Manhattan · Block 1253 · Lot 38 · 10025

316 West 95 Street

7 floors · 45,150 sq ft · built 1903 · class H6 · owner of record: Rb Estates Llc

12open violations
$21,218ECB/OATH penalties owed
0HPD class C (immediately hazardous)
46dto Annual boiler inspection (2 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 46 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-11-03 (Accepted). Agency page

Dec 31, 2026
in 46 days
1 of 2 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 45,150 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 167 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 167 days
Annual filing
Facade inspection report (Cycle 10C) Applies
Local Law 11 / FISP · Feb 21, 2027 to Feb 21, 2029
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 1, 2 or 3 are in sub-cycle 10C. DOB facade records for this building show $527,500 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2029
in 829 days
Filing window not open yet
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 7 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1142 days
Next cycle year 2029

Open violations

ECB / OATH (12) · $21,218 owed
IssuedViolationHearingBalance
Sep 28, 2026Construction CLASS - 2
AT THE TIME OF INSPECTION OBSERVED LEVEL 1 RUST ON THE GAS PIPING LEADING TO THE METERS IN THE GAS METER ROOM. CONTRARY TO . NYC FUEL GAS CODE 401.1 - GOVERNS THE INSTALLATION, MAINTENANCE, AND REPAIR OF FUEL-G
#39205781Y
Dec 3, 2026
PENDING
$1,250
Sep 28, 2026Unknown CLASS - 2
ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE BASEMENT ONE 30 AMP HUNG ELECTRICAL HEATER INSTALLED WITH NEW ARMORED CABLE TO PANEL BOX. CHECKED BIS / DOB NOW NO PERMIT ON FILE ALL WORK MUST BE FILED BY A LI
#39205791H
Dec 3, 2026
PENDING
$1,250
Sep 28, 2026Elevators CLASS - 1
CLASS 1 C/U: DOOR ZONE RESTRICTOR INOPERATIVE, AS PER ASME A17.1 2.12.5. PHASE II "HOLD" POSITION INOPERATIVE, AS PER 2.27.3.3.2. REMEDY: CORRECT DEFECTS AND EMAIL ELEVATOR DIVISION AT EIR@BUILDINGS.NYC.GOV TO
#39205793L
Dec 3, 2026
PENDING
$1,250
Sep 28, 2026Unknown CLASS - 2
FAILURE TO PROTECT CONDUCTOR(S) AGAINST OVERCURRENT. OBSERVED IN THE MAIN ELECTRICAL RM THE MHSS OVERCURRENT PROTECTION ON THE RED PHASE IS INCORRECT 150 AMPS, ON THE ROOF THE ELEVATOR SERVICE SW OVERCURRENT IS
#39205792J
Dec 3, 2026
PENDING
$2,400
Oct 9, 2025Boilers CLASS - 2
WEIL MCLAIN MODEL-1288 BOILER. NO REGISTERED. REGISTERED BOILER AND SUBMIT A CERTIFICATE OF CORRECTION.
#39163143R
Jul 23, 2026
IN VIOLATION
$1,250
Oct 9, 2025Elevators CLASS - 2
CLASS 2 ITEMS: HALL BUTTONS KEEP CANCELING CALLS, REPAIR. ALARM TOO LOW, REPAIR. EMERGENCY PHONE INOPERATIVE, PROVIDE 2 WAY COMMUNICATION. FIRE EXTINGUISHER EXPIRED, PROVIDE SERVICE AND UPDATE THE TAG. MISSING
#39163243Y
Jul 23, 2026
IN VIOLATION
$625
Oct 9, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED PASSAGEWAY OBSTRUCTED AT MAIN ENTRANCE. LOCATED ON 1ST FLOOR MAIN HALLWAY. SECURITY DESK, 3 TABLES AND VENDING MACHINE.B POTENTIAL FIRE HAZARD., R
#39163217K
Jul 23, 2026
IN VIOLATION
$1,250
Dec 4, 2023Construction CLASS - 1
OBSERVED EXCESSIVE DUST IN COMMON ARAES 2-7 ON STAIRS AND STAIR LANDINGS., MAINTAIN ADEQUATE CONSTRUCTION HOUSEKEEPING
#39100650N
Aug 1, 2024
IN VIOLATION
$1,250
Oct 31, 2023Cranes and Derricks CLASS - 1
AT TIME OF INSPECTION, WORK IN PROGRESS WHILE GENERAL LIABILITY INSURANCE POLICY #600GL001854905 EXPIRED - POLICY EXPIRED 10-28-2023, OBTAIN BOND AND/OR INSURANCE AND FILE WITH THE DEPARTMENT; STOP ALL WORK IMM
#39098351N
Aug 14, 2025
IN VIOLATION
$5,000
Oct 31, 2023Construction CLASS - 1
AT TIME OF INSPECTION, WORK IN PROGRESS AT SITE UNDER EXPIRED ALT 1 PERMIT #123256877 - EXPIRED 10-28-2023, OBTAIN PERMIT; STOP ALL WORK IMMEDIATELY - RENEW PERMIT
#39098352P
Aug 14, 2025
IN VIOLATION
$2,500
Oct 19, 2022Local Law CLASS - 2
FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8C REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#804064.AGG1 PRIOR NOV#37018421Y UNDER 2
#37022983H
Mar 16, 2023
IN VIOLATION
$3,125
Feb 13, 2020Local Law CLASS - 2
FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8C REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#804064. REMEDY: SUBMIT ACCEPTABLE REQUIRE
#37018421Y
Aug 17, 2020
IN VIOLATION
$68
DOB (5)
IssuedViolationStatus
Feb 22, 2024NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9C TECHNICAL REPORT BY 2/21/2024
#00227
DOB VIOLATION - ACTIVE
Nov 30, 2007LOCAL LAW 11/98 - FACADE

