Manhattan · Block 905 · Lot 1 · 10010

321 3 Avenue

11 floors · 50,757 sq ft · built 1925 · class HB · owner of record: East Side Inn,

7open violations
$35,312ECB/OATH penalties owed
0HPD class C (immediately hazardous)
63dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 63 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 63 days
Keep the report on file (not filed with DOB)
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $1,148,750 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2027
in 115 days
No Cycle 10 report on record yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 50,757 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 184 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 184 days
Annual filing
Energy audit and retro-commissioning (2035) Likely applies
Local Law 87 · Calendar year 2035
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 905). Agency page

Dec 31, 2035
in 3350 days
Next due 2035
Annual boiler inspection (3 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-06-17 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (17) · $35,312 owed
IssuedViolationHearingBalance
Aug 12, 2026Elevators CLASS - 1
CLASS1 ITEMS: BRAKE ACTUATOR HAS PARTS REMOVED - REPAIR/REPLACE AS REQUIRED. 28-304.1
#39200254J
Mar 29, 2027
PENDING
$1,250
Nov 12, 2025Elevators CLASS - 1
CEASE USE ITEM: TRAVELING CABLE SHOWING EXPOSED COPPER NEAR PIT LADDER. REPLACE CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. CATEGORY 1 TEST TAG EXPIRED.
#39166749P
Jun 11, 2026
IN VIOLATION
$1,250
Jul 31, 2025Construction CLASS - 1
OBSERVED IN BASEMENT GAS LINE RUNNING THROUGH THE FIRE PUMP ROOM. FIRE PUMP GAGE IS BROKEN, FIRE PUMP VALVES TO CLOSE TO WALL. IN KITCHEN OPEN ENDED GAS LINES. SPRINKLER HEADS COVERED IN PAINT. THROUGHOUT BUILD
#39155684J
Dec 17, 2026
$2,500
Jul 31, 2024Elevators CLASS - 1
CLASS 1 ITEM: MAIN BRAKE SWITCH BYPASSED. ONE SIDE OF THE BRAKE NOT PICKING AND RELEASING. NEED TO CORRECT. . REMEDY: TO RESTORE SERVICE, CALL THE D.O.B. ELEVATOR DIVISION AT (212) 393-2144 FOR A REINSPECTION.
#39120422J
Nov 14, 2024
IN VIOLATION
$1,250
Jul 30, 2024Unknown CLASS - 1
I OBSERVED ON ALL FLOORS THE FAILURE TO INSTALL TAMPER-RESISTANT/PROOF RECEPTACLES AS REQUIRED IN PUBLIC HALLS ACCESSIBLE TO CHILDREN AS LL 39/2015. THIS IS A IMMEDIATE SHOCK HAZARD., COMPLY WITH EC; PROVIDE/MA
#39120314M
Nov 14, 2024
IN VIOLATION
$1,600
Jul 30, 2024Unknown CLASS - 1
I OBSERVED ON THE 2ND FLOOR ROOF THE COMPRESSOR MOTOR CONDUCTORS ENERGIZED AND EXPOSED TO THE ELEMENTS. THIS IS AN IMMEDIATE SHOCK/OR FIRE HAZARD. ALSO NOTED IN THE BASEMENT ELECTRICAL ROOM VARIOUS JUNCTION BOX
#39120319L
Nov 14, 2024
IN VIOLATION
$1,600
Jul 30, 2024Unknown CLASS - 1
I OBSERVED THE USE OF FLEXIBLE CORDS AS PERMANENT WIRING IN THE ROOFTOP BOILER ROOM, ON THE 10TH FLOOR TERRACE, AND THE BASEMENT ELEVATOR MOTOR ROOM. AS PER EC 400.8 FLEXIBLE CORDS ARE NOT ALLOWED AS PERMANENT
#39120316X
Jun 12, 2025
IN VIOLATION
$1,600
Jul 30, 2024Construction CLASS - 1
RUSTED AND CORRODED CEILING, EXPOSING LARGE SECTION OF CEILING JOIST, METEL/STEEL I-BEAMS, METAL STUDS, AND WOODEN FLOOR JOIST. LACK OF FIRE-STOPPING CAN RESULT IN HAZARD WHEN MECHANICAL ROOMS ARE NOT SEALED.,
