Manhattan · Block 1035 · Lot 9 · 10036

343 West 44 Street

7 floors · 37,726 sq ft · built 1926 · class H3 · owner of record: Brisam Clinton Llc

12open violations
$39,584ECB/OATH penalties owed
0HPD class C (immediately hazardous)
46dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 46 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 46 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 37,726 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 167 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 167 days
Annual filing
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $656,000 in late-filing or failure-to-file penalties. Agency page

On fileCycle 10 filing on record: SWARMP (2025-12-10)

Open violations

ECB / OATH (12) · $39,584 owed
IssuedViolationHearingBalance
Aug 27, 2026Unknown CLASS - 1
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN THE LOBBY FLEX CORDS PASSING ON THE FLOOR COVED BY CARDBOARD, THE BODY SCANNER CORD STA
#39202191K
Dec 17, 2026
PENDING
$1,600
Aug 27, 2026Construction CLASS - 1
AT THE TIME OF INSPECTION OBSERVED THROUGHOUT THE BUILDING IN STORAGE ROOMS BOXES STACKED TO THE CEILING BLOCKING OPERATION OF SIDE WALL SPRINKLER HEADS CONTRARY TO BC 903.3.3, REPAIR AND/REPLACE
#39202203Z
Dec 17, 2026
$2,500
Aug 27, 2026Construction CLASS - 1
ATOIOBSERVED PLASTIC PVC PIPING BEING USED FOR DRAINAGE UNDER 2 COMPARTMENT SINK WITH NO TRAP INSTALLED HAVING PVC FLEXIBLE PIP DRAINING INTO A NO HUB REDUCING FITTING CONTRARY TO . PC 1002.1 & PC 706.1 ALL FIX
#39202205M
Dec 17, 2026
PENDING
$2,500
Aug 27, 2026Unknown CLASS - 1
FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED IN THE BASEMENT MAIN BUILDING WATER GROUND CLAMP IS RUSTED AND BROKEN AT THE BOLT THE GROUND WIRE IS OXIDIZE. GROUND CLAMP MUST MAINTAIN CONTIUNITY TO PROTECT ELEC
#39202190Z
Dec 17, 2026
PENDING
$4,800
Aug 27, 2026Construction CLASS - 1
AT THE TIME OF INSPECTION OBSERVED 3 NEW HOT WATER HEATERS INSTALLED WITH OUT PERMITS CHECKED BIS/DOBNOW NO PERMITS ON FILE THE BUILDING PD SAID WASNT AWARE HE NEEDED PERMITS ALL WORK NEEDS PERMIT AND MUST BE D
#39202204K
Dec 17, 2026
PENDING
$2,500
Nov 18, 2025Elevators CLASS - 2
CLASS 2: CAR RE-LEVELING WITH THE DOOR OPEN CREATING A TRIPPING HAZZARD, CORRECT CAR FROM RE-LEVELING. CAR DOOR SLAMS OPEN IN THE OPENING CYCLE, ADJUST/REPAIR.
#39167397P
Jan 22, 2026
DEFAULT
$1,562
Nov 17, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION # 39122558H, # 39122560R FOR MISCELLANEOUS VIOLATIONS ( SUSPENDED SCAFFOLD) ISSUED ON 08/20/2024, FILE A CERTIFICATE OF CORRECTION
#39167312R
Jan 22, 2026
DEFAULT
$3,125
Nov 17, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION # 39122564Y ISSUED ON 08/20/2024 FOR NO RECORD OF DAILY INSPECTION OF SUSPENDED SCAFFOLD PERFORMED BY AUTHORIZED PERSON AT SITE, FILE A CERTIFICATE OF C
#39167313Z
Jan 22, 2026
DEFAULT
$3,125
Aug 15, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRATIONS. LOCATED ON FIRST FLOOR (COMMON SPACE COVERED WITH VEN
#39157286N
Apr 6, 2027
$2,530
Jun 25, 2025Elevators CLASS - 1
CEASE USE ITEM: FOUND EXCESSIVE GAP BETWEEN CAR DOOR AND RETURN WHEN IN THE CLOSED POSITION. CLASS 2 ITEM: ALARM BELL INOPERATIVE WHEN STOP SWITCH AND ALARM BELL BUTTON IS ANITIATED.
#39151964X
Feb 18, 2027
$1,280
May 30, 2025Elevators CLASS - 2
CLASS 2 ITEMS: REPLACE PACKING ON HYDRAULIC JACK. CLEAN OIL THOROUGHLY ON TOP OF CAR AND A PIT.
#39149388Y
Aug 7, 2025
DEFAULT
$1,562
Aug 20, 2024Construction CLASS - 1
AT THE TIME OF MY INSPECTION THE REQUESTED INSPECTION LOGS FOR THE SUSPENDED SCAFFOLD WERE NOT PROVIDED BY THE COMPETENT PERSON ON SIGHT. AS PER BC 3314.4.3.4 THIS INSPECTION REPORTS SHALL BE MADE AVAILABLE.; 3
#39122560R
Nov 13, 2025
DEFAULT
$12,500
DOB (2)
IssuedViolationStatus
Feb 22, 2022NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
#02390
DOB VIOLATION - ACTIVE
Jul 15, 2020ELEVATOR

#9027/685917
DOB VIOLATION - ACTIVE
DOB NOW Safety (5)
IssuedViolationStatus
Nov 5, 2026AEUHAZ FTC-AEU-HAZ
Active
Nov 5, 2026AEUHAZ FTC-AEU-HAZ
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Feb 22, 2022Facades FISPNRF
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Nov 5, 2026DOB SafetyAEUHAZ: Open
Nov 5, 2026DOB SafetyAEUHAZ: Open
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Aug 27, 2026ECBUnknown: UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN THE LOBBY FLEX CORDS PASSING ON THE FLOOR COVED BY CARDBOARD, THE BODY SCANNER CORD STAOpen
Aug 27, 2026ECBConstruction: AT THE TIME OF INSPECTION OBSERVED THROUGHOUT THE BUILDING IN STORAGE ROOMS BOXES STACKED TO THE CEILING BLOCKING OPERATION OF SIDE WALL SPRINKLER HEADS CONTRARY TO BC 903.3.3, REPAIR AND/REPLACEClosed
Aug 27, 2026ECBConstruction: ATOIOBSERVED PLASTIC PVC PIPING BEING USED FOR DRAINAGE UNDER 2 COMPARTMENT SINK WITH NO TRAP INSTALLED HAVING PVC FLEXIBLE PIP DRAINING INTO A NO HUB REDUCING FITTING CONTRARY TO . PC 1002.1 & PC 706.1 ALL FIXOpen
Aug 27, 2026ECBUnknown: FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED IN THE BASEMENT MAIN BUILDING WATER GROUND CLAMP IS RUSTED AND BROKEN AT THE BOLT THE GROUND WIRE IS OXIDIZE. GROUND CLAMP MUST MAINTAIN CONTIUNITY TO PROTECT ELECOpen
Aug 27, 2026ECBConstruction: AT THE TIME OF INSPECTION OBSERVED 3 NEW HOT WATER HEATERS INSTALLED WITH OUT PERMITS CHECKED BIS/DOBNOW NO PERMITS ON FILE THE BUILDING PD SAID WASNT AWARE HE NEEDED PERMITS ALL WORK NEEDS PERMIT AND MUST BE DOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 15, 2026, 6:01 AM ET. BBL 1010350009.

Look up another building