Brooklyn · Block 4131 · Lot 1 · 11208

3345 Fulton Street

2 floors · 10,985 sq ft · built 1932 · class O9 · owner of record: The Greenpoint Savings Bank

5open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
1157dto Gas piping inspection (2029 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 61 days
Keep the report on file (not filed with DOB)
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 5 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1157 days
Next cycle year 2029
Annual boiler inspection (3 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-06-24 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (4)
IssuedViolationHearingBalance
Feb 27, 2016Boilers CLASS - 2
B254,36,32A,50A,50,B,50C,50D,50E. 50A- SECOND LOW WATER CUT OFF MISS ING; 50B- SPILL SWITCH MISSING; 50C-BACK FLOW LEAKING; 50D-FRESH AIR INTAKE NOT 36"ABOVE GRADE; 50F-NO EMERGENCE FUEL CUT OFF SWITCH OUT
#32076196K
Apr 18, 2016
STIPULATION/IN-VIO
$0
Feb 27, 2016Construction CLASS - 1
B101, 50A. 50A- NO WORK PERMIT FILED WITH DOB FOR THE REPLACEMENT BOILER.
#32076195Z
Apr 18, 2016
WRITTEN OFF
$0
Feb 27, 2016Boilers CLASS - 2
B254,32A,36,50A,50B,50C,50D,19B 50A-SECOND LOW WATER CUT OFF MISSING;50B- BACKFLOW PREVENTOR LEAKING; 50C- SPILL SWITCH MISSING; 50D-FRESH AIR INTAKE HOT 36"ABOVE GRADE.
#32076194R
Apr 18, 2016
WRITTEN OFF
$0
Feb 27, 2016Boilers CLASS - 2
B254,36,32A,19B,50A,50B,50C,50B. 50A-NO EMERGENCE SWITCH OUTSIDE OF BOILER ROOM FIRE DOOR; 50B-SPILL SWITCH MISSING; 50C-SECOND LOW WATER CUT OFF MISSING; 50D-BACK FLOW PREVENTOR LEAKING.
#32076197M
Apr 18, 2016
WRITTEN OFF
$0
DOB (1)
IssuedViolationStatus
Aug 16, 1993LOCAL LAW 62/91 - BOILERS

#28170
DOB VIOLATION - ACTIVE
DOB NOW Safety (0)

None open.

HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 31, 2026, 11:51 AM ET. BBL 3041310001.