Queens · Block 377 · Lot 13 · 11101

35-02 37 Avenue

5 floors · 80,200 sq ft · built 1915 · class H9 · owner of record: 37-06 36th Street Holdings Llc

28open violations
$13,275ECB/OATH penalties owed
0HPD class C (immediately hazardous)
182dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 61 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 80,200 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 182 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 182 days
Annual filing
Energy audit and retro-commissioning (2027) Likely applies
Local Law 87 · Calendar year 2027
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 377). Agency page

Dec 31, 2027
in 426 days
Next due 2027
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 1 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 792 days
Next cycle year 2028

Open violations

ECB / OATH (16) · $13,275 owed
IssuedViolationHearingBalance
Sep 30, 2026Elevators CLASS - 2
CLASS 2 RTS: 1. DEVICE FOUND IN A NON COMPLIANT CONDITION REQUIRING RETURN TO SERVICE. AS PER 1 RCNY 11 02 AND BC 3001.2. REMEDY: RESTORE DEVICE TO FULL CODE COMPLIANT OPERATION AND VERIFY ALL SAFETY FUNCTIONS.
#39206216X
Dec 8, 2026
PENDING
$625
Sep 29, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI I OBSERVED AT THE 5TH FLOOR LEVER IN ROOM 507 WATER LEAKING FROM THE CEILING AND AROUND THE WINDOW IN VARIOUS AREA, CAUSE FROM THE ROOF LEAKING AND IN
#39205964R
Dec 8, 2026
PENDING
$1,250
Aug 11, 2026Construction CLASS - 1
AT MECHANICAL ROOMS FLOORS 2 THROUGH 5 HOLE PENETRATIONS PRESENT, CAUSE A SEVERE FIRE HAZARD, REPAIR AND/REPLACE
#39200064Z
Oct 20, 2026
DEFAULT
$6,280
Aug 11, 2026Construction CLASS - 2
FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39179691Y, FILE A CERTIFICATE OF CORRECTION
#39200063R
Oct 20, 2026
DEFAULT
$1,280
Aug 11, 2026Construction CLASS - 2
FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39179639R, FILE A CERTIFICATE OF CORRECTION
#39200065K
Oct 20, 2026
DEFAULT
$1,280
Aug 11, 2026Construction CLASS - 2
FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39179637N, FILE A CERTIFICATE OF CORRECTION
#39200061N
Oct 20, 2026
DEFAULT
$1,280
Aug 11, 2026Construction CLASS - 2
FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39179690M, FILE A CERTIFICATE OF CORRECTION
#39200062P
Oct 20, 2026
DEFAULT
$1,280
Mar 9, 2026Construction CLASS - 1
OBSERVED GROUND FLOOR SPRINKLER HEAD OBSTRUCTED. IN BASEMENT SPRINKLER HEADS MISSING CAPS, SPRINKLER SYSTEM TO CAFE IS NOT OPERATIONAL, DOORS STRIKING SPRINKLER SYSTEM VALVES , USING LAMP WICK ON GAS LINES BY G
#39179691Y
May 19, 2026
DEFAULT
$0
Mar 9, 2026Elevators CLASS - 1
CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION
#39179601L
May 19, 2026
DEFAULT
$0
Mar 9, 2026Construction CLASS - 1
OBSERVED IN THE BASEMENT WASTE AND GAS LINES PRESENT IN THE DEDICATED ELECTRICAL ROOM. WATER LEAKED FROM CELLING ONTO THE FLOOR. EJECTOR PUMP NOT PROPERLY VENTED. ON SECOND FLOOR PVC PIPING ON WASTE LINE UNDER
#39179690M
May 19, 2026
DEFAULT
$0
Mar 9, 2026Unknown CLASS - 1
FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED IN MAIN ELECTRICAL ROOM IN BASEMENT NO ELECTRODE GROUND ROD NOT INSTALLED. THIS IS A SECOND MEANS OF GROUNDING. EC 250.64 PO
#39179637N
May 19, 2026
DEFAULT
$0
Mar 9, 2026Construction CLASS - 1
OBSERVED IN HOT WATER HEATER ROOMS ON FLOORS 2 THROUGH 5 IMPROPER HOT WATER HEATERS EXHAUST PIPING. ON 5 FLOOR NO TEMPERATURE RELIEF VALVE DRAIN INSTALLED. SPRINKLER SYSTEM TO MECHANICAL ROOMS AND BOILER ROOMS
#39179689P
May 19, 2026
DEFAULT
$0
Mar 9, 2026Unknown CLASS - 1
MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED IN MAIN ELECTRICAL ROOM THERE WAS WATER POOLING IN FRONT OF ELECTRICAL DISTRIBUTION. THIS POTENTIAL FOR HAZARD OF ELECTRICAL SHOCK /
#39179638P
May 19, 2026
DEFAULT
$0
Mar 9, 2026Elevators CLASS - 2
CLASS 2: EMERGENCY PHONE INOPERATIVE, PROVIDE 24-HOUR 2-WAY COMMUNICATION SERVICE. IN-CAR POSITION INDICATOR INOPERATIVE, REPAIR.
#39179602N
May 19, 2026
DEFAULT
$0
Mar 9, 2026Unknown CLASS - 1
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN STAIRWAY ELECTRIC HEAT BLOWERS ON 4TH,2ND, CELLAR HAS NO DISCONNECT SWITCH FOR SERVICE
#39179639R
May 19, 2026
DEFAULT
$0
Mar 9, 2026Elevators CLASS - 1
CLASS 1: FIREFIGHTER SERVICE PHASE I INOPERATIVE - NO ELEVATOR RECALL, KEY CYLINDER ROTATES 360, REPAIR AND REQUEST RE-INSPECTION FROM DOB ELEVATOR DIVISION. CLASS 2: EMERGENCY PHONE INOPERATIVE, PROVIDE 24-HOU
#39179600J
May 19, 2026
DEFAULT
$0
DOB (1)
IssuedViolationStatus
Mar 21, 1991ELEVATOR
DEVICE #4P2644
#1214D03
VIOLATION UNSERVED ECB-WORK WITHOUT PERMIT-ACTIVE
DOB NOW Safety (10)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction
Active
Sep 16, 2026AEUHAZ FTC-AEU-HAZ
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
Jul 30, 2026AEUHAZ FTC-AEU-HAZ
Active
HPD (1) · C 0 · B 0 · A 1
IssuedClassViolationCorrect by
May 6, 2026A(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.Aug 9, 2026

