Queens · Block 307 · Lot 10 · 11101

33-17 Greenpoint Avenue

5 floors · 34,666 sq ft · built 1940 · class H3 · owner of record: Jai Ambe .

19open violations
$17,768ECB/OATH penalties owed
0HPD class C (immediately hazardous)
61dto Annual boiler inspection (2 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 61 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2024-03-12 (Accepted). Agency page

Dec 31, 2026
in 61 days
2 of 2 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 34,666 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 182 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 182 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 2 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1157 days
Next cycle year 2029

Open violations

ECB / OATH (17) · $17,768 owed
IssuedViolationHearingBalance
Sep 10, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES. ATOI I OBSERVED AT EXPOSURE# 1,2,3,4 OF THE FACADE WALLS ON ALL LEVEL, CRACK IN BRICK FACADE WITH LOOSE AND MISSING BRICKS WITH MORTAR MISSING BETWEEN BRICK
#39203585H
Nov 17, 2026
PENDING
$5,000
Sep 4, 2026Construction CLASS - 2
AT TIME OF INSPECTION, OBSERVED PLASTIC PVC USED ON WASHING MACHINE DRAINAGE & SLOP SINK. THE SINK ALSO DID NOT HAVE A TRAP CONTRARY TO PC 701.9 & 1002.1, REPAIR AND/OR REPLACE
#39203114L
Nov 10, 2026
PENDING
$1,250
Sep 4, 2026Elevators CLASS - 1
CLASS 1 C/U: 1. TOP-OF-CAR STOP SWITCH - INOPERATIVE, FAILING REQUIRED EMERGENCY STOP FUNCTION FOR PERSONNEL ON TOP OF CAR. AS PER ASME A17.1 2.27 & 8.6. 2. FIRE SERVICE PHASE I - IMPROPER PHASE I OPERATION, FA
#39203113J
Nov 10, 2026
PENDING
$1,250
Sep 3, 2025Elevators CLASS - 1
CLASS 1 C/U ITEM: DOOR LOCK MONITORING SYSTEM INOPERABLE, REPAIR AND EMAIL THE ELEVATOR DIVISION AT EIR@BUILDINGS.NYC.GOV FOR A RE-INSPECTION. 97-X-17.
#39159111K
Jun 4, 2026
IN VIOLATION
$1,250
May 8, 2025Construction CLASS - 2
FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION # 39125354J, FILE A CERTIFICATE OF CORRECTION
#39147460K
Dec 15, 2026
$1,280
Sep 19, 2024Construction CLASS - 2
OBSERVED PAINTED SPRINKLER CAPS IN THE FOOD SERVICE ROOM LOCATED ON THE MAIN FLOOR. AS PER 901.6 MAINTENANCE. FIRE PROTECTION SYSTEMS SHALL BE MAINTAINED IN GOOD WORKING ORDER AT ALL TIMES. ANY FIRE PROTECTION
#39125355L
Nov 26, 2024
IN VIOLATION
$312
Sep 19, 2024Construction CLASS - 1
OBSERVED EXCESSIVE HOLES PENETRATION THROUGHOUT THE BUILDING. LOCATED IN STORAGE ROOMS AND MECHANICAL ROOM ON TOP FLOOR., PROVIDE/MAINTAIN FIRE STOPPING
#39125354J
Nov 26, 2024
IN VIOLATION
$2,500
Nov 7, 2022Construction CLASS - 1
OBSERVED: FROM SECOND FL TO 5TH FL EXIT CORRIDORS ARE BEING OBSTRUCTED BY MATERIALS SUCH AS GARBAGE CANS, DESKS, CHAIRS, MICROWAVE OVENS, TABLES AND OTHER ELEMENTS THAT OBSTRUCT THE EXITS PASSAGEWAY. ALSO, AT F
#39073550P
Jan 24, 2023
IN VIOLATION
$312
Nov 7, 2022Construction CLASS - 2
OBSERVED: AT FIRST FL, ELECTRICAL/BOILER RMS, WALLS SHOW SIGNS OF WATER PENETRATION WITH DAMAGE /DETACHMENT OF MORTAR AND PAINT, MAINTAIN EXTERIOR BUILDING WALL
#39073553K
Jan 24, 2023
IN VIOLATION
$625
Nov 7, 2022Unknown CLASS - 2
I OBSERVED THROUGHOUT THE CORRIDORS AND THE STAIRWELLS THE REPLACEMENT OF EXISTING EMERGENCY LIGHTS. NO ACTIVE PERMIT ON FILE IN DOB RECORDS COVERS THE ABOVEMENTIONED WORK., OBTAIN PERMIT; OBTAIN PERMIT AND CAL
#39073561K
Jan 24, 2023
IN VIOLATION
$400
Nov 7, 2022Construction CLASS - 2
OBSERVED: AT EXPOSURE #1,2,3 &4, BRICK FACADE/ CHIMNEY WITH MANY CRACKS, LOSS OF MORTAR. DAMAGE AND LOSS OF GUTTERS/METAL CORNICE, AT SECOND FL, STORAGE ROOM/LOCKERS, CRACKS, IN DIFFERENT LOCATIONS , ALSO, OPEN
#39073554M
Jan 24, 2023
IN VIOLATION
$625
Nov 7, 2022Unknown CLASS - 1
I OBSERVED IN THE STORAGE ROOM NEAR ROOM 302, THE STAFF BREAKROOM AND LOCKER ROOM ON THE 2ND FLOOR, THE USE OF FLEXIBLE CORDS AS PERMANENT WIRING. FLEXIBLE WIRING SHALL NOT BE INSTALLED IN THE WALL, USED FOR FI
#39073559L
May 23, 2023
IN VIOLATION
$1,600
Nov 7, 2022Construction CLASS - 2
OBSERVED: AT 5TH FL, ROOMS UNDER THE ROOF AS STORAGE RM/MECHANICAL RM, ELEVATOR RM, STORAGE RM FROM 5TH FL TO 2ND FL & AT FIRST FL, ELECTRICAL/BOILER RMS SEVERAL OPENING/DILATIONS DUE PIPE/CABLES PENETRATION, C
#39073552Z
Jan 24, 2023
IN VIOLATION
$625
Nov 7, 2022Unknown CLASS - 2
I OBSERVED IN THE LAUNDRY, THE METAL RACEWAY SUPPLYING POWER TO THE DRYER BROKEN WITH EXPOSED WIRES AND THE SHUT-OFF SWITCH FOR THE WASHING MACHINE WITHOUT PROPER ACCESS/WORK SPACE. ALSO NOTED ON THE 5TH FLOOR
#39073560Z
Jan 24, 2023
IN VIOLATION
$400
Sep 19, 2022Elevators CLASS - 2
DIRTY PIT , CLEAN / WORN RELEASE ROLLERS , REPLACE / CLUTCH SCRAPING AGAINST FACIA , ADJUST / MCP LOG BOOK NOT CURRENT , PROVIDE UPDATED LOG BOOK
#39070284H
Nov 15, 2022
IN VIOLATION
$312
Sep 30, 2021Elevators CLASS - 1
NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION INSTALL DLM AND PERFOR
#39048456Y
Nov 16, 2021
IN VIOLATION
$27
Jul 25, 2019Construction CLASS - 1
OBSERVED FALSE DOCUMENTS SUBMITTED FOR ECB #35383929H STATING THAT THE VIOLATING CONDITIONS WERE CORRECTED BY JAI AMBE. THE C OF C WAS SUBMITTED ON 06/12/19., CORRECT CONDITIONS CITED AND FILE A VALID CERTIFICA
#39006367R
Jun 22, 2021
IN VIOLATION
$0
DOB (4)
IssuedViolationStatus
Apr 1, 2022PLUMBING
LAA DIVISION HAS ORDERED TO STOP ALL PLUMBING WORK IMMEDIATELY UNDER PERMIT # Q00604969 DUE TO UNRESPONSIVE AUDIT OBJECTIONS. OBSERVED 100 % OF WORK DONE AT THE TIME OF MY INSPECTION.
#22-00936
DOB VIOLATION - ACTIVE
Mar 20, 2014ELEVATOR

