22 floors · 50,150 sq ft · built 2012 · class H3 · owner of record: 32-34 West 29th Street Realty Llc
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 57 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 50,150 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 178 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 178 days | Annual filing |
| Facade inspection report (Cycle 10B) Applies Local Law 11 / FISP · Feb 21, 2026 to Feb 21, 2028 What this isBuildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 0, 7 or 8 are in sub-cycle 10B. DOB facade records for this building show $208,000 in late-filing or failure-to-file penalties. Agency page | Feb 21, 2028 in 474 days | No Cycle 10 report on record yet |
| Gas piping inspection (2029 cycle) Likely applies Local Law 152 · During 2029 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 5 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2029 in 1153 days | Next cycle year 2029 |
| Energy audit and retro-commissioning (2030) Likely applies Local Law 87 · Calendar year 2030 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 830). Agency page | Dec 31, 2030 in 1518 days | Next due 2030 |
| Annual boiler inspection (4 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-07-30 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Aug 20, 2026 | Elevators CLASS - 1 CLASS 1 C/U: 1. ALARM BELL AND EMERGENCY PHONE INOPERATIVE, FAILING REQUIRED EMERGENCY ALERTING AND TWO-WAY COMMUNICATION. AS PER ASME A17.1 2.27 AND 2.14; CONDITION MEETS CLASS 1 C/U CRITERIA PER 1 RCNY 102-01 #39201167X | Oct 29, 2026 PENDING | $1,250 |
| Aug 20, 2026 | Elevators CLASS - 2 CLASS 2: 1. EMERGENCY PHONE INOPERATIVE; RESPONDENT UNABLE TO HEAR OCCUPANT IN THE CAR, FAILING REQUIRED TWO-WAY COMMUNICATION. AS PER ASME A17.1 2.27. REMEDY: REPAIR EMERGENCY PHONE AND VERIFY CLEAR, RELIABLE #39201168H | Oct 29, 2026 PENDING | $625 |
| Aug 18, 2026 | Unknown CLASS - 1 ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON THE ROOF THE ELECTRICAL CLOSET AND THE ELEVATOR MACHINE ROOM IN THE BASEMENT THE STORAGE OF BUILDING SUPPLIES ICE MAKER, BU #39200880R | Oct 22, 2026 DEFAULT | $1,230 |
| Aug 18, 2026 | Unknown CLASS - 2 MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED ON ALL FLOORS THRU OUT BUILDING THAT THE ELECTRICAL CLOSETS AND MECHANICAL CLOSETS AND FIRE ALARM CLOSETS HAS NO LIGHTING FOR REPAIRS #39200881Z | Oct 22, 2026 DEFAULT | $830 |
| Aug 18, 2026 | Construction CLASS - 1 ATOI OBSERVED THROUGH OUT THE BUILDING OBSTRUCTED SPRINKLER HEADS AND PAINTED CAPS BY THE 04 ROOMS THE TELECOM/LINEN CLOSETS SPRINKLERS HAD THE PROTECTIVE CAPS ON STILL AND PAINTED ALSO STUFFED TO THE HEADS WIT #39200884Y | Oct 22, 2026 DEFAULT | $2,530 |
| Aug 18, 2026 | Construction CLASS - 1 ATOI OBSERVED PVC PIPING USED ON THE LAUNDRY ROOM WASHING MACHINE WASTE & ON THE SLOP SINK ALSO THE BASEMENT BATHROOM CONTRARY TO PC 1002.1 & PC 1101.10, REPAIR AND/REPLACE #39200885X | Oct 22, 2026 DEFAULT | $2,530 |
