3 floors · 41,446 sq ft · built 1954 · class N2 · owner of record: Nyc Department Of Homeless Services
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 62 days | Keep the report on file (not filed with DOB) |
| Annual boiler inspection (2 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2025-07-01 (Accepted). Agency page | Dec 31, 2026 in 62 days | 2 of 2 without an accepted 2026 report yet |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 41,446 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 183 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 183 days | Annual filing |
| Gas piping inspection (2028 cycle) Likely applies Local Law 152 · During 2028 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 10 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2028 in 793 days | Next cycle year 2028 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Sep 30, 2026 | Boilers CLASS - 2 FOUND FITZGIBBONS OIL FIRED BOILER MODEL#99042 WITH DEFECTIVE SAFETY RELIEF VALE(LEAKING). SECONDARY BOILER ROOM DOOR NOT SELF CLOSING. POOR LIGHTING IN BOILER ROOM. #39206155L | Oct 28, 2026 PENDING | $1,250 |
| Sep 30, 2026 | Boilers CLASS - 2 FOUND FITZGIBBON OIL FIRED BOILER MODEL#99042 WITH CORRODED AND LEAKING BOILER BASE, SAFETY RELIEF VALVES DEFECTIVE , LEAKING AND LABELS NOT LEGIBLE, EXPOSED WIRES AT CONTROLS, OIL PUMP SET NOT TO RUN CONSTANT. #39206150M | Oct 28, 2026 PENDING | $1,250 |
| Nov 19, 2024 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED CEILING CHIPPED AND FALLING OFF CEILING. THIS IS A OVERHEAD HAZARD. LOCATED IN AUDITORIUM/ LUNCHROOM., REPAIR AND/REPLACE #39130734H | Nov 21, 2024 POP/IN-VIO | $0 |
| Jun 3, 2024 | Unknown CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB# 39077703P ISSUED ON 01/11/2023 AND FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01 FOR FAILURE TO GROUND ELEC #39115811R | Jul 27, 2024 POP/IN-VIO | $0 |
| Jun 3, 2024 | Unknown CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE SERVICE DISCONNECT SWITCH IMPROPER FUSING. THE SWITCH HAS (2) 300 AMP FUSES AND (1) 400 AMP FUSE. ALL FUSES IN A DISCONNECT SHALL BE COORDINATED., PROVIDE PROTECTION A #39115807Y | Jul 27, 2024 POP/IN-VIO | $0 |
| Jun 3, 2024 | Construction CLASS - 1 FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB# 39077701L ISSUED ON 01/11/2023 FOR IMPROPER FUSING OF ELECTRICAL CONDUCTORS AND FILE A CERTIFICATE OF CORRECTION AS PURSUANT TO 28-201.1 AND 1RCNY #39115806M | Aug 2, 2024 POP/IN-VIO | $0 |
| Mar 7, 2024 | Construction CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB # 39077703P ISSUED ON 01/11/2023 AND FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURE TO SAFEGUARD PER #39108326H | May 30, 2024 POP/IN-VIO | $0 |
| Mar 7, 2024 | Construction CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB # 39077698J ISSUED ON 01/11/2023 AND FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURE TO SAFEGUARD PER #39108246H | May 30, 2024 POP/IN-VIO | $0 |
| Mar 7, 2024 | Construction CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB # 39077701L ISSUED ON 01/11/2023 AND FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURE TO SAFEGUARD PER #39108245X | May 30, 2024 POP/IN-VIO | $0 |
| Dec 20, 2023 | Construction CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39077701L ISSUED ON 08/03/23 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLY #39101876K | Jan 2, 2024 POP/IN-VIO | $0 |