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of CorrectionOpen
Sep 30, 2026ECBElevators: CLASS 2 RTS: 1. DEVICE FOUND IN A NON COMPLIANT CONDITION REQUIRING RETURN TO SERVICE. AS PER 1 RCNY 11 02 AND BC 3001.2. REMEDY: RESTORE DEVICE TO FULL CODE COMPLIANT OPERATION AND VERIFY ALL SAFETY FUNCTIONS.Open
Sep 29, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI I OBSERVED AT THE 5TH FLOOR LEVER IN ROOM 507 WATER LEAKING FROM THE CEILING AND AROUND THE WINDOW IN VARIOUS AREA, CAUSE FROM THE ROOF LEAKING AND INOpen
Sep 16, 2026DOB SafetyAEUHAZ: Open
Aug 11, 2026ECBConstruction: AT MECHANICAL ROOMS FLOORS 2 THROUGH 5 HOLE PENETRATIONS PRESENT, CAUSE A SEVERE FIRE HAZARD, REPAIR AND/REPLACEOpen
Aug 11, 2026ECBConstruction: FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39179691Y, FILE A CERTIFICATE OF CORRECTIONOpen
Aug 11, 2026ECBConstruction: FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39179639R, FILE A CERTIFICATE OF CORRECTIONOpen
Aug 11, 2026ECBConstruction: FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39179637N, FILE A CERTIFICATE OF CORRECTIONOpen
Aug 11, 2026ECBConstruction: FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39179690M, FILE A CERTIFICATE OF CORRECTIONOpen
Jul 30, 2026DOB SafetyAEUHAZ: Open
Jul 30, 2026DOB SafetyAEUHAZ: Open
Jul 30, 2026DOB SafetyAEUHAZ: Open
Jul 30, 2026DOB SafetyAEUHAZ: Open
Jul 30, 2026DOB SafetyAEUHAZ: Open
Jul 30, 2026DOB SafetyAEUHAZ: Open
Jul 30, 2026DOB SafetyAEUHAZ: Open
Jul 30, 2026DOB SafetyAEUHAZ: Open

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 31, 2026, 7:45 PM ET. BBL 4003770013.