6 floors · 426,224 sq ft · built 1915 · class W1 · owner of record: Nyc Department Of Education
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 63 days | Keep the report on file (not filed with DOB) |
| Annual boiler inspection (3 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2025-12-18 (Accepted). Agency page | Dec 31, 2026 in 63 days | 3 of 3 without an accepted 2026 report yet |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 426,224 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 184 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 184 days | Annual filing |
| Gas piping inspection (2029 cycle) Likely applies Local Law 152 · During 2029 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 7 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2029 in 1159 days | Next cycle year 2029 |
| Energy audit and retro-commissioning (2032) Likely applies Local Law 87 · Calendar year 2032 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 5002). Agency page | Dec 31, 2032 in 2255 days | Next due 2032 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Mar 13, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:CLASSROOM DOORS DO NOT SELF-CLOSE PROPERLY WHEN TESTED AT 3RD FLR-302,317,319,323,328,348,361.2ND FLR-264,261,258,241,239,237,244,236,228,225,219A,219 #35722184X | Mar 30, 2026 POP/IN-VIO | $0 |
| Mar 13, 2026 | Construction CLASS - 2 REISSUE#35725367M EXIT DOOR NOT SELF-CLOSING.NOTED:AT 3RD FLR-STAIRCASE I & J 2ND FLR-STAIRCASE N.AT 1ST FLR-LIBRARY,CAFETERIA ALL DOORS IN DISREPAIR/NOT CLOSING WHEN TESTED.REM:REPAIR/REPLACE DOORS. #35722183Y | Mar 30, 2026 POP/IN-VIO | $0 |
| Mar 13, 2026 | Construction CLASS - 2 REISSUE#35725370N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT 1ST FLR-EXIT 11 MISSING MESH GLASS PANEL.REM:REPAIR AND/OR REPLACE. #35722181K | Mar 30, 2026 POP/IN-VIO | $0 |
| Mar 13, 2026 | Construction CLASS - 2 REISSUE#35725371P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:AT 1ST FLR AUDITORIUM,CAFETERIA,LIBRARY EMERGENCY L #35722180Z | Mar 30, 2026 POP/IN-VIO | $0 |
| Mar 13, 2026 | Construction CLASS - 2 REISSUE#35725368Y FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCESNOTED:AT EXP.1 AND EXP.3 FACADES WITH CRACKS AND LOOSE/MISSING MORTAR.REM:MAINTAIN EXTERIOR BUILDING WALL. #35722182M | Aug 30, 2026 POP/IN-VIO | $0 |
| Sep 18, 2025 | Construction CLASS - 2 REISSUE ECB #35678995Y. EXIT DOOR NOT SELF-CLOSING NOTED: AT(3RD FL) STAIR C, I, H(2ND FL) STAIR N(1ST FL) STAIR D, Q, LIBRARY, MAIN ENTRANCE, CAFETERIA ALL DOOR IN DISREPAIR/NOT CLOSING WHEN TESTED. REMEDY: RE #35725367M | Oct 21, 2025 POP/IN-VIO | $0 |
| Sep 18, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: AT(1ST FL) AUDITORIUM, CAFETERIA, LIBRARY EMERGENCY LIGHTS NOT W #35725371P | Oct 21, 2025 POP/IN-VIO | $0 |
| Sep 18, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT(1ST FL) EXIT 11 MISSING MESH GLASS PANEL. REMEDY: REPAIR AND/OR REPLACE. #35725370N | Oct 21, 2025 POP/IN-VIO | $0 |
| Sep 18, 2025 | Construction CLASS - 2 REISSUE ECB #35678994M. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: AT EXP. 1 AND EXP. 3 FACADES WITH CRACKS AND LOOSE/MISSING MORTAR. REMEDY: MAINTAIN EXTERIOR BUILDING. #35725368Y | Oct 21, 2025 POP/IN-VIO | $0 |
| Mar 21, 2024 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES NOTED EXP#1(FRONT)HORIZONTAL CRACK WITH MISSING MORTAR JOINT ALONG WINDOW LINTEL NEXT TOEXIT#11 AT EXPO#3(REAR)VERTICAL CRACK IN BRICK FACADE APPROX.24" IN LE #35678994M | May 13, 2024 POP/IN-VIO | $0 |
| Mar 21, 2024 | Construction CLASS - 2 EXIT DOOR NOT SELF CLOSING EXTERIOR EXIT DOORS AT EXIT#15 GETS STUCK ON SADDLE(DIFFICULT TO OPEN)EXIT H & I DOORS HAVE RUSTED FRAMES, NOT OPENING/CLOSING PROPERLY.ADDITIONALLY DOORS AT 3RD FL STAIRWELL J,I & H #35678995Y | May 13, 2024 POP/IN-VIO | $0 |
| Apr 30, 2021 | Construction CLASS - 2 SIDEWALK SHED DOES NOT MEET CODE SPECIFICATIONS.NOTE:AT THE TIME OF MYINSPECTION,I OBSERVED SIDEWALK SHED POST ERECTED ON A RAIN GARDEN SOILTHAT DOES NOT PROVIDE ADEQUATE FOUNDING AS PER B.C.3307.6.4.10 REMEDY: #35558232J | Jul 20, 2021 DEFAULT | $0 |
| Issued | Violation | Status |
|---|---|---|
| Mar 5, 2019 | ELEVATOR #9027/646409 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Oct 10, 2025 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction | Active |
| Oct 10, 2025 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction | Active |
| Oct 25, 2024 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device | Active |
| Oct 11, 2024 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device | Active |
None open.
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 29, 2026, 7:47 AM ET. BBL 4050020001.