Manhattan · Block 1050 · Lot 7501 · 10036

440 West 41st Street

14 floors · 9 apartments · 53,177 sq ft · built 1988 · class RM · owner of record: 440 W 41 Owner Llc

10open violations
$60,055ECB/OATH penalties owed
0HPD class C (immediately hazardous)
Overdueto Annual property registration

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

OverdueRegistration expired 2025-09-01
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 47 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 47 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 47 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 63 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 53,177 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 168 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 168 days
Annual filing
Facade inspection report (Cycle 10B) Applies
Local Law 11 / FISP · Feb 21, 2026 to Feb 21, 2028
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 0, 7 or 8 are in sub-cycle 10B. DOB facade records for this building show $342,500 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2028
in 464 days
No Cycle 10 report on record yet
Energy audit and retro-commissioning (2030) Likely applies
Local Law 87 · Calendar year 2030
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 1050). Agency page

Dec 31, 2030
in 1508 days
Next due 2030

Open violations

ECB / OATH (20) · $60,055 owed
IssuedViolationHearingBalance
Apr 7, 2026Unknown CLASS - 1
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN THE SUB CELLAR IN THE JANITORS CLOSET ONE ELECTRIC HOT WATER HEATER HAS NO MEANS OF DIS
#39183551Y
Mar 4, 2027
PENDING
$1,600
Apr 7, 2026Unknown CLASS - 1
FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED IN THE MAIN ELECTRICAL ROOM NO INSTALLATION OF ELECTRODE GROUND ROD PRESENT. THIS IS SECOND MEANS OF GROUNDING MUST PROVIDE.
#39183550M
Mar 4, 2027
PENDING
$4,800
Oct 14, 2025Construction CLASS - 2
AT TIME OF INSPECTION, WORK COMPLETED UNDER PERMIT M08021119-I1-EL EXPIRING ON 10/29/2025 HOWEVER FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION # 39131574M ISSUED ON 11/27/2024 FOR ELECTRICAL WORK W
#39163586X
Dec 18, 2025
DEFAULT
$6,250
Nov 27, 2024Unknown CLASS - 2
I OBSERVED IN THE CORRIDORS AT THE STAIRWAY ENTRANCES THE EMERGENCY LIGHTS INSTALLED UNDER PERMIT# M00915799 INSTALLED WITH CANOPY BASE MISSING AND THE JUNCTION BOX AND WIRES EXPOSED., PERFORM PROPER INSTALLATI
#39131572Z
Feb 6, 2025
ADMIT/IN-VIO
$0
Nov 27, 2024Construction CLASS - 1
I OBSERVED IN DOB RECORDS THE SUBMISSION OF C OF C #0249597 ON 08/03/2023 FOR ECB# 39088336X WITH NO PERMIT INCLUDED. THE COMMISSIONER'S ORDER STATE THAT ALL REQUIRED PERMITS SHALL BE OBTAINED., COMPLY WITH COM
#39131573K
Feb 6, 2025
DEFAULT
$6,250
Nov 27, 2024Construction CLASS - 1
UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB 39088338J ISSUED ON 06/12/2023 AND SUBMIT A C OF C., COMPLY WITH COMMISSIONER'S ORDER; FILE A C OF C FOR CORRECTION OF VIOLATING CONDI
#39131571R
Feb 6, 2025
DEFAULT
$6,250
Nov 27, 2024Unknown CLASS - 1
I OBSERVED IN DOB RECORDS THE FAILURE TO SUBMIT AN ELECTRICAL PERMIT FOR THE WORK COMPLETED FOR ECBS # 39088336X,& 39088338J ISSUED ON 06/12/2023. ALL ELECTRICAL WORK SHALL BE PERMITTED PRIOR TO BEGINNING WORK.
#39131574M
Aug 28, 2026
ADMIT/IN-VIO
$0
Jun 12, 2023Unknown CLASS - 1
