Manhattan · Block 830 · Lot 67 · 10001

32 West 29 Street

22 floors · 50,150 sq ft · built 2012 · class H3 · owner of record: 32-34 West 29th Street Realty Llc

10open violations
$15,845ECB/OATH penalties owed
0HPD class C (immediately hazardous)
178dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 57 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 50,150 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 178 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 178 days
Annual filing
Facade inspection report (Cycle 10B) Applies
Local Law 11 / FISP · Feb 21, 2026 to Feb 21, 2028
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 0, 7 or 8 are in sub-cycle 10B. DOB facade records for this building show $208,000 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2028
in 474 days
No Cycle 10 report on record yet
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 5 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1153 days
Next cycle year 2029
Energy audit and retro-commissioning (2030) Likely applies
Local Law 87 · Calendar year 2030
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 830). Agency page

Dec 31, 2030
in 1518 days
Next due 2030
Annual boiler inspection (4 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-07-30 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (10) · $15,845 owed
IssuedViolationHearingBalance
Aug 20, 2026Elevators CLASS - 1
CLASS 1 C/U: 1. ALARM BELL AND EMERGENCY PHONE INOPERATIVE, FAILING REQUIRED EMERGENCY ALERTING AND TWO-WAY COMMUNICATION. AS PER ASME A17.1 2.27 AND 2.14; CONDITION MEETS CLASS 1 C/U CRITERIA PER 1 RCNY 102-01
#39201167X
Oct 29, 2026
PENDING
$1,250
Aug 20, 2026Elevators CLASS - 2
CLASS 2: 1. EMERGENCY PHONE INOPERATIVE; RESPONDENT UNABLE TO HEAR OCCUPANT IN THE CAR, FAILING REQUIRED TWO-WAY COMMUNICATION. AS PER ASME A17.1 2.27. REMEDY: REPAIR EMERGENCY PHONE AND VERIFY CLEAR, RELIABLE
#39201168H
Oct 29, 2026
PENDING
$625
Aug 18, 2026Unknown CLASS - 1
ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON THE ROOF THE ELECTRICAL CLOSET AND THE ELEVATOR MACHINE ROOM IN THE BASEMENT THE STORAGE OF BUILDING SUPPLIES ICE MAKER, BU
#39200880R
Oct 22, 2026
DEFAULT
$1,230
Aug 18, 2026Unknown CLASS - 2
MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED ON ALL FLOORS THRU OUT BUILDING THAT THE ELECTRICAL CLOSETS AND MECHANICAL CLOSETS AND FIRE ALARM CLOSETS HAS NO LIGHTING FOR REPAIRS
#39200881Z
Oct 22, 2026
DEFAULT
$830
Aug 18, 2026Construction CLASS - 1
ATOI OBSERVED THROUGH OUT THE BUILDING OBSTRUCTED SPRINKLER HEADS AND PAINTED CAPS BY THE 04 ROOMS THE TELECOM/LINEN CLOSETS SPRINKLERS HAD THE PROTECTIVE CAPS ON STILL AND PAINTED ALSO STUFFED TO THE HEADS WIT
#39200884Y
Oct 22, 2026
DEFAULT
$2,530
Aug 18, 2026Construction CLASS - 1
ATOI OBSERVED PVC PIPING USED ON THE LAUNDRY ROOM WASHING MACHINE WASTE & ON THE SLOP SINK ALSO THE BASEMENT BATHROOM CONTRARY TO PC 1002.1 & PC 1101.10, REPAIR AND/REPLACE
#39200885X
Oct 22, 2026
DEFAULT
$2,530
Aug 11, 2025Elevators CLASS - 1
CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B. EIR@BUILDINGS.NYC.GOV. FOR A REINSPECTION.
#39156629L
Oct 16, 2025
IN VIOLATION
$1,250
Aug 7, 2024Unknown CLASS - 2
I OBSERVED IN THE ROOFTOP ELEVATOR MOTOR ROOM THE FUSES IN THE DISCONNECT RATED HIGHER THAN THE CONDUCTORS ALLOWABLE AMPACITY. I NOTED THE FUSING AT 150 AMPS FOR CONDUCTORS RATED AT 110 AMPS. CONDUCTORS AND FUS
#39121166Y
Mar 2, 2026
IN VIOLATION
$2,400
Aug 7, 2024Unknown CLASS - 2
I OBSERVED IN THE BASEMENT LAUNDRY ROOM A CONVENIENCE OUTLET NOT OF THE GFCI TYPE NOR GFCI PROTECTED AS REQUIRED WITHIN 6 FT OF A SINK., INSTALL GFC1 PROTECTION; PROVIDE GFCI PROTECTION.
#39121165M
Sep 4, 2025
IN VIOLATION
$2,400
Aug 7, 2024Unknown CLASS - 2
I OBSERVED IN THE ELEVATOR MOTOR ROOM THE USE OF AN EXTENSION CORD TO SUPPLY POWER TO THE A.C UNIT., ALSO NOTED ON THE FIRST FLOOR MEZZ. FROM THE BASEMENT TO SUPPLY POWER FOR A COFFEE MAKER. NO FLEXIBLE CORDS S
#39121168H
Sep 4, 2025
IN VIOLATION
$800
DOB (2)
IssuedViolationStatus
Dec 1, 2024FAILURE TO POST ENERGY GRADE/SCORE
FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
#2400183
DOB VIOLATION - ACTIVE
Jul 30, 2014ELEVATOR

