5 floors · 36,808 sq ft · built 2007 · class H3 · owner of record: 300 Wild Llc
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 46 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 36,808 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 167 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 167 days | Annual filing |
| Gas piping inspection (2029 cycle) Likely applies Local Law 152 · During 2029 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 2 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2029 in 1142 days | Next cycle year 2029 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Aug 25, 2026 | Elevators CLASS - 2 REPLACE OR SECURE GIBS WHERE NEEDED (2.11.11.5.7.)> MAINTNENANCE LOG NOT UP TO DATE (8.6.1.4.). OIL AND WATER MIXTURE IN PIT (2.2.2.4.). CAB HANDRAIL MISSING. #39201734N | Dec 16, 2026 PENDING | $625 |
| Apr 13, 2026 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS. NO CERTIFICATE OF CORRECTION ON FILE FOR VIO#39122120N AS OF 4/13/2026., FILE A CERTIFICATE #39184311J | Jun 15, 2027 DEFAULT | $6,250 |
| Apr 13, 2026 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS. NO CERTIFICATE OF CORRECTION ON FILE FOR VIO#39122119X AS OF 4/13/2026., FILE A CERTIFICATE #39184318M | Jun 15, 2027 DEFAULT | $6,250 |
| Apr 13, 2026 | Construction CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER. FOR WORK WITHOUT A PERMIT FOR VIO#39143435K NO PERMIT ON FILE AS OF 4/13/2026., COMPLY WITH COMMISSIONER'S ORDER #39184300Y | Jun 15, 2027 DEFAULT | $12,500 |
| Apr 13, 2026 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS. NO CERTIFICATE OF CORRECTION ON FILE FOR VIO#39122117M AS OF 4/13/2026., FILE A CERTIFICATE #39184307R | Jun 15, 2027 DEFAULT | $6,250 |
| Apr 13, 2026 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS. NO CERTIFICATE OF CORRECTION ON FILE FOR VIO#39122098X AS OF 4/13/2026., FILE A CERTIFICATE #39184304L | Jun 15, 2027 DEFAULT | $6,250 |
| May 22, 2025 | Construction CLASS - 2 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS. AT TIME OF INSPECTION, OBSERVED THE 5TH FLOOR DO NOT CONFORM TO NB JOB APP #500842109. NOTED 19 ADDITIONAL GUEST ROOMS ON THE #39151648Y | Mar 8, 2027 PENDING | $1,280 |
| Apr 1, 2025 | Construction CLASS - 2 NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 VIOLATION 39122117M ISSUED FOR GAS CONNECTION TO HVAC SYSTEM NOT INSTALLED AS PER CODE. GAS CONNECTION HAS BEEN FIXED WITHOUT PERMIT., FILE A CERTIFICATE OF CORR #39143432P | Jun 18, 2025 IN VIOLATION | $0 |
| Apr 1, 2025 | Construction CLASS - 2 NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 ELECTRICAL VIOLATION 39122115Z ISSUED FOR ELECTRICAL WIRING NOT INSTALLED AS PER CODE. WIRING HAS BEEN FIXED UNDER APPROVED JOB #S01115437., FILE A CERTIFICATE O #39143434Z | Jun 18, 2025 IN VIOLATION | $0 |
| Apr 1, 2025 | Construction CLASS - 2 NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 VIOLATION 39122098X ISSUED FOR MISSING FIRE STOPPING THROUGHOUT PUBLIC CORRIDORS. SUMMONS FOUND IN VIO, CIVIL PENALTY UNPAID., FILE A CERTIFICATE OF CORRECTION #39143433R | Jun 18, 2025 IN VIOLATION | $0 |
| Apr 1, 2025 | Construction CLASS - 1 WORK WITHOUT A PERMIT; VIOLATION #39122117M ISSUED FOR FLEX GAS LINE INSTALLED TO SUPPLY GAS TO HVAC SYSTEM ON ROOF. FLEX LINE HAS SINCE BEEN REMOVED AND REPLACED WITH APPROPRIATE GAS LINES. NO PERMITS ON FILE #39143435K | Jun 18, 2025 IN VIOLATION | $0 |
| Apr 1, 2025 | Construction CLASS - 2 NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 ELECTRICAL VIOLATION 39122119X ISSUED FOR UNAPPROVED USE OF ELECTRICAL EQUIPMENT. CONDITIONS HAVE BEEN FIXED UNDER APPROVED JOB #S01115437, FILE A CERTIFICATE OF #39143436M | Jun 18, 2025 IN VIOLATION | $0 |
