Manhattan · Block 106 · Lot 17 · 10038

320 Pearl Street

9 floors · 27,356 sq ft · built 2002 · class H3 · owner of record: 320 Pearl Street Propco Llc

19open violations
$14,375ECB/OATH penalties owed
0HPD class C (immediately hazardous)
177dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 56 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 27,356 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 177 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 177 days
Annual filing
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 1 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 787 days
Next cycle year 2028
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $191,250 in late-filing or failure-to-file penalties. Agency page

On fileCycle 10 filing on record: SAFE (2025-07-14)

Open violations

ECB / OATH (7) · $14,375 owed
IssuedViolationHearingBalance
Oct 27, 2026Elevators CLASS - 1
VF... ALARM BELL INOPERATIVE . REPAIR.. COMMUNICATION INOPERATIVE REPAIR... 8.6.4.15...MAINTENANCE LOG UPDATE MISSING PROVIDE...8.6.1.4....
#39209459Y
Dec 31, 2026
PENDING
$3,125
Aug 12, 2026Plumbing CLASS - 1
AT THE TIME OF INSPECTION OBSERVED WITH IN MAIN HOT WATER HEATER ROOM NO FLOOR DRAIN INSTALLED ALL MECHANICAL/BOILER ROOM REQUIRE FLOOR DRAIN FOR LIQUID WASTE DISPOSAL; MC 1004.6, COMPLY WITH NOTICE OF VIOLATIO
#39200271L
Dec 31, 2026
PENDING
$2,500
Aug 12, 2026Construction CLASS - 1
AT THE TIME OF INSPECTION OBSERVED HOT WATER HEATERS INSTALLED WITH OUT A PERMIT ON FILE CHECKED BIS/DOBNOW NO PERMITS ON FILE. MANAGING AGENT ALSO SAID SHE DIDNT HAVE A PERMIT, OBTAIN PERMIT
#39200270J
Dec 31, 2026
PENDING
$2,500
Aug 12, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED THE FOLLOWING VIOLATING. HOLE PENETRATIONS (PLASTIC ACCESS PANELS/WOOD) NOT FIRE RATED. LOCATED THROUGHOUT BUILDING.B POTENTIAL FIRE HAZARD. MAY A
#39200285M
Dec 3, 2026
PENDING
$2,500
Aug 12, 2026Construction CLASS - 1
AT THE TIME OF INSPECTION OBSERVED OBSTRUCTED SPRINKLER HEADS AND CAPS PAINTED TO THE CEILING WHICH IS CONTRARY TO 903.3.3 ALL SPRINKLER SHOULD BE FREE OF OBSTRUCTIONS, REPAIR AND/REPLACE
#39200269M
Dec 10, 2026
$2,500
Aug 12, 2026Elevators CLASS - 1
CLASS 1: 1. FIREFIGHTER'S SERVICE PHASE II KEY ROTATES FREELY 360 DEGREES EVEN THOUGH IT ACTIVATES PHASE II MODE, INDICATING IMPROPER KEY CONTROL. AS PER ASME A17.1 2.27. REMEDY: CORRECT PHASE II KEY MECHANISM
#39200373M
Dec 31, 2026
PENDING
$1,250
May 6, 2025Unknown CLASS - 2
AT TIME OF INSPECTION OF A 9 STORIES BUILDING I OBSERVED SIDEWALK SHED IN PLACE ON EXPOSURE#1 UPON REVIEW THE DEPARTMENT RECORDS TO VERIFY COMPLIANCE IT WAS REVEAL THAT THE PERMIT HAD EXPIRED SINCE 03-22-2025AN
#39539863H
Jul 10, 2025
DEFAULT
$0
DOB (0)

None open.

DOB NOW Safety (8)
IssuedViolationStatus
Sep 25, 2026Benchmarking - LL84 FTF-EN-BENCH
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
Active
Jun 22, 2026Benchmarking - LL84 FTF-EN-BENCH
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
Active
Mar 6, 2026Energy Grade - LL33 FTP-EN-EGRDEA
FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER AD CODE SEC. 28-309.12.3
Active
Mar 6, 2026Benchmarking - LL84 FTF-EN-BENCH
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
Active
Dec 8, 2025GHG Emissions - LL97 FTF-EN-LL97320
Active
Dec 3, 2025Benchmarking - LL84 FTF-EN-BENCH
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Sep 26, 2025Benchmarking - LL84 FTF-EN-BENCH
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
Active
HPD (5) · C 0 · B 0 · A 3
IssuedClassViolationCorrect by
Nov 22, 2024I§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID R—
Nov 17, 2025I§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID R—
May 8, 2026A(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.Aug 11, 2026
Jun 13, 2025A(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.Sep 16, 2025
Apr 17, 2024A(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.Jul 21, 2024

Issued in the last 120 days

DateSourceWhatNow
Oct 27, 2026ECBElevators: VF... ALARM BELL INOPERATIVE . REPAIR.. COMMUNICATION INOPERATIVE REPAIR... 8.6.4.15...MAINTENANCE LOG UPDATE MISSING PROVIDE...8.6.1.4....Open
Sep 25, 2026DOB SafetyBenchmarking - LL84: FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4Open
Aug 12, 2026ECBPlumbing: AT THE TIME OF INSPECTION OBSERVED WITH IN MAIN HOT WATER HEATER ROOM NO FLOOR DRAIN INSTALLED ALL MECHANICAL/BOILER ROOM REQUIRE FLOOR DRAIN FOR LIQUID WASTE DISPOSAL; MC 1004.6, COMPLY WITH NOTICE OF VIOLATIOOpen
Aug 12, 2026ECBConstruction: AT THE TIME OF INSPECTION OBSERVED HOT WATER HEATERS INSTALLED WITH OUT A PERMIT ON FILE CHECKED BIS/DOBNOW NO PERMITS ON FILE. MANAGING AGENT ALSO SAID SHE DIDNT HAVE A PERMIT, OBTAIN PERMITOpen
Aug 12, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED THE FOLLOWING VIOLATING. HOLE PENETRATIONS (PLASTIC ACCESS PANELS/WOOD) NOT FIRE RATED. LOCATED THROUGHOUT BUILDING.B POTENTIAL FIRE HAZARD. MAY AOpen
Aug 12, 2026ECBConstruction: AT THE TIME OF INSPECTION OBSERVED OBSTRUCTED SPRINKLER HEADS AND CAPS PAINTED TO THE CEILING WHICH IS CONTRARY TO 903.3.3 ALL SPRINKLER SHOULD BE FREE OF OBSTRUCTIONS, REPAIR AND/REPLACEClosed
Aug 12, 2026ECBElevators: CLASS 1: 1. FIREFIGHTER'S SERVICE PHASE II KEY ROTATES FREELY 360 DEGREES EVEN THOUGH IT ACTIVATES PHASE II MODE, INDICATING IMPROPER KEY CONTROL. AS PER ASME A17.1 2.27. REMEDY: CORRECT PHASE II KEY MECHANISMOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 5, 2026, 4:09 AM ET. BBL 1001060017.