| Dec 20, 2023 | Construction CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39077698J ISSUED ON 01/11/23 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLY #39101888H | Jan 2, 2024 POP/IN-VIO | $0 |
| Dec 20, 2023 | Construction CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39077703P ISSUED ON 01/13/23 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLY #39101874R | Jan 2, 2024 POP/IN-VIO | $0 |
| Oct 25, 2023 | Unknown CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF THE GROUND BAR FOR THE SERVICE DISCONNECTS WITH NO MAIN CONDUCTOR FROM THE WATER MAIN. A SUPPLEMENTAL GROUND ROD IS PROVIDING THE PRIMARY GROUND., PROV #39098023Y | Nov 15, 2023 POP/IN-VIO | $0 |
| Oct 25, 2023 | Unknown CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF (2) 300 AMP FUSES AND (1) 400 AMP FUSE. THIS IS NOT PERMITTED ALL FUSING OF CONDUCTORS SHALL BE THE SAME RATING. PHOTOS TAKEN., PROVIDE PROTECTION AGAI #39098022M | Nov 15, 2023 POP/IN-VIO | $0 |
| Jan 13, 2023 | Unknown CLASS - 1 I OBSERVED IN THE ELECTRICAL SERVICE ROOM THE INSTALLATION OF A GROUND BAR FOR THE SERVICE DISCONNECTS WITH NO MAIN GROUND ELECTRODE CONDUCTOR FROM THE WATER MAIN. A SUPPLEMENTAL GROUND ROD IS SUPPLYING THE PRI #39077703P | Jan 25, 2023 POP/IN-VIO | $0 |
| Jan 11, 2023 | Construction CLASS - 2 OBSERVED: FIRE PROOF SELF-CLOSING DOOR AT SECOND FL, SMOKE DOOR NEAR RM 213 & FIRST FL, EXIT DOORS # 3,4,2, LIBRARY (OBSTRUCTION EXIT WAY) & CAFETERIA (3 DOORS) ALSO, CAFETERIA/ EXIT DOOR ARE MISSING PUSH BARS. #39077513Y | Jan 25, 2023 POP/IN-VIO | $0 |
| Jan 11, 2023 | Unknown CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF (2) 300 AMP FUSES AND (1) 400 AMP FUSES. THIS NOT PERMITTED ALL FUSING OF CONDUCTORS ARE TO BE OF THE SAME RATING. PHOTOS TAKEN., PROVIDE PROTECTION AG #39077701L | Jan 25, 2023 POP/IN-VIO | $0 |
| Jan 11, 2023 | Unknown CLASS - 2 I OBSERVED IN THE MAIN DISCONNECT SWITCHES THE ELECTRICAL ROOM THE IMPROPER TERMINATION OF THE CONDUCTORS .FOR THE TERMINATION OF TWO CONDUCTORS UNDER A SINGLE LUG IT SHALL BE OF THE TYPE DESIGNED FOR SUCH INST #39077700J | Jan 25, 2023 POP/IN-VIO | $0 |
| Jan 11, 2023 | Unknown CLASS - 1 I OBSERVED ON ROOFTOP A THE USE OF FLEXIBLE RUBBER CORD THROUGH THE CONCRETE WALL AND IMPROPERLY SPLICED WITH EXPOSED AND ENERGIZED WIRING SUPPLYING POWER TO THE DOWN LIGHT. AS EC 400.8 FLEXIBLE CORDS ARE NOT P #39077698J | Jan 25, 2023 POP/IN-VIO | $0 |
| Jan 11, 2023 | Unknown CLASS - 2 I OBSERVED ON THE ROOFTOP "A" SIDE 8(#S 5-6-8-9-10-11-13-14) DEFECTIVE/INOPERABLE EXHAUST FANS. PHOTOS TAKEN, COMPLY WITH EC; REPAIR/OR REPLACE DEFECTIVE EQUIPMENT. #39077699L | Jan 25, 2023 POP/IN-VIO | $0 |
| May 13, 2022 | Boilers CLASS - 2 REPAIR CLAMP USED TO STOP LEAK-CORROSION ON VALVE BOILER NO. 2-PIPING UNCAPPED AT MIXING VALVE AND PIPING CAPPED W/WASTE FITTING-ELECTRICAL CONNECTION BOX FOR FIRE SWITCH W/O A COVER-NO SHUT-OFF VALVE FUEL OIL #39062066J | Jun 8, 2022 POP/IN-VIO | $0 |
| Dec 7, 2021 | Construction CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM, AN EXCESSIVE AMOUNT OF WATER LEAKING FROM ABOVE ONTO THE MAIN ELECTRICAL EQUIPMENT. EQUIPMENT IS CURRENTLY BEING DETERIORATED, AND THE WATER POOLING CAN LEAD TO A SHOCK H #39052532Z | Dec 13, 2021 POP/IN-VIO | $0 |
| Sep 22, 2021 | Boilers CLASS - 2 FOUND FITZGIBBON BOILER ACTIVE WITH DEFECTS. COMBUSTION AIR FAN SAIL SWITCH DEFECTIVE. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION. #39047921X | Oct 15, 2021 POP/IN-VIO | $0 |
| Aug 27, 2021 | Construction CLASS - 1 AN UNLAWFUL ACT.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS#35253004K ISSUED ON 4/12/2017,FORFAILURE TO GROUND THE ELECTRICAL SERVICE IN THE BASEMENT.ALSO SUMMONS# #35583956J | Nov 18, 2021 POP/IN-VIO | $0 |
| Sep 23, 2019 | Construction CLASS - 2 NOTED: EXIT DOORS AT 3RD AND 2ND FLOOR STAIRWAY A, AND 1ST FLOOR STAIRWAY B, DO NOT SELF CLOSE, DOORS ARE RUBBING ON THE FLOOR. , REPAIR/REPLACE DOOR #39009882P | Oct 4, 2019 POP/IN-VIO | $0 |
| Sep 23, 2019 | Unknown CLASS - 2 I OBSERVED IN THE ELECTRICAL EQUIPMENT ROOM THE INSTALLATION OF TWO SERVICE SWITCHES WITH CONDUITS AND WIRING TO SUPPLY POWER TO THE KITCHEN AND A SECOND UNSPECIFIED LOCATION. THE CONNECTIONS TO PROVIDE POWER A #39009890P | Oct 4, 2019 POP/IN-VIO | $0 |
| Sep 23, 2019 | Unknown CLASS - 1 I OBSERVED IN THE ELECTRICAL ROOM, SERVICE SWITCHES WITH IMPROPER FUSING , , PROVIDE PROTECTION AGAINST OVERCURRENT; INSTALL FUSES UNIFORMLY. #39009891R | Oct 4, 2019 POP/IN-VIO | $0 |
| Sep 23, 2019 | Construction CLASS - 2 NOTED: OPERATING A PLACE OF ASSEMBLY AT 1ST FLOOR CAFETERIA/GYM, WITHOUT A VALID CERTIFICATE TO OPERATE, TABLES AND CHAIRS ARRANGED FOR SEATING 93 PERSONS., OBTAIN PLACE OF ASSEMBLY CERTIFICATE OF OPERATION #39009883R | Oct 4, 2019 POP/IN-VIO | $0 |
| Sep 23, 2019 | Unknown CLASS - 1 I OBSERVED IN THE ELECTRICAL SERVICE ROOM THE INSTALLATION OF A GROUND BAR FOR THE SERVICE DISCONNECTS WITH NO MAIN GROUNDING ELECTRODE CONDUCTOR FROM THE WATER MAIN. A SUPPLEMENTAL GROUND ROD CONDUCTOR IS SUPP #39009889H | Oct 4, 2019 POP/IN-VIO | $0 |
| May 8, 2019 | Boilers CLASS - 2 PIPING ON FEED WATER LEAK-SMOKE ALARM DEFECTIVE-BACKFLOW DRAIN NOT CONNECTED-SURFACE BLOW DOWN DRAIN NOT PIPED-BODY DRAINS NOT INSTALLED ON SAFETY VALVES-FLAME GLASS MISSING-LOW WATER CUTOFF VALVE DEFECTIVE; CO #39002754Z | May 9, 2019 POP/IN-VIO | $0 |
| Apr 17, 2019 | Construction CLASS - 2 WORK WITHOUT A PERMIT. OBSERVED IN CELLAR PLUMBING WORK DONE TO REMOVE TWO TEMPORARY AVL PIPES LINE FROM TWO BOILERS WITHOUT A PERMIT. REM: OBTAIN ALL REQUIRED PERMITS. #35415222H | Apr 22, 2019 POP/IN-VIO | $0 |
| Aug 21, 2018 | Boilers CLASS - 2 B254,42,50A-50F 50A-NEED SUMP PUMP TO BE REPAIRED OR REPLACED; 50B- SMOKE ALARM NOT WORKING; 50C-FRESH AIR FAN NOT WORKING AND MISSING SAIL SWITCH; 50D- NO OPEN BALL VALVES; 50E-MISSING ADDER AND PLATFORM #32097010X | Oct 25, 2018 POP/IN-VIO | $0 |
| Apr 2, 2018 | Construction CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPIANT MANNER. OBSERVED ON 4218 AT ABOVE ADDRESS ACTIVE LEAK ON WATER PIPING IN WATER/SPRINKLER ROOM. RMDY: REPAIR AND/OR REPLACE. PHOTOS TAKEN............................. #35326458J | Jun 21, 2018 POP/IN-VIO | $0 |
| Feb 2, 2018 | Construction CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. IN AUGUST 21, 2017, 28, 17, APRIL 12, 2017. FOUR ELECTRICAL VIOLATIONS WAS ISSUED TO THE RESPONDENT. THE RESPONDENT FAILED TO COMPLY WITH (NYC #35312723Y | Apr 5, 2018 POP/IN-VIO | $0 |
| Aug 28, 2017 | Plumbing CLASS - 2 FAIL TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.RC:INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER P.C. 102.3;27-902. OBSERVED ON 8/28/17 AT ABOVE ADDRESS JIM CAPS INSTALLED IN BASEMENT OUTSIDE #35290537X | Dec 14, 2017 POP/IN-VIO | $0 |
