Manhattan · Block 2178 · Lot 530 · 10033

348 Dyckman Street

class Q1 · owner of record: Nyc Department Of Parks And Recreation

19open violations
$43,750ECB/OATH penalties owed
0HPD class C (immediately hazardous)
—no dated deadlines found

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

We couldn't find building attributes for this lot, so no deadlines are listed.

Open violations

ECB / OATH (17) · $43,750 owed
IssuedViolationHearingBalance
Mar 24, 2022Construction CLASS - 1
FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER SUMMONS 35644718K 35343150H 35343154P 35343155R 35343156Z AND 35343157K STILL EXISTS, COMPLY WITH COMMISSIONER'S ORDER; COMPLY WITH CODE
#39058742Y
May 12, 2022
DEFAULT
$6,250
Feb 9, 2022Construction CLASS - 1
UNLAWFUL ACTS.FAIL TO COMPLY WITH AN ORDER OF COMMISSIONER.FAIL TO CORRECT AND CERTIFY ECB#35343154P-NO GFCI PROVIDED OUTDOOR ECB#35343155R-FIXABLE METAL CONDUIT MORE THAN 6 FT ECB#35343150H-FAILURE TO GROUND,N
#35644718K
May 12, 2022
DEFAULT
$12,500
Dec 21, 2021Construction CLASS - 1
UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS ECB#35343950H;ECB#35343154P AND ECB#35343156Z.UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS
#35644701Y
Mar 24, 2022
DEFAULT
$12,500
Nov 6, 2021Construction CLASS - 1
UNLAWFUL ACTS. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS#35343150H NO WATER MAIN GROUND,SUMMONS#35343151J GEC IS NOT OF PROPER SIZE,SUMMONS#35343154P OUTDOORS AND
#35634351Y
Feb 24, 2022
POP/IN-VIO
$0
Sep 23, 2021Construction CLASS - 1
FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER SUMMONS 35343150H AND 35343155R STILL REMAINS, COMPLY WITH COMMISSIONER'S ORDER; COMPLY WITH CODE
#39048014R
Nov 18, 2021
DEFAULT
$12,500
May 21, 2019Construction CLASS - 2
FAILURE TO COMPLY W/ COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35343248X ISSUED ON 8/6/18,AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1RCNY 102-01(D)(2). AN ACCEPTABLE CERTIFICATE
#37015095Y
Aug 8, 2019
POP/IN-VIO
$0
Oct 5, 2018Unknown CLASS - 2
FAIL TO PROVIDE/MAINTAIN SUFFICIENT ACCESS/WORKSPACE ABOUT ELECTRICAL EQUIPMENT.MIN CLEARANCE IS NOT PROVIDED IN FRONT OF ELECTRICAL PANELS IN KITCHEN ELECT AREA.REM:PROVIDE/MAINTAIN ACCESS/WORK SPACE
#35343158M
Dec 13, 2018
POP/IN-VIO
$0
Oct 5, 2018Unknown CLASS - 1
FAILURE TO GROUND ELECTRICAL SYSTEM.NO WATER MAIN GROUND IS PROVIDED AT WATER MAIN FOR YOU A SENSWIS.REM:PROVIDE GROUNDING.MUST FILE AN ELECTRICAL APPLICATION
#35343150H
Dec 13, 2018
POP/IN-VIO
$0
Oct 5, 2018Unknown CLASS - 1
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICE APPLIANCES OR WIRING IN USE,FLEXIBLE CORD USED AS PERMANENT WIRING OUTDOOR FLEXIBLE CORD USED AS PERMANENT WIRING OUTDOOR FEEDING FAS
#35343157K
Dec 13, 2018
POP/IN-VIO
$0
Oct 5, 2018Unknown CLASS - 1
350.12.3.AMENDMENT.FLEXIBLE METAL CONDUIT FEEDING OUTDOOR AC UNIT BEHIND BAK IS MORE THAN 6FT.REM:COMPLY WITH EC CODE.MUST FILE AN ELECTRICAL APPLICATION
#35343155R
Dec 13, 2018
POP/IN-VIO
$0
Oct 5, 2018Unknown CLASS - 1
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE.EMT USED OUTDOOR TO SUPPLY POWER TO WOMEN LOCKER ROOM.REM:COMPLY WITH EC CODE MUST FILE AN ELECTRICAL AP
#35343156Z
Dec 13, 2018
POP/IN-VIO
$0
Oct 5, 2018Unknown CLASS - 1
TABLE 250.66.GROUNDING CONDUCTOR AT 400 SER SW IS NOT OF PROPER SIZE #8 BARE SOLID CONDUCTOR USE FOR SER ENTRNACE CONDUCTOR 500 INCH GROUNDING CONDUCTOR IS NOT AS PER TABLE.REM:COMPLY WITH EC CODE MUST FILE AN
#35343151J
Dec 13, 2018
POP/IN-VIO
$0
Oct 5, 2018Unknown CLASS - 1
210.8.B.GFCI IS NOT PROVIDED FOR OUTLETS OUTDOOR AND OUTDOOR BAKS ENTIRE GROUNDS OUTDOOR AREA,REC AREA,WOMEN LOCKER ROOM,SHEDS.REM:COMPLY WITH EC CODE MUST FILE AN ELECTRICAL APPLICATION
#35343154P
Dec 13, 2018
POP/IN-VIO
$0
Aug 6, 2018Unknown CLASS - 2
UNAPPROVED/UNSAFE/UNSUITABLE/ELECTRICAL EQUIPMENTS,APPARATUS,MATERIALS,DEVICES,APPARATUS OR WIRING IN USE.EXTERNSION CORDS & FIXTURE/ZIP CORDS USED AS PERMENANT WIRING THROUGHOUT.REM:COMPLY W/EC CODE/OBTAIN PER
#35343248X
Sep 20, 2018
STIPULATION/IN-VIO
$0
Jul 24, 2018Construction CLASS - 1
WORK WITHOUT A PERMIT.AT THE TIME OF MY INSPECTION I OBSERVED THE INSTALLATION OF MOBILE BATHROOM AT THE REAR OF THE ESTABLISHMENT I ALSO OBSERVED THAT THESE BATHROOMS HAD PVC PIPING USED FOR THE WASTE LINES I
#35251183X
Dec 20, 2018
POP/IN-VIO
$0
Jul 24, 2018Plumbing CLASS - 2
FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.FAILURE TO COMPLY WITH LAW FOR DRAINAGE SYSTEM PER 702.1;27-911;THE ABOVE MENTION DATE I OBSERVED THE USE OF PVC PIPING USED THROUGHOUT PREMISES.THE PIPIN
#35251184H
Dec 20, 2018
POP/IN-VIO
$0
Jul 24, 2018Plumbing CLASS - 1
GFC503.4.1.MISC VIOLATIONS USE OF APPROVED MAINTAIN.ON THE ABOVE MENTIONED DATE I OBSERVED PVC PIPING BEING USED TO VENT 2 HOT WATER HEATERSAT THIS PROPERTY WHICH IS NOT PERMITTED AS PER THE CODE.REM:COMPLY WI
#35251185J
Dec 20, 2018
POP/IN-VIO
$0
DOB (0)

None open.

DOB NOW Safety (3)
IssuedViolationStatus
Jan 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle D (premises is in Community District 12)
Active
Jan 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle D (premises is in Community District 12)
Active
Jan 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle D (premises is in Community District 12)
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 28, 2026, 1:06 PM ET. BBL 1021780530.