Staten Island · Block 5605 · Lot 1 · 10312

380 Genesee Avenue

2 floors · 68,800 sq ft · built 1926 · class W1 · owner of record: Nyc Department Of Education

38open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
168dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 47 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 68,800 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 168 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 168 days
Annual filing
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 778 days
Next cycle year 2028
Energy audit and retro-commissioning (2035) Likely applies
Local Law 87 · Calendar year 2035
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 5605). Agency page

Dec 31, 2035
in 3334 days
Next due 2035
Annual boiler inspection (4 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-09-29 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (28)
IssuedViolationHearingBalance
Apr 1, 2026Construction CLASS - 2
REISSUE#35692454M FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:THERE ARE SEVERAL EXTERIOR EXIT DOORS THAT ARE ROTTED,RUSTED, AND SEVERLY DETERIORATED,LARGE HOLES AT DOOR BOTTOMS ALLOW RODENTS,WAT
#35727191R
May 28, 2026
POP/IN-VIO
$0
Mar 31, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE WERE SEVERAL ROOMS SCATTERED THROUGH OUT THE SCHOOL THAT HAVE COMBUSTIBLE MATERIALS HANGING, CREATING A FIRE HAZARD. OBSERVED ELECTRICAL STRIN
#35727190P
Jun 5, 2026
POP/IN-VIO
$0
Mar 31, 2026Construction CLASS - 2
RE-ISSUE #35692451R. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE IS WATER PENETRATION WITH EVERY RAIN AT STAIRWAY #AAT EACH LEVEL. THE CHANGE IS SERIOUS AT THE WINDOWS AT ALL LEVELS. REM
#35727188X
Jun 5, 2026
POP/IN-VIO
$0
Mar 31, 2026Construction CLASS - 2
RE-ISSUE #35692452Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE IS DAMAGE TO THE WALLS AND CEILINGS OF BULKHEADS FROM THE WATER LEAKING THROUGH ROOF ABOVE. REMEDY: REPAIR/REPLACE.
#35727187Y
Jun 5, 2026
POP/IN-VIO
$0
Mar 31, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE ARE SEVERAL WINDOWS SCATTERED THROUGH OUT THE SCHOOL THAT ARE BROKEN OR DAMAGED AND DO NOT OPERATER CORRECTLY. SOME SCREWED AND INOPERABLE. RE
#35727189H
Jun 5, 2026
POP/IN-VIO
$0
Mar 27, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE ARE SEVERAL EXIT DOORS THROUGHOUT THE ECHOOL THAT NEED TO BE REPLACED. THEY ARE SERIOUSLY RUSTED, ROTTED AND DETERIORATING AT DOOR BOTTOMS AND
#35692454M
May 6, 2025
POP/IN-VIO
$0
Mar 27, 2025Construction CLASS - 2
RE-ISSUE #35672294Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THE WINDOWS AT STAIRWAY #A AT ALL LEVELS ALLOW WATER PENETRATION WHEN/EVER IT RAINS. ONGOING FOR YEARS, DAMAGE CONTINUES. REMED
#35692451R
May 6, 2025
POP/IN-VIO
$0
Mar 27, 2025Construction CLASS - 2
RE-ISSUE #35672293M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: WALLS AND CEILINGS AT BULKHEAD LOCATIONS SHOW SIGNS OF WATER DAMAGE FROM THE ROOF LEAKS ABOVE THESE AREAS. REMEDY: REPAIR/REPLA
#35692452Z
May 6, 2025
POP/IN-VIO
$0
Mar 14, 2024Construction CLASS - 2
REISSUE#35665335X FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THE WINDOWS AT STAIRWAY#A AT ALL LEVELS ALLOW WATER PENETRATION WHEN LIT RAINS.REM:REPAIR/REPLACE-FIX LEAKS AT WINDOWS.
