Brooklyn · Block 998 · Lot 1 · 11215

411 4 Avenue

4 floors · 43,950 sq ft · built 1916 · class W2 · owner of record: Roman Catholic Church Of St. Thomas Aqui Nas

20open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
66dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 66 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 66 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 43,950 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 187 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 187 days
Annual filing
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-03-11 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (16)
IssuedViolationHearingBalance
Apr 10, 2026Construction CLASS - 2
REISSUE#35693204Y AT THE TIME OF INSPECTION,THE FOLLOWING EMERGENCY LIGHTS WERE INOPERABLE BOX#11 ON 1ST FLOOR,BOX#13 IN STAIRCASE A ON 2ND FLOOR,BOX#17,#18,#23,,#8,#12.REM:REPAIR/REPLACE LIGHTING.
#35731615N
May 28, 2026
POP/IN-VIO
$0
Apr 10, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.THE FOLLOWING DOORS WERE NOT SELF-CLOSING.AT THE TIME OF INSPECTION,STAIR B AT BASEMENT,STAIR A ON 1ST FLOOR,STAIR B ON 2ND FLOOR STAIRCASE BW ON 2ND FLOOR
#35731612H
May 26, 2026
POP/IN-VIO
$0
Apr 10, 2026Construction CLASS - 2
REISSUE#35693208L AT THE TIME OF INSPECTION,THE REOWNING WALLS AROUND PLAY AREA HAS CRACKS,ESPECIALLY THESE AREAS WITH METAL POSTS.REM:REPAIR AND/OR REPLACE.
#35731611X
May 28, 2026
POP/IN-VIO
$0
Apr 10, 2026Construction CLASS - 2
REISSUE#35693207J AT THE TIME OF INSPECTION,MULTIPLE WINDOWS WERE NOT WORKING PROPERLY HARD TO OPEN,SLAM SHUT DO NOT OPEN.A WINDOW IN ROOM 301 DOES NOT STAY CLOSE.A WINDOW IN ROOM 218 DOES NOT STAY CLOSE.BUBBLI
#35731614L
May 26, 2026
POP/IN-VIO
$0
Apr 16, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE ARE SEVERAL WINDOWS THROUGHOUT THE SCHOOL NOT WORKING PROPERLY. HARD TO OPEN TO OPEN, WON'T OPEN, WON'T STAY OPEN, SLAM SHUT. REMEDY: REPAIR/R
#35693207J
May 22, 2025
POP/IN-VIO
$0
Apr 16, 2025Construction CLASS - 2
RE-ISSUE #35864631Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT T. O. I. THERE WERE SEVERAL EMERGENCY LIGHTS SCATTERED
#35693204Y
May 22, 2025
POP/IN-VIO
$0
Jul 9, 2024Construction CLASS - 2
REISSUE #35672058M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT TIMEOF MY INSPECTION I OBSERVED AT THE 4TH FLOOR
#35684631Y
Aug 16, 2024
POP/IN-VIO
$0
Mar 9, 2023Construction CLASS - 2
REISSUE 35554002X WORK W/O PERMIT.EXP #3 7TH STREET SIDE OF YARD CURB CUT MADE APROX 25 IN LENGTH SO CARS CAN ENTER YARD AREA.REMEDY:OBTAIN ALL PERMITS.
#35672059Y
Jun 7, 2023
POP/IN-VIO
$0
Mar 9, 2023Construction CLASS - 2
REISSUE 35643274Y FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS.4TH FL GYM & STAIRCASE A&B LIGHTS NOT WORKING WHEN TESTED.REMEDY:REPAIR/REPLACE
#35672058M
Jun 7, 2023
POP/IN-VIO
$0
Apr 22, 2022Construction CLASS - 2
REISSUE:35422443R-FAILURETO MAINTAIN BUILDING IN CODE-COMPLIANT MANNERILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1;27-381 NOTED 4TH FLOOR GYM,STAIRS,1ST FLOOR STAIR A,B.EMERGENCY LIGH
#35643274Y
Oct 12, 2022
POP/IN-VIO
$0
May 7, 2021Construction CLASS - 2
REISSUE#35328848Y WORK WITHOUT A PERMIT EXP 3 7TH STREET SIDE OF YARD CURB CUT MADE APPROX 25'IN LENGTH SO CARS CAN ENTER YARD AREA.REM:OBTAIN ALL PERMITS.
#35554002X
Nov 24, 2021
POP/IN-VIO
$0
May 7, 2021Construction CLASS - 2
REISSUE#35498235N FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS. 4TH FL GYM &STAIRCASE A&B EMG LIGHTS NOT WORKING. REMEDY: REPAIR/REPLACE LIGHTING.
#35554001Y
Oct 20, 2021
POP/IN-VIO
$0
May 10, 2019Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOREXITS, EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1; 27-381 NOTED:24TH FL GYM, STAIR A 1ST FL STAIR A,B EMERGENCY LIGHTS AND EXIT SIGNS
#35422443R
Sep 23, 2019
POP/IN-VIO
$0
Nov 20, 2018Construction CLASS - 2
FAILURE TO COMPLY W/ COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35272641R ISSUED ON 12/14/17, AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1RCNY 102-01(D)(2). AN ACCEPTABLE CERTIFIC
#37012446N
Mar 25, 2019
IN VIOLATION
$0
Apr 10, 2018Construction CLASS - 2
REISSUE #35272641R WORK W/O PERMIT. NOTE AT EXPOSURE 3 REAR OF BUILDING ON 7TH ST SIDE CURB CUT APPRX 25' IN LENGTH OBSERVED NO PERMIT ON FILE. RMDY: OBTAIN ALL REQUIRED PERMITS.
#35328848Y
Jul 2, 2018
POP/IN-VIO
$0
Dec 14, 2017Construction CLASS - 3
WORK W/OUT A PERMIT OBSERVED:@4 STORY BLDG EXP#2 ALONG 7TH STREET REAR LEFT CORNER OF ROMAN CATHOLIC SCHOOL YAR CONST CRUB CUT APPROX 25' IN LENGTH.REM:OBTAIN PERMIT OR RESTORE PREMISES TO PRIOR LEGAL CONDITION
#35272641R
Mar 12, 2018
STIPULATION/IN-VIO
$0
DOB (1)
IssuedViolationStatus
Jun 24, 2009CONSTRUCTION

#AH01JG
VIOLATION WORK WITHOUT PERMIT - ACTIVE
DOB NOW Safety (3)
IssuedViolationStatus
Oct 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle C (premises is in Community District 6)
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2018 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 26, 2026, 6:43 AM ET. BBL 3009980001.