIBLE OR REMOVE ILLEGAL CONSTRUCTION.
#34270871R
Aug 3, 2001
WRITTEN OFF
$0
May 25, 1999Construction Non-Hazardous
WORK W/O A PERMIT. WORK NOTED: CONSTRUCTION OF CONCRETE BLOCK WALLS ATFRONT & SIDE OF PROPERTY APPROX 70'X70'X23'. REMEDY: OBTAIN PERMIT ORRESTORE PREMISES TO PRIOR LEGAL CONDITION.
#34188136H
Nov 26, 1999
WRITTEN OFF
$0
Mar 23, 1998Construction Non-Hazardous
WORK WITHOUT A PERMIT. WORK NOTED: HAVING CONSTRUCTED MASONRY BLOCK WALLS APPROX 50'X50' AT FRONT & SIDE. REMEDY: FILE PLANS & OBTAIN APPROVAL W/ PERMIT OR RESTORE BACK TO LEGAL PRIOR CONDITION.
#34166321M
Jun 12, 1998
WRITTEN OFF
$0
DOB (0)

None open.

DOB NOW Safety (3)
IssuedViolationStatus
Jan 8, 2026Gas Piping - LL152 FTF-PL-PER
Cycle 2, Sub-cycle A (premises is in Community District 3)
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 16, 2026, 5:35 AM ET. BBL 2029060093.