#9027/501949
DOB VIOLATION - ACTIVE
Feb 22, 2013ELEVATOR

#9027/444079
DOB VIOLATION - ACTIVE
Jan 13, 1997LOCAL LAW 10/81 - ELEVATOR

#03637
DOB VIOLATION - ACTIVE
DOB NOW Safety (10)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 21, 2026AEUHAZ FTC-AEU-HAZ
Active
Oct 21, 2026AEUHAZ FTC-AEU-HAZ
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 21, 2026DOB SafetyAEUHAZ: Open
Oct 21, 2026DOB SafetyAEUHAZ: Open
Sep 10, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES. ATOI I OBSERVED AT EXPOSURE# 1,2,3,4 OF THE FACADE WALLS ON ALL LEVEL, CRACK IN BRICK FACADE WITH LOOSE AND MISSING BRICKS WITH MORTAR MISSING BETWEEN BRICKOpen
Sep 4, 2026ECBConstruction: AT TIME OF INSPECTION, OBSERVED PLASTIC PVC USED ON WASHING MACHINE DRAINAGE & SLOP SINK. THE SINK ALSO DID NOT HAVE A TRAP CONTRARY TO PC 701.9 & 1002.1, REPAIR AND/OR REPLACEOpen
Sep 4, 2026ECBElevators: CLASS 1 C/U: 1. TOP-OF-CAR STOP SWITCH - INOPERATIVE, FAILING REQUIRED EMERGENCY STOP FUNCTION FOR PERSONNEL ON TOP OF CAR. AS PER ASME A17.1 2.27 & 8.6. 2. FIRE SERVICE PHASE I - IMPROPER PHASE I OPERATION, FAOpen