Manhattan · Block 734 · Lot 7 · 10018

449 West 36 Street

10 floors · 12,340 sq ft · built 2005 · class H3 · owner of record: Essence Hotel Ii Llc

0open violations
$15,736ECB/OATH penalties owed
0HPD class C (immediately hazardous)
52dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 52 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 52 days
Keep the report on file (not filed with DOB)
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $390,000 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2027
in 104 days
No Cycle 10 report on record yet

Open violations

ECB / OATH (10) · $15,736 owed
IssuedViolationHearingBalance
Mar 10, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED GAS AND CARBON MONOXIDE SPILLAGE IN SPRINKLER ROOM. FROM HOT WATER HEATER UNITS. CON ED SHUT OFF BOTH HWT UNITS, AND A TAGGED BOTH. LOCATED AT BAS
#39179968H
Mar 25, 2027
$2,500
Mar 10, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS. LOCATED AT BASEMENT LEVEL ON THE CEILING. PARTIAL HOLE COVERED WITH VENT GRILL COVERS., REPAIR AND/REPLACE
#39179967X
May 21, 2026
DEFAULT
$6,250
Feb 19, 2026Unknown CLASS - 1
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN ELEVATOR MACHINE RM ON ROOM EXTENSION CORD BEING USED TO POWER A/C FROM OUTSIDE GFCI LO
#39177995Y
Feb 26, 2027
$1,600
Jan 20, 2026Boilers CLASS - 2
@CELLAR MECH ROOM>GAS HOT WATER HEATERS HAVE CORRODED FLUE@HEATERS+IN DROP CEILING+DRAFT INDUCER@TOP OF CHIMNEY IS MISSING DRAFT PROVING SWITCH INTERLOCKED WITH EACH WATER HEATER, MAINTAIN BOILER; CORRECT VIOLA
#39174457N
Jul 9, 2026
IN VIOLATION
$625
Aug 13, 2024Unknown CLASS - 1
I OBSERVED ON ALL FLOORS THE FAILURE TO PROVIDE TAMPER-RESISTANT/PROOF RECEPTACLES AS PER LL 39/2015 RECEPTACLES IN THE COMMON HALLWAYS ACCESSIBLE TO CHILDREN SHALL BE MADE TAMPER PROOF. THIS IS AN IMMEDIATE SH
#39121780Y
Jul 10, 2025
IN VIOLATION
$800
Aug 13, 2024Unknown CLASS - 1
I OBSERVED IN THE ELEVATOR MOTOR ROOM, THE FIRST FLOOR, AND UNDER THE BASEMENT STAIRS THE UNPERMITTED USE OF FLEXIBLE CORDS AS PERMANENT WIRING, AS PER EC 400.8 FLEXIBLE WIRING SHALL NOT PASS THROUGH WALLS, CON
#39121779R
Jul 10, 2025
IN VIOLATION
$800
Aug 13, 2024Unknown CLASS - 1
I OBSERVED IN THE BASEMENT AREA ELECTRICAL ROOM AND THE ELECTRICAL GROUND SYSTEM IN THE WATER METER ROOM THE EQUIPMENT IN A STATE OF CORROSION DUE TO WATER LEAKS AND STANDING WATER CONDITIONS. AS PER EC 110.11
#39121781X
Jul 10, 2025
IN VIOLATION
$1,600
Aug 8, 2024Construction CLASS - 1
OBSERVED RUSTED AND CORRODE GAS PIPING IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. AS PER 102.3 ON THE PLUMBING CODE MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINT
#39121341M
Dec 11, 2025
IN VIOLATION
$312
Aug 8, 2024Construction CLASS - 1
OBSERVED EXCESSIVE STORAGE IN THE MECHANICAL ROOMS THROUGHOUT BUILDING AND ALSO IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. AS PER E3 OF THE FUEL GAS CODE GAS METER ROOMS, WHEN PROVIDED, SHALL AT ALL
#39121340K
Dec 11, 2025
IN VIOLATION
$312
Aug 6, 2024Boilers CLASS - 1
FLUE SPILLAGE AT THE DIVETER OF BOTH RHEEM WATER HEATERS. FLUE PIPE IS CORRODED & THERE IS NO CHIMNEY CLEAN OUT FOR THE FLUE PIPE.CEASE USE BOTH WATER HEATERS. CORRECT ALL HAZARDOUS CONDITIONS IMMEDIATELY., MAI
#39120983J
Oct 10, 2024
IN VIOLATION
$937
DOB (0)

None open.

DOB NOW Safety (0)

None open.

HPD (0)

None open.