3 floors · 325 apartments · 145,332 sq ft · built 1988 · class N2 · owner of record: Nyc Department Of Homeless Services
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 67 days | Keep the report on file (not filed with DOB) |
| Bedbug annual filing Applies Local Law 69 · December 1 to 31 each year What this isOwners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page | Dec 31, 2026 in 67 days | Annual |
| Annual boiler inspection (2 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2025-10-30 (Accepted). Agency page | Dec 31, 2026 in 67 days | 2 of 2 without an accepted 2026 report yet |
| Annual notice: window guards and lead paint Applies HPD / Health Code · January 1 to 16 each year What this isDeliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page | Jan 16, 2027 in 83 days | Annual |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 145,332 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 188 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 188 days | Annual filing |
| Annual property registration Applies HPD registration · September 1 each year What this isResidential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page | Overdue | No current registration found |
| Gas piping inspection (2028 cycle) Likely applies Local Law 152 · During 2028 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 1 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2028 in 798 days | Next cycle year 2028 |
| Energy audit and retro-commissioning (2032) Likely applies Local Law 87 · Calendar year 2032 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2572). Agency page | Dec 31, 2032 in 2259 days | Next due 2032 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Apr 5, 2024 | Elevators CLASS - 1 NO DLM WAS INSTALLED ON THIS CONTROLLER AS MANDATED BY THE 2014 NYCBC SECTION 3.10.12. IN CAR PHONE NOT WORKING. BASEMENT BRAIL TAG IS LABELED AS THE EAGLES FLOOR WITH THE STAR. BUT THE FIREMAN SERVICE KEY STAT #39110905P | Jun 7, 2024 POP/IN-VIO | $0 |
| Feb 5, 2024 | Construction CLASS - 2 OBSERVED LIGHTS INSTALLED TO CLOSE TO THE SPRINKLER HEADS. AS PER 314.5 OF THE FIRE CODE SPRINKLER HEADS SHALL NOT BE OBSTRUCTED., REPAIR AND/OR REPLACE #39105151L | Apr 27, 2024 POP/IN-VIO | $0 |
| Feb 5, 2024 | Construction CLASS - 2 OBSERVED IN THE BOILER ROOM LOCATED IN THE BASEMENT/CELLAR 2 CABINETS BEING STORED BEHIND ON OF THE BOILERS. AS PER 315.2.3 OF THE FIRE CODE EQUIPMENT ROOMS. COMBUSTIBLE MATERIAL SHALL NOT BE STORED IN BOILER R #39105152N | Apr 27, 2024 POP/IN-VIO | $0 |
| Dec 29, 2023 | Construction CLASS - 2 HOLE PENETRATION FOUND THROUGHOUT BUILDING., PROVIDE/MAINTAIN FIRE STOPPING #39102495L | Jan 10, 2024 POP/IN-VIO | $0 |
| Dec 29, 2023 | Construction CLASS - 2 NO EMERGENCY LIGHTING IN HALLWAYS, CORRIDORS, AND STAIRCASES THROUGHOUT BUILDING., REPAIR AND/OR REPLACE LIGHTING #39102494J | Jan 10, 2024 POP/IN-VIO | $0 |
| Dec 29, 2023 | Construction CLASS - 2 EMERGENCY EXITS CORRIDORS ARE BLOCKED, DAYCARE, GROUND LEVEL., PROVIDE PROPER CORRIDOR WIDTH #39102496N | Jan 10, 2024 POP/IN-VIO | $0 |
| Dec 29, 2023 | Construction CLASS - 2 EMERGENCY EXITS DOORS DO NOT FUNCTION/OPEN PROPERLY THROUGHOUT BUILDING., REPAIR AND/OR REPLACE #39102493H | Jan 4, 2024 POP/IN-VIO | $0 |
| Dec 28, 2023 | Elevators CLASS - 1 CLASS 1 ITEM: NO DOOR LOCK MONITORING INSTALLED ON THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BUILDING CODE. THIS IS A FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION, INSTAL #39102345X | Jan 10, 2024 POP/IN-VIO | $0 |
| Aug 8, 2022 | Boilers CLASS - 2 FOUND EXPOSED WIRES ON COMBUSTION AIR FAN, COVER TO COMBUSTION AIR FAN NOT PROPERLY SECURED, SAFETY RELIEF VALVE LEAKING, #39067588J | Aug 20, 2022 POP/IN-VIO | $0 |
| Jul 29, 2022 | Boilers CLASS - 2 AS PER ONE WEIL MCLAIN 1288 IN CELLAR BOILER ROOM; MOTOR COVERING AND BELT GUARD FOR COMBUSTION AIR FAN NOT IN PLACE-ELECTRICAL WIRES EXPOSED AT COMBUSTION AIR FAN MOTOR. #39066958N | Aug 20, 2022 POP/IN-VIO | $0 |
| Jul 27, 2022 | Elevators CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION INSTALL DLM AND PERFOR #39066796J | Jul 27, 2022 POP/IN-VIO | $0 |
| May 9, 2022 | Construction CLASS - 2 I OBSERVED THROUGHOUT BUILDING SPRINKLER HEADS ARE INSTALLED TO CLOSE TO LIGHT FIXTURES, ALSO BOILER #2 HAS AN ACTIVE LEAK ON COPPER PIPING., REPAIR AND/OR REPLACE #39061833R | May 11, 2022 POP/IN-VIO | $0 |
| May 9, 2022 | Construction CLASS - 2 AT FIRST FLOOR, EXIT DOORS SHOW FAILURE TO CLOSE & OPEN PROPERLY., REPAIR/REPLACE DOOR #39061830L | May 11, 2022 POP/IN-VIO | $0 |
| Aug 13, 2021 | Elevators CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION INSTALL DLM AND PERFOR #39045992Y | Sep 14, 2021 POP/IN-VIO | $0 |
| May 21, 2018 | Construction CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. MULTIPLE EXHAUST FAN UNITS NOT WORKING. UNITS ARE LOCATED ON ROOF. NOTE: APPROX 10 UNITS NOT WORKING. REM: REPAIR &/OR REPLACE. #35331847J | Aug 3, 2018 POP/IN-VIO | $0 |
| Apr 10, 2018 | Boilers CLASS - 2 B254,50A,50B,50C. AS PER CLASS 2 (B254) 28-301.1 FAILURE TO MAINTAIN 50A-HEATING PUMP OVER BOILER IS LEAKING; 50B-EXPOSED ELECTRICAL WIRES FROM CONNECTION BOXES LIGHT FIXTURES; 50C-BOILER ROOM DOORS NOT SELF #32096625H | Jun 1, 2018 WRITTEN OFF | $0 |
| Issued | Violation | Status |
|---|---|---|
| Mar 2, 2020 | ELEVATOR #9028/673634 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Oct 10, 2025 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction | Active |
| Aug 29, 2025 | Elevators FTF-VT-PER-CO Violation Issued-Failure To File 2024 Periodic Inspection Report | Active |
| Oct 23, 2023 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction | Active |
| Oct 23, 2023 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction | Active |
| Oct 23, 2023 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction | Active |
None open.
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 25, 2026, 11:00 AM ET. BBL 2025720006.