3 floors · 181,092 sq ft · built 1962 · class W1 · owner of record: Nyc Department Of Education
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 46 days | Keep the report on file (not filed with DOB) |
| Energy audit and retro-commissioning (2026) Likely applies Local Law 87 · Calendar year 2026 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 4916). Agency page | Dec 31, 2026 in 46 days | Due this year |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 181,092 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 167 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 167 days | Annual filing |
| Gas piping inspection (2027 cycle) Likely applies Local Law 152 · During 2027 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2027 in 411 days | Next cycle year 2027 |
| Annual boiler inspection (2 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-13 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Apr 8, 2026 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:CRACKED WIRE MESH GLASS VISION PANELS ON CLASSROOM 3C AND SMOKE DOOR WEST ENTRANCE/LEFT DOOR OBSERVED UPON INSPECTION.REM:REPAIR AND/OR REPLACE. #35732276M | Jul 10, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 REISSUE ON ECB #35717498M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: PERIMETER STONE KNEE WALL AROUND THE WHOLE SCHOOL WITH MISSING, LOOSE AND CRACKED STONE IN VARIOUS LOCATIONS OBSERVED UPO #35732252H | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 REISSUE ON ECB #35717497K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: SPALLING CONCRETE ON UNDERSIDE OF EMERGENCY EXTERIOR EXIT DOORWAY OVERHANG ON EXITS 5, EXIT 4 AND EXIT 2, OBSERVED UPON I #35732253J | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 REISSUE ON ECB #35717495R. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: EMERGENCY ILLUMINATED DISCHARGE EXITS #35732254L | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 REISSUE ON ECB #35717494P. EXIT DOOR NOT SELF-CLOSING. NOTED: EMERGENCY EXTERIOR EXIT DOORS NOT SELF-CLOSING DUE TO BINDING, MISSING OR FAULTY HARDWARE ON EXTERIOR DOOR EXIT 2 (3)DOORS 1ST FLOOR, EXIT 6 (2)DOOR #35732255N | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:FLAG POLE NOT FUNCTIONING DUE TO MISSING PULLEY AND HAS NOT WORKED FOR AWHILE,OBSERVED UPON INSPECTION.REM:REPAIR AND/OR REPLACE. #35732261J | Jul 10, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:FIRE RATEDCLASSROOMS AND SMOKE DOORS NOT SELF-CLOSING DUE TO BINDING,MISSING ANDOR FAULTY HARDWARE ON CLASSROOMS 4C,2C,4D,5B,3C,3D,3A,3B,INCLUDING SMO #35732275K | Jul 10, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:STAIRS LEADING TO EMERGENCY EXTERIOR EXIT 6 HAS SPALLING CRACKED AND LOOSE TERRAZZO TREAD STEP OBSERVED UPON INSPECTION.REM:REPAIR AND/OR REPLACE. #35732260H | Jul 10, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:WALKWAY CONCRETE PAVED PAD STAIRWAY AT EXP#4 HAS MISSING CONCRETE,SPALLING AND CRACKED AROUND PERIMETER OF SEWER ACROSS CAUSING,ANKLE TWISTING AND OR #35732259K | Jul 10, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:STEP AT EXP#2 ON FACADE BY EXIT 6 AND AT EXP#1 DECORATIVE CERAMIC TILE MISSING,INCLUDING MISSING MORTAR BETWEEN BRICK AT INTERMEDIATE ROOF AT BULKHEAD #35732262L | Jul 10, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 REISSUE#35719800N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EMERGENCY ILLUMINATED EXIT DISCHARGE BOXES NOT WORK #35732277Y | Jul 10, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 REISSUE ON ECB #35717499Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: SPALLING PLASTER ON FOUNDATION WALL AT CELLAR LEVELSTAIRWELL D DUE TO WATER DAMAGE FROM WATER SEEPAGE THROUGH POROUS WALL #35732251X | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 REISSUE ON ECB 35717492L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). NOTED: INSTALLATION OF ILLEGAL KICK STOPS ON FIRE RATED AND SM #35732257R | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 REISSUE ON ECB #35717493N. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: MISSIN AND/OR REMOVED FIRE RATED SMOKE DOORS ON 3RDFLOOR CORRIDOR BY 326 CLASSROOM AND 2ND FLOOR CORRIDOR BY CLASSROOM 20 #35732256P | Jun 12, 2026 POP/IN-VIO | $0 |