| Aug 11, 2025 | Elevators CLASS - 1 CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B. EIR@BUILDINGS.NYC.GOV. FOR A REINSPECTION. #39156629L | Oct 16, 2025 IN VIOLATION | $1,250 |
| Aug 7, 2024 | Unknown CLASS - 2 I OBSERVED IN THE ROOFTOP ELEVATOR MOTOR ROOM THE FUSES IN THE DISCONNECT RATED HIGHER THAN THE CONDUCTORS ALLOWABLE AMPACITY. I NOTED THE FUSING AT 150 AMPS FOR CONDUCTORS RATED AT 110 AMPS. CONDUCTORS AND FUS #39121166Y | Mar 2, 2026 IN VIOLATION | $2,400 |
| Aug 7, 2024 | Unknown CLASS - 2 I OBSERVED IN THE BASEMENT LAUNDRY ROOM A CONVENIENCE OUTLET NOT OF THE GFCI TYPE NOR GFCI PROTECTED AS REQUIRED WITHIN 6 FT OF A SINK., INSTALL GFC1 PROTECTION; PROVIDE GFCI PROTECTION. #39121165M | Sep 4, 2025 IN VIOLATION | $2,400 |
| Aug 7, 2024 | Unknown CLASS - 2 I OBSERVED IN THE ELEVATOR MOTOR ROOM THE USE OF AN EXTENSION CORD TO SUPPLY POWER TO THE A.C UNIT., ALSO NOTED ON THE FIRST FLOOR MEZZ. FROM THE BASEMENT TO SUPPLY POWER FOR A COFFEE MAKER. NO FLEXIBLE CORDS S #39121168H | Sep 4, 2025 IN VIOLATION | $800 |
| Issued | Violation | Status |
|---|---|---|
| Dec 1, 2024 | FAILURE TO POST ENERGY GRADE/SCORE FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3 #2400183 | DOB VIOLATION - ACTIVE |
| Jul 30, 2014 | ELEVATOR #9028/514990 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Dec 1, 2024 | Energy Grade - LL33 FTP-EN-EGRDEA | Active |
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Aug 20, 2026 | ECB | Elevators: CLASS 1 C/U: 1. ALARM BELL AND EMERGENCY PHONE INOPERATIVE, FAILING REQUIRED EMERGENCY ALERTING AND TWO-WAY COMMUNICATION. AS PER ASME A17.1 2.27 AND 2.14; CONDITION MEETS CLASS 1 C/U CRITERIA PER 1 RCNY 102-01 | Open |
| Aug 20, 2026 | ECB | Elevators: CLASS 2: 1. EMERGENCY PHONE INOPERATIVE; RESPONDENT UNABLE TO HEAR OCCUPANT IN THE CAR, FAILING REQUIRED TWO-WAY COMMUNICATION. AS PER ASME A17.1 2.27. REMEDY: REPAIR EMERGENCY PHONE AND VERIFY CLEAR, RELIABLE | Open |
| Aug 18, 2026 | ECB | Unknown: ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON THE ROOF THE ELECTRICAL CLOSET AND THE ELEVATOR MACHINE ROOM IN THE BASEMENT THE STORAGE OF BUILDING SUPPLIES ICE MAKER, BU | Open |
| Aug 18, 2026 | ECB | Unknown: MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED ON ALL FLOORS THRU OUT BUILDING THAT THE ELECTRICAL CLOSETS AND MECHANICAL CLOSETS AND FIRE ALARM CLOSETS HAS NO LIGHTING FOR REPAIRS | Open |
| Aug 18, 2026 | ECB | Construction: ATOI OBSERVED THROUGH OUT THE BUILDING OBSTRUCTED SPRINKLER HEADS AND PAINTED CAPS BY THE 04 ROOMS THE TELECOM/LINEN CLOSETS SPRINKLERS HAD THE PROTECTIVE CAPS ON STILL AND PAINTED ALSO STUFFED TO THE HEADS WIT | Open |
| Aug 18, 2026 | ECB | Construction: ATOI OBSERVED PVC PIPING USED ON THE LAUNDRY ROOM WASHING MACHINE WASTE & ON THE SLOP SINK ALSO THE BASEMENT BATHROOM CONTRARY TO PC 1002.1 & PC 1101.10, REPAIR AND/REPLACE | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Nov 4, 2026, 3:47 AM ET. BBL 1008300067.