#35672294Y
May 3, 2024
POP/IN-VIO
$0
Mar 14, 2024Construction CLASS - 2
REISSUE#35665336H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.WATER PENETRATION THRU ROOF AT BULKHEAD LOCATIONS.WALLS AND CEILINGSAT BULKHEADS SHOW OBVIOUS SIGNS OF THE LEAKS.REM:REPAIR/REPLACE ROOFIN
#35672293M
May 3, 2024
POP/IN-VIO
$0
Jan 30, 2023Construction CLASS - 2
REISSUE #35636504P FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:WINDOWS ON ALL LEVEL AT STAIRWAY A ALLOW RAINWATER TO PENETRATE INTO BUILDING.WINDOWS HAVE BEEN LEAKING FOR YEARS & NEED TO BE FIXE
#35665335X
May 17, 2023
POP/IN-VIO
$0
Jan 30, 2023Construction CLASS - 2
REISSUE #35636506Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:ONGOING PROBLEM OF LEAKS IN ROOF CONTINUES.BULKHEADS SHOW OBVIOUS PROOF OF LEAKS BY WATER.REMEDY:REPAIR/REPLACE/FIX LEAKS IN ROOF
#35665336H
May 17, 2023
POP/IN-VIO
$0
Feb 7, 2022Construction CLASS - 2
REISSUE#35555848Y.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED AT TOI THE WINDOWS AT STAIRCASE A LEAK WHEN IT'S RAINING FROM UPPER FLOORS TO GROUND FLOOR.REMEDY:REPAIR/REPLACE FIX LEAKS.
#35636504P
May 4, 2022
POP/IN-VIO
$0
Feb 7, 2022Construction CLASS - 2
REISSUE#35555843P.FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.OBSERVED AT TOI THE ROOF LEAKS AT SEVERAL LOCATIONS.THIS PROBLEM IS MOST EVIDENT AT ALL 3 BULKHEAD LOCATIONS CAUSING DAMAGE AT BULKHEADS
#35636506Z
May 4, 2022
POP/IN-VIO
$0
Apr 19, 2021Construction CLASS - 2
REISSUE35502146K FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTE@ROOF LEVEL BULKHEAD C&A WATER PENETRATION@BOTTOM OF BULKHEAD CAUSING DAMAGE TO INTERIOR WALLS.REPAIR &/OR REPLACE.
#35555843P
Jul 7, 2021
POP/IN-VIO
$0
Apr 19, 2021Construction CLASS - 2
FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES NOTE@STAIRCASER WINDOWS LEAK WHEN RAINING FROM TOP FL TO GROUND FL.MAINTAIN BLDG EXTERIOR WALLS.
#35555848Y
Jul 7, 2021
POP/IN-VIO
$0
Apr 19, 2021Construction CLASS - 2
REISSUE35502143P FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTE@BULKHEAD B&C WATER DAMAGE TO WALLS&STAIRS.REPAIR&/OR REPLACE.
#35555845Z
Jul 7, 2021
POP/IN-VIO
$0
Jul 6, 2020Construction CLASS - 2
REISSUE ECB #35459549Y FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER AT BULKHEAD AND STAIRCASE #B&C WATER FAMAGE AND STRING IN NEED OF REPAIR ,PROBLEM CONTINUED AND GETS WORSE WITH EACH HEAVY RAIN REPAI
#35502143P
Oct 7, 2020
POP/IN-VIO
$0
Jul 6, 2020Construction CLASS - 2
REISSUE 35452238P FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANENR NOTE ROOF LEVEL WATER PENETRTAION AT BULKHED (C) AT BOTTOM OF BULKHEAD ON EAST AND SOUTH SIDE ALSO ROOF MATERIALS IN POOR SHAPE WITH VARIO
#35502146K
Oct 7, 2020
POP/IN-VIO
$0
Mar 5, 2020Construction CLASS - 2
WORK AFTER HOURS W/O A VARIANCE PERMIT CONTRARY TO 28-105.12.5. NOTE:AT THE TIME OF INSPECTION IT WAS OBSERVED TEMPORARY ELECTRIC WORK BEINGPERFORMED ON THE OUTSIDE OF THE ABOVE ADDRESS. VARIANCE PERMIT#5008765
#35454191X
May 6, 2020
ADMIT/IN-VIO
$0
Dec 6, 2019Construction CLASS - 2
FAILURE TO MAINTAIN. NOTED:AT TIME OF INSPECTION,AT BULKHEAD AND STAIRCASE#B&#C WATER DAMAGE AND STAINING IN NEED OF REPAIR. PROBLEM CONTINUED AND GETS WORSE W/ EACH HEAVY RAIN. REMEDY:REPAIR/REPLACE. FIX THE L
#35459549Y
Mar 18, 2020
POP/IN-VIO
$0
Oct 23, 2019Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT BULKHEAD C & STAIRCASE B&C WATER PENETRATION TAKES PLACE WHEN HEAVY RAINS ARE ACTIVE.SIGNS OF WATER ARE OBVIOUS EVEN WHEN DRY.REMEDY:REPAIR/REPLACE
#35452466R
Dec 18, 2019
POP/IN-VIO
$0
Sep 3, 2019Construction CLASS - 1
REISSUED #35386193L FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTE AT ROOF LEVEL BULKHEAD C WATER PENETRATION INSTAIRASE B& C ALSO BULKHEAD B WATER PENETRATION AT WINDOW ON 3RD FLOOR REPAIR AND OR R
#35452237N
Nov 20, 2019
POP/IN-VIO
$0
Sep 3, 2019Construction CLASS - 2
FAILURE T MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTE AT ROOF LEVEL WATER PENETRATION AT BULKHEAD C AT BOTTON OF BULKHEAD ON EAST AND SOUTH SIDE ALSO ROOF MATERIAL IN POOR SHAPE WITH VARIOUS AREAS ROTTON AN
#35452238P
Nov 20, 2019
POP/IN-VIO
$0
Jul 12, 2018Construction CLASS - 2
REISSUE #35271118H FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.WATER PENETRATION AT VARIOUS LOCATIONS AT STAIRCASE B & C FROM BULKHEAD TO GAS METER ROOM. DAMAGE TO WINDOW LINTEL AT 3RD FLOOR BELOW BULKHE
#35329393L
Oct 3, 2018
POP/IN-VIO
$0
Jun 21, 2017Construction CLASS - 2
REISSUE#35216964P FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNERS. NOTED: STAIRCASE'A'LANDING'S BETWEEN 2ND & 3RD FL THE WINDOW LINTEL IS CORRODED & RUSTED SIGNS OF WATER PENETRATION AT STAIRCASE'B'&'C'
#35271118H
Sep 20, 2017
POP/IN-VIO
$0
Oct 28, 2016Construction CLASS - 2
REISSUE #35093569H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT STAIRCASE (A) AT LANDINGS 1ND, 3RD FLOOR WINDOWS, TOP WINDOW SILLS SPALLING AND DAMAGE FROM INSIDE. ALSO, AT BULKHEAD STAIRC
#35216964P
Jan 4, 2017
POP/IN-VIO
$0
Mar 31, 2014Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: INTERIOR. AT STAIRWAY A AT LANDINGS 2ND & 3RD FLOOR WINDOWS, TOP WINDOW SILLS SPALLING & DAMAGED FROM INSIDE. REMEDY: REPAIR TOP WINDOW SILLS INTEIROR.
#35093569H
Jun 4, 2014
POP/IN-VIO
$0
DOB (4)
IssuedViolationStatus
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#20500
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#25946
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#05118
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#05119
DOB VIOLATION - ACTIVE
DOB NOW Safety (6)
IssuedViolationStatus
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 14, 2026, 3:29 PM ET. BBL 5056050001.