I OBSERVED ON ALL FLOORS IN THE COMMON HALLWAYS THE CONVENIENCE OUTLETS NOT OF THE TAMPER RESISTANT TYPE NOR MADE TAMPER RESISTANT AS REQUIRED BY LL 39. ALL RECEPTACLES ACCESSIBLE TO CHILDREN BELOW THE HEIGHT O
#39088336X
Feb 8, 2024
DEFAULT
$4,000
Jun 12, 2023Elevators CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11
#39088277P
Feb 8, 2024
DEFAULT
$3,125
Jun 12, 2023Unknown CLASS - 2
I OBSERVED ON FLOORS 8 THRU 13 THE INSTALLATION OF EMERGENCY LIGHTS AT LEAST 6 INCHES BELOW THE OPENING OF THE STAIRWAY DOOR. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALL TO AVOID PHYSICAL DAMAGE. ALSO NOTED NO EQ
#39088337H
Feb 8, 2024
DEFAULT
$4,000
Jun 12, 2023Unknown CLASS - 1
I OBSERVED ON THE 10 FLOOR I N THE METER ROOM THE INSTALLATION OF DATA WIRING EQUIPMENT AS PER THE EC THE ELECTRICAL CLOSET SHALL BE DEDICATED TO ELECTRICAL DISTRIBUTION ELECTRICAL EQUIPMENT ONLY. PHOTOS TAKEN.
#39088339L
Feb 8, 2024
DEFAULT
$3,000
Jun 12, 2023Unknown CLASS - 2
I OBSERVED IN THE SECOND FLOOR LAUNDRY ROOM THE FAILURE TO INSTALL GFCI RECEPTACLE OUTLETS BEHIND THE WASHING MACHINES WHICH ARE WITHIN 6' (FEET) OF A SINK. PHOTOS TAKEN., INSTALL GFC1 PROTECTION; PROVIDE GFCI
#39088338J
Feb 8, 2024
DEFAULT
$5,000
Jun 12, 2023Construction CLASS - 2
-HOLE PENETRATION ARE FILLED WITH UNPERMITTED FOAM MATERIAL LOCATED THROUGHOUT ALL MECHANICAL ROOMS LOCATED AT SUB-CELLAR LEVEL., PROVIDE/MAINTAIN FIRE STOPPING; REPAIR AND/OR REPLACE
#39088327Y
Feb 8, 2024
DEFAULT
$3,125
Jun 12, 2023Construction CLASS - 2
EMERGENCY EXIT DOORS ARE NOT INSTALLED/HINDGED TO ALLOW OCCUPANTS TO ESCAPE ROOF PROPERLY, (EMERGENCY EXIT DOORS OPEN INTO THE STAIR CORRIDOR) LOCATED AT ROOF LEVEL., PROVIDE LEGAL HARDWARE; REPAIR AND/OR REPLA
#39088326M
Feb 8, 2024
DEFAULT
$1,562
May 30, 2019Construction CLASS - 1
BC907.2.8 FAILURE TO PROVIDE FIRE ALARM SYSTEM FOR TRANSIENT USE FOUND IN APT 9B. PREVIOUS VIOLATION 55418040K. RMDY: DISCONTINUE ILLEGAL OCCUPANCY.
#35417694P
Mar 10, 2022
IN VIOLATION
$3,125
May 30, 2019Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 703.2 - 27954 FOR TRANSIENT USE FOUND IN APT 9B. PREVIOUS VIOLATION 35418039N. RMDY:DISCONTI
#35417693N
Mar 10, 2022
IN VIOLATION
$781
May 30, 2019Quality of Life CLASS - 1
PERMANENT DWELLING USED/CONVERTED FROM OTHER THAN PERMANENTN RESIDENTIAL PURPOSES. CO/O #113993 INDICATES BUILDING TO BE LEGALLY APPROVED ASA CLASS "A" M.D. NOW APT #9R USED/CONVERTED TO TRANSIENT USE NOTED: HA
#35417692L
Mar 10, 2022
IN VIOLATION
$3,125
May 24, 2019Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLER WHERE REQUIRED AS PER BC 903.2 AND 27-954 FORTRANSIENT USE OF APT #10F AND APT #12A. RMDY: DISCONTINUE ILLEGAL USE.
#35418039N
Jan 27, 2022
IN VIOLATION
$312
May 24, 2019Quality of Life CLASS - 1
PERMANENT DWELLING USED/CONVERTED FOR OTHERN THAN PERMANENT RESIDENTIAL PURPOSEDS. COFO #113993 INDICATES PREMISES TO BE LEGALLY APPROVED ASA CLASS "A" MULTIPLE DWELLING. NOW APARTMENTS #10F AND 12A HAVE BEEN
#35418038L
Jan 27, 2022
IN VIOLATION
$1,250
May 24, 2019Construction CLASS - 1
BC 907.2.8 FAILURE TO PROVIDE FIRE ALARM SYSTEM FOR TRANSIENT USE AT APT 10E AND 12A. RMDY: DISCONTINUE ILLEGAL USE.
#35418040K
Jan 27, 2022
IN VIOLATION
$2,500
DOB (0)

None open.

DOB NOW Safety (4)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of CorrectionOpen
Jul 30, 2026DOB SafetyAEUHAZ: Open
Jul 30, 2026DOB SafetyAEUHAZ: Open

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 14, 2026, 2:23 PM ET. BBL 1010507501.

Look up another building