6 floors · 315,000 sq ft · built 1928 · class W1 · owner of record: Nyc Department Of Education
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 47 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 315,000 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 168 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 168 days | Annual filing |
| Gas piping inspection (2028 cycle) Likely applies Local Law 152 · During 2028 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2028 in 778 days | Next cycle year 2028 |
| Energy audit and retro-commissioning (2028) Likely applies Local Law 87 · Calendar year 2028 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 408). Agency page | Dec 31, 2028 in 778 days | Next due 2028 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Aug 5, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THROUGHOUTTHE SCHOOL AT THE STAIRWAYS,THE GLASS PARTITION PANELS ARE MISSING,BROKEN OR CRACKED.DANGEROUS CONDITION WITH STUDENT TRAFFIC OVER 100 PANEL #35734582J | Aug 20, 2026 POP/IN-VIO | $0 |
| Aug 5, 2026 | Construction CLASS - 2 REISSUE#35693260Z FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER115.6(1968 CODE)FGC APPENDIX E(E4)(2014 CODE)NO VENTILATION PRESENT ATT.O.I.REM:COMPLY WITH NOTICE OF VIOLATION/PROVIDE VENTILATION. #35734581H | Aug 20, 2026 POP/IN-VIO | $0 |
| Aug 5, 2026 | Construction CLASS - 2 REISSUE#35693262M EXIT DOOR NOT SELF-CLOSING.NOTED:AT VARIOUS LOCATIONS THROUGHOUT THE SCHOOL,THERE WERE EXIT DOORS,SMOKE DOORS THAT WERE NOT SELF CLOSING AS THEY SHOULD.REM:REPAIR/REPLACE DOORS. #35734579Z | Aug 20, 2026 POP/IN-VIO | $0 |
| Aug 5, 2026 | Construction CLASS - 2 REISSUE#35693261K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THERE ARE SEVERAL DOORS SCATTERED AROUND THE SCHOOLS INTERIOR THAT ARE NOT OPERATING CORRECTLY.REM:REPAIR/REPLACE. #35734580X | Aug 20, 2026 POP/IN-VIO | $0 |
| Aug 14, 2025 | Construction CLASS - 2 28-301.1. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER 115.6(1968 CODE), FGC APPENDIX E(E4)(2014 CODE). RE-ISSUE #35688657K. REMEDY:COMPLY WITH NOTICE OF VIOLATION. #35693260Z | Sep 10, 2025 POP/IN-VIO | $0 |
| Aug 14, 2025 | Construction CLASS - 2 RE-ISSUE #35688656Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE ARE SEVERAL DOORS NOT OPERATING PROPERLY. SCATTEREDON 2ND FLOOR, 3RD FLOOR AND 5TH FLOOR. REMEDY: REPAIR/REPLACE. #35693261K | Sep 10, 2025 POP/IN-VIO | $0 |
| Aug 14, 2025 | Construction CLASS - 2 RE-ISSUE #35688654P. EXIT DOOR NOT SELF-CLOSING. NOTED: AT T. O. I., THERE WERE EXIT DOORS AND SMOKE DOOR AT VARIOUS LOCATIONS THAT WERE NOTSELF-CLOSING AS THEY SHOULD. REMEDY: REPAIR/REPLACE DOORS. #35693262M | Sep 10, 2025 POP/IN-VIO | $0 |
| Sep 9, 2024 | Construction CLASS - 2 EXIT DOOR NOT SELF-CLOSING. AT 1 FLOOR EXIT 4, SMOKE DOORS 8 AND 3 ARENOT CLOSING PROPERLY. REMEDY: REPAIR/REPLACE DOOR. #35688654P | Oct 21, 2024 POP/IN-VIO | $0 |
| Sep 9, 2024 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT 5TH FLOOR ROOM 524, 3FL 304 AND 2FL. CORRIDOR BY 238A DOOR ARE NOT CLOSING PROERLY. REMEDY: REPAIR AND/OR REPLACE. #35688656Z | Oct 21, 2024 POP/IN-VIO | $0 |
| Sep 9, 2024 | Construction CLASS - 2 REISSUE #35674757K. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE), FGC APPENDIX E(EY)(2014) CODE. NOTED: THERE IS NO FRESH AIR FROM OUTSIDE VENTILATING GAS METER ROOM. REMEDY: COMPLY WI #35688657K | Oct 21, 2024 POP/IN-VIO | $0 |
| Apr 26, 2023 | Construction CLASS - 2 28-301.1 REISSUE#35657962P FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968CODE, FGC APPENDIX E (E4) 2014 CODE.) AT TIME OF INSPECTION I OBSERVED AT CELLAR LEVEL AT GAS METER ROOM NO NATURAL OR #35674757K | Aug 24, 2023 POP/IN-VIO | $0 |