#NRF43247
DOB VIOLATION - ACTIVE
Jul 25, 2007CONSTRUCTION

#MTF01EM
VIOLATION WORK WITHOUT PERMIT - ACTIVE
Jul 25, 2007CONSTRUCTION

#MTF02EM
DOB VIOLATION - ACTIVE
Jul 25, 2007ZONING

#MTF03EM
DOB VIOLATION - ACTIVE
DOB NOW Safety (3)
IssuedViolationStatus
Feb 22, 2024Facades FISPNRF
FAILED TO FILE FISP CYCLE 9C TECHNICAL REPORT BY 2/21/2024
Active
Apr 30, 2019Facades FISPNRF
FAILED TO FILE FISP CYCLE 8C TECHNICAL REPORT BY 02/21/2019
Active
Nov 30, 2007Facades LL1198
CYCLE 6 NO REPORT FILED
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Sep 28, 2026ECBConstruction: AT THE TIME OF INSPECTION OBSERVED LEVEL 1 RUST ON THE GAS PIPING LEADING TO THE METERS IN THE GAS METER ROOM. CONTRARY TO . NYC FUEL GAS CODE 401.1 - GOVERNS THE INSTALLATION, MAINTENANCE, AND REPAIR OF FUEL-GOpen
Sep 28, 2026ECBUnknown: ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE BASEMENT ONE 30 AMP HUNG ELECTRICAL HEATER INSTALLED WITH NEW ARMORED CABLE TO PANEL BOX. CHECKED BIS / DOB NOW NO PERMIT ON FILE ALL WORK MUST BE FILED BY A LIOpen
Sep 28, 2026ECBElevators: CLASS 1 C/U: DOOR ZONE RESTRICTOR INOPERATIVE, AS PER ASME A17.1 2.12.5. PHASE II "HOLD" POSITION INOPERATIVE, AS PER 2.27.3.3.2. REMEDY: CORRECT DEFECTS AND EMAIL ELEVATOR DIVISION AT EIR@BUILDINGS.NYC.GOV TOOpen
Sep 28, 2026ECBUnknown: FAILURE TO PROTECT CONDUCTOR(S) AGAINST OVERCURRENT. OBSERVED IN THE MAIN ELECTRICAL RM THE MHSS OVERCURRENT PROTECTION ON THE RED PHASE IS INCORRECT 150 AMPS, ON THE ROOF THE ELEVATOR SERVICE SW OVERCURRENT ISOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 15, 2026, 10:36 AM ET. BBL 1012530038.