| Apr 8, 2026 | Construction CLASS - 2 REISSUE ON ECB #35719946X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FIRE RATED CLASSROOM AND SMOKE DOORS NOT SELF-CLOSING DUE TO BINDING MISSING OR FAULTY HARDWARE ON SMOKE DOORS AT MAIN EN #35732258Z | Jun 12, 2026 POP/IN-VIO | $0 |
| Jun 26, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED MISSING/REMOVED CROSS CORRIDOR SMOKE DOORS AT 3RD FL BY RM #326, 2ND FL BY RM #208 AND RM #226. CAFETERIA ENTRY DOORS MISSING DOOR MULLION CREATING " #35717493N | Sep 5, 2025 POP/IN-VIO | $0 |
| Jun 26, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS; EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED APPROX 95% OF EMERGENCY LIGHTS NOT WORKING THROUGHOUT THE SCHOOL #35717495R | Sep 5, 2025 POP/IN-VIO | $0 |
| Jun 26, 2025 | Construction CLASS - 2 EXIT DOOR NOT SELF-CLOSING. EXTERIOR DOORS AT EXIT #2 AND 6 WERE NOT SELF-CLOSING PROPERLY DUE TO DEFECTIVE CLOSER DEVICES OR BEING RACHED. REMEDY: REPAIR/REPLACE DOOR. #35717494P | Sep 5, 2025 POP/IN-VIO | $0 |
| Jun 26, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. FACADE IN DISREPAIR. CRUMBLING/SPALLING CEMENT AT EXITS #5, 4 AND 2 OVERHANG ABOVE DOOR UNDERSIDE. AT EXP #2 BY EXIT #6 LARGE STEP CRACK IN MASONRY WALL CO #35717497K | Sep 5, 2025 POP/IN-VIO | $0 |
| Jun 26, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED SPALLING PLASTER ON WALL AT CELLAR LEVEL STAIRWELL D DUE TO WATER INFILTRATION FROM EXTERIOR. REMEDY: REPAIR AND/OR REPLACE. #35717499Y | Sep 5, 2025 POP/IN-VIO | $0 |
| Jun 26, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED EXTERIOR STONE KNEE WALL AROUND SCHOOL'S PERIMETER HAS SEVERAL AREAS WITH CRACKS AND MISSING OF LOOSE STONE PIECES THROUGHOUT ALL EXPOSURES. REMEDY: #35717498M | Sep 5, 2025 POP/IN-VIO | $0 |
| Jun 26, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1; 27-371(J). NOTED ILLEGAL KICKDOWN DOOR STOPS MOUNTED ON FPSC DOORS IN CLASSROOM #330, 329, 328, 313, #35717492L | Sep 5, 2025 POP/IN-VIO | $0 |
| Jun 26, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXIT, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED APPROX. 9 EMERGENCY LIGHTS NOT WORKING WHEN TESTED THROUGHOUT TRAN #35719800N | Sep 5, 2025 POP/IN-VIO | $0 |
| Jun 16, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED @ EXIT3 MAIN ENTRANCE FROM BAYCHESTER AVE VESTIBULE, 3 OUT OF 4 DOOR NOT CLOSED PROPERLY WHEN TESTED DOOR TO DOOR CHECK DEFECTIVE. REMEDY: REPAIR #35719946X | Jul 18, 2025 POP/IN-VIO | $0 |
| Jul 15, 2010 | Construction CLASS - 2 EXTERIOR FOUNDATION WALL HAS BECOME POROUS & ALLOWING RAIN INTO THE BLDG CAUSING INTERIOR DAMAGES IN THE BOILER ROOM @ CELLAR LEVEL ADJACENTTO BAYCHESTER.REM:WATER-PROOF EXTERIOR FOUNDATION WALL #34863560N | Sep 17, 2010 WRITTEN OFF | $0 |
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2025 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION #07356 | DOB VIOLATION - ACTIVE |
| Nov 14, 2025 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION #07357 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Oct 29, 2026 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction | Active |
| Nov 14, 2025 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Nov 14, 2025 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Oct 10, 2025 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction | Active |
| Jan 31, 2025 | Gas Piping - LL152 FTF-PL-PER Cycle 1, Sub-cycle D (premises is in Community District 12) | Active |
| Oct 11, 2024 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction | Active |
| Oct 23, 2023 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction | Active |
| Aug 25, 2023 | Elevators FTF-VT-PER-CO Violation Issued-Failure To File 2022 Periodic Inspection Report | Active |
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Oct 29, 2026 | DOB Safety | Elevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Nov 15, 2026, 9:25 PM ET. BBL 2049160001.