#39120329P
Nov 21, 2024
IN VIOLATION
$1,250
Jul 30, 2024Construction CLASS - 1
IMPROPER STORAGE, (DESK, CHAIRS, WATER HEATER TANK, BUCKETS OF PAINT, AND OTHER CLEANING CHEMICAL MATERIALS AND UNDERNEATH METAL STAIRCASE LEADING TO STREET LEVEL, (HVAC DUCT/VENTS, CLEANING CHEMICALS, AND COOK
#39120325H
Nov 14, 2024
IN VIOLATION
$1,250
Jul 30, 2024Unknown CLASS - 1
I OBSERVED IN THE ROOFTOP ELEVATOR ROOM THE IMPROPER TERMINATION OF 2 CONDUCTORS UNDER A SINGLE LUG NOT DESIGNED FOR THAT PURPOSE. ALSO NOTED IN BASEMENT ELEVATOR MOTOR ROOM THE IMPROPER FUSING OF THE NEUTRAL I
#39120317H
Jun 12, 2025
IN VIOLATION
$1,600
Jul 30, 2024Unknown CLASS - 1
I OBSERVED IN THE ROOFTOP ELEVATOR ROOM, THE MOTOR DISCONNECT CONDUCTORS INSTALLED IN THE SAME RACEWAY WHICH NEGATES THE FUSE PROTECTION. THIS IMPROPER CROSSING OF LINE AND LOAD CONDUCTORS IS NOT PERMITTED., PR
#39120315Y
Jun 12, 2025
IN VIOLATION
$4,800
Jul 30, 2024Unknown CLASS - 2
I OBSERVED IMPROPER INSTALLATION OF OR FAILURE TO PROVIDE GFCI PROTECTION AS REQUIRED IN THE ROOFTOP BOILER ROOM, THE TENTH FLOOR BATHROOM, AND THE BASEMENT ELEVATOR ROOM., INSTALL GFC1 PROTECTION; PROVIDE/ MAI
#39120318J
Nov 14, 2024
IN VIOLATION
$1,200
Feb 10, 2023Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING.NOTED;EXIT DOORS & CORRIDOR SMOKE DOORS NOT SELF CLOSING LOCATED ON 6TH,7TH,8TH FL LEVELS.REMEDY:REPAIR/REPLACE DOORS.
#35666508J
May 18, 2023
IN VIOLATION
$312
Dec 2, 2022Local Law CLASS - 2
FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 8A & 9A REPORT OF CRITICALEXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCES RE QUIRED BY 28-302.4 FOR CONTROL #913104 AGG1:HISTORY OF NONCOMPLIANCE O
#37024172N
Mar 23, 2023
IN VIOLATION
$6,250
Jun 1, 2021Local Law CLASS - 2
FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 7A AND 8A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #813104. AGG2 HISTORY OF NONCOMP
#37021389K
Jun 2, 2022
IN VIOLATION
$1,250
May 20, 2020Local Law CLASS - 2
FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 7A & 8A REPORT CRITICALEXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#813104. AGG2 HISTORY OF NONCOMPLIANCE ON
#37018995N
Dec 3, 2020
IN VIOLATION
$6,250
May 18, 2018Local Law CLASS - 2
FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#813104. REMEDY: SUBMIT REQUIRED TECHNICAL REPORT
#37010497Y
Mar 14, 2019
IN VIOLATION
$100
DOB (5)
IssuedViolationStatus
May 22, 1997CONSTRUCTION

#06BL03
VIOLATION UNSERVED ECB-ACTIVE
Jan 23, 1997CONSTRUCTION

#06S1
VIOLATION UNSERVED ECB-ACTIVE
Apr 8, 1995ELEVATOR

#71A1
DOB VIOLATION - ACTIVE
Mar 18, 1994LOCAL LAW 62/91 - BOILERS

#04883
DOB VIOLATION - ACTIVE
Mar 18, 1993LOCAL LAW 62/91 - BOILERS

#04883
DOB VIOLATION - ACTIVE
DOB NOW Safety (1)
IssuedViolationStatus
Sep 16, 2026AEUHAZ FTC-AEU-HAZ
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Sep 16, 2026DOB SafetyAEUHAZ: Open
Aug 12, 2026ECBElevators: CLASS1 ITEMS: BRAKE ACTUATOR HAS PARTS REMOVED - REPAIR/REPLACE AS REQUIRED. 28-304.1Open

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 29, 2026, 9:43 PM ET. BBL 1009050001.