Manhattan · Block 1275 · Lot 50 · 10017

295 Madison Avenue

45 floors · 301,128 sq ft · built 1929 · class O4 · owner of record: 295 Madison Property Owner Llc

19open violations
$30,625ECB/OATH penalties owed
0HPD class C (immediately hazardous)
112dto Facade inspection report (Cycle 10A)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 60 days
Keep the report on file (not filed with DOB)
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $121,200 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2027
in 112 days
No Cycle 10 report on record yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 301,128 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 181 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 181 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 5 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1156 days
Next cycle year 2029
Energy audit and retro-commissioning (2035) Likely applies
Local Law 87 · Calendar year 2035
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 1275). Agency page

Dec 31, 2035
in 3347 days
Next due 2035

Open violations

ECB / OATH (9) · $30,625 owed
IssuedViolationHearingBalance
Jun 17, 2024Construction CLASS - 2
A. C. 27-929.1, FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OF AUTOMATIC SPRINKLERS AND FILE A FINAL SPRINKLER REPORT PREPARED BY A REGISTERED DESIGN PROFESSIONAL IN AN OFFICE BUILDING 100 FEET OR MOR
#37028854Z
Aug 21, 2025
IN VIOLATION
$6,250
Mar 30, 2023Construction CLASS - 1
AT TIME OF INSPECTION I OBSERVED SIDEWALK SHED INSTALLED ON EXPOSURE #1 AND 2 WITH INOPERABLE LIGHT BULBS UNDERSIDE THE SHED TO BRING ILLUMINATION FAILURE TO PROVIDE LIGHTING CREATES UNSAFE AND MUGGING CONDITIO
#39514803P
Jan 5, 2024
IN VIOLATION
$0
Feb 28, 2023Construction CLASS - 2
A.C.27-929.1,FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OF AUTOMATIC SPRINKLERS AND FILE A FINAL SPRINKLER REPORT PREPARED BY A REGISTERED DESIGN PROFESSIONAL IN AN OFFICE BUILDING 100' OR MORE IN HE
#37025444M
Feb 8, 2024
IN VIOLATION
$6,250
Oct 22, 2022Construction CLASS - 1
FAILURE TO PROVIDE ADEQUATE SAFETY MEASURE.AT TIME OF INSPECTION ON 10/22/2022,OBSERVED NO SIDEWALK SHED OR SAFETY MEASURES IN PLACE FOR DOCUMENTED UNSAFE FACADE FILED BY QEWI(RA/PE)FILING UNSAFE#904254-9A-001
#35669167Y
Sep 28, 2023
IN VIOLATION
$10,000
Nov 1, 2021Construction CLASS - 2
27-929.1 AC27-929.1,FAILURE TO COMPLETE INSTALLATION OF FULL SYSTEM OFAUTOMATIC SPRINKLERS&FILE FINAL SPRINKLER REPORT PREPARED BY REGISTERED DESIGN PROFESSIONAL IN OFFICE BLDG 100' OR MORE IN HT IN EXISTENCE O
#37022508Z
Mar 17, 2022
STIPULATION/IN-VIO
$3,125
Dec 14, 2020Elevators CLASS - 2
CLASS 2 VIOLATION ISSUED, 1 NO ACCESS TO OVERHEAD 2 MACHINE ROOM 3 PIT OF HOIST WAY,REMEDY; PROVIDE KEYS FOR ACCESS SO A COMPLETE INSPECTION CAN BE PERFORMED ON DISMANTLED DEVICE, AS PER ASME A17.1 SECTION 8.1.
#39033432H
Jun 3, 2021
IN VIOLATION
$625
Jul 22, 2020Construction CLASS - 2
ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1 - 28-118.3.2. OBSERVED GYM ON 1ST FLOOR AND CELLAR NO C/O ISSUED FOR ALT 1 JOB #123095907 AND BUILDING FULLY OCCUPIED
#39025753Z
Nov 5, 2020
IN VIOLATION
$1,250
Jul 13, 2020Construction CLASS - 2
AC 27-929 FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OF AUTOMATIC SPRINLERS AND FILE A FINAL SPRINKLER REPORT PREPARED BY A REGISTERED DESIGN PROFESSIONAL BY JULY 1, 2019 IN AN OFFICE BUILDING 100 FE
#37019854Y
Jul 1, 2021
IN VIOLATION
$3,125
Nov 15, 2019Construction CLASS - 2
SEC. 27-929.1 FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OFAUTOMATIC SPRINKLERS & FILE A FINAL SPRINKLER REPORT PREPARED BY A REGISTERED DESIGN PROFESSIONAL BY 7/1/19,IN AN OFFICE BLDG 100 FEET OR MO
#37016538Z
Feb 20, 2020
STIPULATION/IN-VIO
$0
DOB (7)
IssuedViolationStatus
Mar 10, 2026CONSTRUCTION
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED MULTIPLE DEFECTS. AT EXPOSURE 1 OBSERVED SPALLING ON DECORATIVE STONES ERODING MORTAR JOINTS MULTIPLE LOCATIONS & DAMAGED MORTAR JOINTS AT MULTIPLE LOCATIONS. REMEDY: REPAIR AND/OR REPLACE DEFECTIVE CONDITIONS
#SR0501NS
DOB VIOLATION - ACTIVE
Dec 1, 2024FAILURE TO POST ENERGY GRADE/SCORE
FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
#2400329
DOB VIOLATION - ACTIVE
Jun 13, 2023HAZARDOUS CONDITION (FACADE)
CYCLE 9A UNSAFE REPORT FILED
#911161
DOB VIOLATION - ACTIVE
Sep 3, 2019SPRINKLER
FAILED TO FILE FINAL SPRINKLER REPORT BY JULY 1, 2019
#NRF00493
DOB VIOLATION - ACTIVE
Jun 21, 2011ELEVATOR

#9027/388882
DOB VIOLATION - ACTIVE
Aug 19, 2009ELEVATOR

#9011/311398
DOB VIOLATION - ACTIVE
Mar 23, 2000ELEVATOR

#9011/120061
DOB VIOLATION - ACTIVE
DOB NOW Safety (4)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Dec 1, 2024Energy Grade - LL33 FTP-EN-EGRDEA
Active
Jun 13, 2023Facades FISPHAZ
CYCLE 9A UNSAFE REPORT FILED
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen