Bronx · Block 2557 · Lot 1 · 10454

376 St Anns Avenue

2 floors · 39,450 sq ft · built 1931 · class Q1 · owner of record: Nyc Department Of Parks And Recreation

18open violations
$12,500ECB/OATH penalties owed
0HPD class C (immediately hazardous)
47dto Annual boiler inspection (2 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 47 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2025-12-17 (Accepted). Agency page

Dec 31, 2026
in 47 days
2 of 2 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 39,450 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 168 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 168 days
Annual filing
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 1 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 778 days
Next cycle year 2028

Open violations

ECB / OATH (7) · $12,500 owed
IssuedViolationHearingBalance
Jul 10, 2025Construction CLASS - 1
3 STORY ST. MARY'S RECREATION CENTER PARKS DEPARTMENT BUILDING OBSERVED SUPPORT OF EXCAVATION WORK AT EXP#3. EXCAVATED AREA MORE THAN 10 FEET IN DEPTH PILES LAGGING & SHORING. UPON RESEARCH ON BIS/DOB NOW & CRM
#39542311R
Sep 19, 2025
ADMIT/IN-VIO
$0
Jul 10, 2025Construction CLASS - 2
3 STORY ST. MARY'S RECREATION CENTER PARKS DEPARTMENT BUILDING OBSERVED SUPPORT OF EXCAVATION WORK AT EXP#3. CONSTRUCTION SUPER ONSITE SITE SAFETY JOBSITE PERMIT#X01206566. UPON REQUEST FOR SITE SAFETY PLANS ON
#39542312Z
Sep 19, 2025
ADMIT/IN-VIO
$0
Sep 16, 2022Unknown CLASS - 2
FAILURE TO PROVIDE SUPER LOGS FAILURE TO DESIGNATE COMPETENT PERSON
#39506423N
Nov 4, 2022
ADMIT/IN-VIO
$0
Oct 9, 2021Construction CLASS - 1
AN UNLAWFUL ACT-FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS NUMBERS#35360017N,35360018P,AND 35547840J.REMEDY:COMPLY WITH EC CODE.
#35584094J
Jan 7, 2022
DEFAULT
$12,500
May 5, 2021Construction CLASS - 1
UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. RECORD INDICATE NO APPLICATION WAS MADE TO CERTIFY AND CORRECT ECB #'S 35360018P & 35360017N. REMEDY: COMPLY WITH COMMISSIONERS ORDERS
#35547840J
Jul 30, 2021
POP/IN-VIO
$0
Nov 22, 2019Unknown CLASS - 1
UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,OR WIRING IN USE.BASEMENT ELECTRICAL ROOM:DEFECTIVE ENTRANCE CONDUCTOR,WINDOW SERVICE,ENTRANCE THROUGH Q/M TEMPORARY WIRING AND NOT
#35360017N
Feb 21, 2020
POP/IN-VIO
$0
Nov 22, 2019Unknown CLASS - 1
FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS.BASEMENT ELECTRICAL ROOM.1200 AVE SERVICE ENTRANCE CONDUCTORS ARE NOT BINDEE, AND GROUNDED."PLEASE NOTE"THIS IS NOT A FINAL INSPECTION!!REMEDY:PROVIDE PROPER BONDING.
#35360018P
Feb 21, 2020
POP/IN-VIO
$0
DOB (6)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#07854
DOB VIOLATION - ACTIVE
Sep 23, 2024LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
#07035
DOB VIOLATION - ACTIVE
Jun 30, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
#34615
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
#14415
DOB VIOLATION - ACTIVE
Apr 25, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
#09260
DOB VIOLATION - ACTIVE
Oct 29, 2019CONSTRUCTION

#CN0101AJ
DOB VIOLATION - ACTIVE
DOB NOW Safety (5)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Sep 23, 2024Boiler LBLVIO
Violation Issued-Failure To File 2023 External Low Pressure Inspection Report
Active
Jun 30, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
Active
Apr 25, 2023Boiler LBLVIO
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2022 INSPECTION REPORT
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 14, 2026, 12:16 AM ET. BBL 2025570001.