| Apr 1, 2025 | Construction CLASS - 2 NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 ELECTRICAL VIOLATION 39122120N ISSUED FOR UNPERMITTED WIRING DEVICES, CIRCUIT BREAKERS INSTALLED TO VARIOUS RECEPTACLES WITHOUT PERMITS. CONDITIONS REPAIRED UNDE #39143437Y | Jun 18, 2025 IN VIOLATION | $0 |
| Sep 6, 2024 | Construction CLASS - 2 OBSERVED GAS PIPE TO HVAC UNIT ON ROOF NOT BEING SUPPORTED CORRECTLY. AS PER 308.3 OF THE PLUMBING CODE AND ANCHORS SHALL BE ATTACHED TO THE BUILDING CONSTRUCTION IN AN APPROVED MANNER., REPAIR AND/OR REPLACE #39124138K | Nov 20, 2024 STIPULATION/IN-VIO | $310 |
| Aug 15, 2024 | Unknown CLASS - 1 I OBSERVED IN THE ELEVATOR MOTOR ROOM THE UNPERMITTED OF A FLEXIBLE CORD AS PERMANENT WIRING PLUGGED IN TO A RECEPTACLE OUTLET AND TERMINATED IN A DISCONNECT SWITCH. THIS AN IMMEDIATE SHOCK AND FIRE HAZARD. PHO #39122115Z | Mar 19, 2025 IN VIOLATION | $1,600 |
| Aug 15, 2024 | Construction CLASS - 1 I OBSERVED ON THE ROOF THE GAS SERVICE SUPPLIED TO THE HVAC UNIT CONNECTED WITH FLEX. AS PER THE FGC 411.1THE CONNECTION SHALL BE OF RIGID PIPING AND FITTINGS ONLY, SEMI RIGID (FLEXIBLE PIPING IS NOT PERMITTED) #39122117M | Mar 19, 2025 IN VIOLATION | $2,500 |
| Aug 15, 2024 | Unknown CLASS - 1 I OBSERVED IN THE 5TH AND 4TH FLOOR MECHANICAL ROOM, AND THE CELLAR PANTRY ROOM, DEFECTIVE GFCI OUTLETS IN USE. THIS IS AN IMMEDIATE SHOCK AND SAFETY HAZARD., COMPLY WITH EC; PROVIDE GFCI PROTECTION AS REQUIRED #39122119X | Mar 19, 2025 IN VIOLATION | $0 |
| Aug 15, 2024 | Unknown CLASS - 1 I OBSERVED IN THE WATER METER ROOM THE IMPROPER INSTALLATION OF THE WATER METER JUMPER, THE CONDUCTOR WAS WRAPPED AROUND THE VARIOUS COMPONENTS OF THE WATER MAIN. THE CONDUCTOR SHALL BE INSTALLED SO THAT IT PRO #39122114R | Mar 19, 2025 IN VIOLATION | $4,800 |
| Aug 15, 2024 | Unknown CLASS - 1 I OBSERVED IN THE CELLAR ELECTRICAL ROOM THE INSTALLATION OF BRANCH CIRCUIT WIRING, DEVICES, CIRCUIT BREAKERS TO VARIOUS RECEPTACLES, AND LAUNDRY EQUIPMENT. NO PERMIT IN DOB RECORDS COVERS THIS WORK., OBTAIN PE #39122120N | Mar 19, 2025 IN VIOLATION | $0 |
| Aug 15, 2024 | Construction CLASS - 1 MULTIPLE HOLES, LARGE SECTION OF FIRE-STOP REMOVED FROM CEILINGS AND WALLS, AND ILLEGAL PLASTIC ACCESS PANELS INSTALLED IN CEILING CORRIDORS AND ALL MECHANICAL ROOMS LOCATED THROUGHOUT BUILDING. REMOVING FIRE-S #39122098X | Mar 19, 2025 IN VIOLATION | $2,500 |
| Issued | Violation | Status |
|---|---|---|
| Feb 21, 2012 | ELEVATOR #9027/417104 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Oct 29, 2026 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction | Active |
| Mar 17, 2026 | AEUHAZ FTC-AEU-HAZ | Active |
| Mar 17, 2026 | AEUHAZ FTC-AEU-HAZ | Active |
| Mar 17, 2026 | AEUHAZ FTC-AEU-HAZ | Active |
| Mar 17, 2026 | AEUHAZ FTC-AEU-HAZ | Active |
| Mar 17, 2026 | AEUHAZ FTC-AEU-HAZ | Active |
| Mar 17, 2026 | AEUHAZ FTC-AEU-HAZ | Active |
| Oct 10, 2025 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction | Active |
| Oct 10, 2025 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction | Active |
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Oct 29, 2026 | DOB Safety | Elevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction | Open |
| Aug 25, 2026 | ECB | Elevators: REPLACE OR SECURE GIBS WHERE NEEDED (2.11.11.5.7.)> MAINTNENANCE LOG NOT UP TO DATE (8.6.1.4.). OIL AND WATER MIXTURE IN PIT (2.2.2.4.). CAB HANDRAIL MISSING. | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)