| May 20, 2022 | Construction CLASS - 2 28-301.1 REISSUE35558081L DATE4.29.21 FAILURE TO PROVIDE VENTILATION TO GAS METER RM PER P115.6(1968CODE) FGC APPENDIXE(E4)(2014CODE).ATOI IOBSERVED NO FRESH AIR OR VENTILATION WAS PROVIDED@GAS METER RM.PROVIDE #35657962P | Sep 15, 2022 POP/IN-VIO | $0 |
| Apr 29, 2021 | Construction CLASS - 2 SEC. 28-301.1 REISSUE@35495767K FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P 115.6(1968 CODE),FGC APPENDIX E(E4)2014 CODE. NOTED: AT TIME OF MY INSPECTION,I OBSERVED NO FRESH AIR VENTILATION WAS PROVI #35558081L | Sep 2, 2021 POP/IN-VIO | $0 |
| May 28, 2020 | Construction CLASS - 2 SEC. 28-301.1 REISSUE#35415376K FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGG APPENDIX E(E4)2014 CODE. NOTED: AT TIME OF INSPECTION I OBSERVED NO FRESH AIR VENTILATION WAS PROVIDE #35495767K | Sep 10, 2020 POP/IN-VIO | $0 |
| May 10, 2019 | Construction CLASS - 2 28-301.1 RE-ISSUE #35322520N.FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE)FGC APPENDIX E(E4)(2014 CODE).NOTED:THEREIS NO FRESH AIR FROM THE OUTSIDE FOR GAS METER RM.REM:COMPLY WITH CODE #35415376K | Aug 8, 2019 POP/IN-VIO | $0 |
| Mar 13, 2018 | Construction CLASS - 2 28-301.1 REISSUE #35253058X. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115(1968) FGC APPENDIX(E) 2014. NO VENTILATION AT GAS METER ROOM AT CELLAR. REM: PROVIDE VENTILATION. #35322520N | Jul 5, 2018 POP/IN-VIO | $0 |
| Apr 24, 2017 | Construction CLASS - 2 27-766 REISSUE #35201091N NOTEED: AT CELLAR LEVEL, GAS METER ROOM, NO FRESH AIR INLET (FAI). RMDY: COMPLY WITH CODE/PROVIDE FRESH AIR INLET. #35253058X | Oct 19, 2017 POP/IN-VIO | $0 |
| Jul 29, 2016 | Construction CLASS - 2 27-766 MISC. VIOL. NOTED: NO FRESH AIR INLET (FA1) AT CELLAR GAS METER ROOM, NO F.A.1 RMDY: PROVIDE FA1. RMDY: COMPLY WITH CODE PROVIDE FRESH AIR VENT. #35201091N | Nov 17, 2016 POP/IN-VIO | $0 |
| Oct 5, 2015 | Construction CLASS - 2 27-766 REISSUE #35093836N NO FRESH AIR INLET INLET (FAI) @ CELLAR GAS METER ROOM, NO F.A.I. REMEDY: PROVIDE F.A.I. #35147666K | Jan 7, 2016 POP/IN-VIO | $0 |
| Apr 2, 2014 | Unknown CLASS - 2 27-766 NO FRESH AIR INLET (FAI) @ CELLAR GAS METER ROOM, NO F.A.I. REMEDY: PROVIDE F.A.I. #35093836N | Jun 5, 2014 POP/IN-VIO | $0 |
| Issued | Violation | Status |
|---|---|---|
| Jan 13, 1997 | LOCAL LAW 10/81 - ELEVATOR #00234 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Oct 2, 2026 | Elevators FTF-VT-PER-CO Violation Issued-Failure To File 2025 Periodic Inspection Report | Active |
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Oct 2, 2026 | DOB Safety | Elevators: Violation Issued-Failure To File 2025 Periodic Inspection Report | Open |
| Aug 5, 2026 | ECB | Construction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THROUGHOUTTHE SCHOOL AT THE STAIRWAYS,THE GLASS PARTITION PANELS ARE MISSING,BROKEN OR CRACKED.DANGEROUS CONDITION WITH STUDENT TRAFFIC OVER 100 PANEL | Open |
| Aug 5, 2026 | ECB | Construction: REISSUE#35693260Z FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER115.6(1968 CODE)FGC APPENDIX E(E4)(2014 CODE)NO VENTILATION PRESENT ATT.O.I.REM:COMPLY WITH NOTICE OF VIOLATION/PROVIDE VENTILATION. | Open |
| Aug 5, 2026 | ECB | Construction: REISSUE#35693262M EXIT DOOR NOT SELF-CLOSING.NOTED:AT VARIOUS LOCATIONS THROUGHOUT THE SCHOOL,THERE WERE EXIT DOORS,SMOKE DOORS THAT WERE NOT SELF CLOSING AS THEY SHOULD.REM:REPAIR/REPLACE DOORS. | Open |
| Aug 5, 2026 | ECB | Construction: REISSUE#35693261K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THERE ARE SEVERAL DOORS SCATTERED AROUND THE SCHOOLS INTERIOR THAT ARE NOT OPERATING CORRECTLY.REM:REPAIR/REPLACE. | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Nov 14, 2026, 2:39 PM ET. BBL 1004080030.