#9028/514990
DOB VIOLATION - ACTIVE
DOB NOW Safety (1)
IssuedViolationStatus
Dec 1, 2024Energy Grade - LL33 FTP-EN-EGRDEA
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Aug 20, 2026ECBElevators: CLASS 1 C/U: 1. ALARM BELL AND EMERGENCY PHONE INOPERATIVE, FAILING REQUIRED EMERGENCY ALERTING AND TWO-WAY COMMUNICATION. AS PER ASME A17.1 2.27 AND 2.14; CONDITION MEETS CLASS 1 C/U CRITERIA PER 1 RCNY 102-01Open
Aug 20, 2026ECBElevators: CLASS 2: 1. EMERGENCY PHONE INOPERATIVE; RESPONDENT UNABLE TO HEAR OCCUPANT IN THE CAR, FAILING REQUIRED TWO-WAY COMMUNICATION. AS PER ASME A17.1 2.27. REMEDY: REPAIR EMERGENCY PHONE AND VERIFY CLEAR, RELIABLEOpen
Aug 18, 2026ECBUnknown: ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON THE ROOF THE ELECTRICAL CLOSET AND THE ELEVATOR MACHINE ROOM IN THE BASEMENT THE STORAGE OF BUILDING SUPPLIES ICE MAKER, BUOpen
Aug 18, 2026ECBUnknown: MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED ON ALL FLOORS THRU OUT BUILDING THAT THE ELECTRICAL CLOSETS AND MECHANICAL CLOSETS AND FIRE ALARM CLOSETS HAS NO LIGHTING FOR REPAIRSOpen
Aug 18, 2026ECBConstruction: ATOI OBSERVED THROUGH OUT THE BUILDING OBSTRUCTED SPRINKLER HEADS AND PAINTED CAPS BY THE 04 ROOMS THE TELECOM/LINEN CLOSETS SPRINKLERS HAD THE PROTECTIVE CAPS ON STILL AND PAINTED ALSO STUFFED TO THE HEADS WITOpen
Aug 18, 2026ECBConstruction: ATOI OBSERVED PVC PIPING USED ON THE LAUNDRY ROOM WASHING MACHINE WASTE & ON THE SLOP SINK ALSO THE BASEMENT BATHROOM CONTRARY TO PC 1002.1 & PC 1101.10, REPAIR AND/REPLACEOpen