| Aug 28, 2017 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNE:NO FIRE STOPPING PER BC 712.3:27-345. NOTED: AT CELLAR IN GAS METER ROOM,OPENINGS AROUND PLUMBING ELIMINATING FIRE STOPPING.REMEDY:PROVIDE/MAINTAIN FIRE STOP #35290354N | Dec 14, 2017 POP/IN-VIO | $0 |
| Aug 28, 2017 | Unknown CLASS - 2 FAIL TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS/ ENCLOSURES/CABLE ARMOR.OBSERVED SEALTITE IN KITCHEN DISCONNECTED FROM FIXED APPLIANCE WAITH WIRING EXPOSED.REMEDY:COMPLY WITH CODE/PROVIDE #35290390K | Dec 14, 2017 POP/IN-VIO | $0 |
| Aug 28, 2017 | Construction CLASS - 2 OPERATION OF A PLACE OF ASSEMBLY WITHOUT A CURRENT CERTIFICATE OF OPERATION.NOTED: NO CURRENT CERTIFICATE OF OPERATION FOR 1ST STORY CAFETERIA WITH MAXIMUM OCCUPANCY SIGN FOR 365 PERSON.REMEDY:OBTAIN A PLACE #35290353L | Dec 14, 2017 POP/IN-VIO | $0 |
| Aug 28, 2017 | Unknown CLASS - 1 110.4 CONDUCTORS NOT PROPERLY INSTALLED /TERMINATED . OBSERVED PRIOR CONDITION NOT RECTIFIED AS PER PREVIOUS ECB #35253006Y. TWO CONDUCTORS TERMINATED UNDER A SINGLE LUG TERMINAL NOT DESIGNED FOR INSTALLATION #35290388L | Dec 14, 2017 POP/IN-VIO | $0 |
| Aug 21, 2017 | Construction CLASS - 1 UNLAWFUL ACTS.FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.IN APRIL 12,2017, JUNE 26,2017.THREE ELECTRICAL VIOS WAS ISSUE TO THE RESPONDENT.THE RESPONDENT FAILED TO COMPLY W/(NYC) ELECTRICAL CODE #250.4,110 #35284858X | Dec 21, 2017 POP/IN-VIO | $0 |
| Jun 26, 2017 | Construction CLASS - 1 AN UNLAWFUL ACT. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. FAILED TO CORRECT & CERTIFY ECB#35253004K RECEIVED ON 3-12-17 FOR BROKEN OR MISSING THE MAIN HOUSE AROUNDING WIRE WHICH WAS CONNECTED TO THE #35228248M | Aug 10, 2017 POP/IN-VIO | $0 |
| Apr 12, 2017 | Plumbing CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC 102.3;27-302. OBSERVED ON 4/12/17 @ ABOVE ADDRESS JIM CAPS & ALSO IN ELECTRIC METER ROOM. #35252954J | May 11, 2017 POP/IN-VIO | $0 |
| Apr 12, 2017 | Unknown CLASS - 1 FAILURE TO GROUND ELECTRICAL SYSTEM. AT THE TIME OF INSP. I OBSERVED THE MAIN BLDG GROUND WAS CUT OFF FROM THE BLDG WATER MAIN PIPE. THIS ISAN IMMEDIATE HAZARD TO PERSON & PROPERTY AS IT DOESN'T ALLOW INCIDENTA #35253004K | May 11, 2017 POP/IN-VIO | $0 |
| Apr 12, 2017 | Unknown CLASS - 1 EC110.14A. CONDITIONS NOT PROPERLY INSTALLED/TERMINATED. I OBSERVED @ TIME OF INSP. THE OUTDOOR A.C. SERVICE SWITCHES WITH 2 CONDUCTORS SERVICE UNDER A SINGLE TERMINAL LUG, BSMT SERVICE SWITCHES WITH 2 CONDUCTO #35253006Y | May 11, 2017 POP/IN-VIO | $0 |
| Aug 8, 2016 | Construction CLASS - 2 OPERATION OF A PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERAT TION(PACO) NOTED: NO CURRENT CERTIFICATE OF OPERATION FOR 1ST FLOOR CAFETERIA WITH MAXIMUM OCCUPANCY SIGN POSTED FOR 365 PERSONS.PREVIOUS #35200759J | Nov 17, 2016 POP/IN-VIO | $0 |
| Feb 19, 2016 | Construction CLASS - 2 OPERATION OF PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERATION.NOTED: OPERATING 1ST FLR CAFETERIA W/MAXIMUM OCCUPANCY 365 PERSONS W/OCURRET CERTIFICATE OF OPERAITONS.RMDY: OBTAIN A PLACE OF ASSEMBLY CERT #35171437R | Mar 31, 2016 POP/IN-VIO | $0 |
None open.
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device | Active |
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Sep 30, 2026 | ECB | Boilers: FOUND FITZGIBBONS OIL FIRED BOILER MODEL#99042 WITH DEFECTIVE SAFETY RELIEF VALE(LEAKING). SECONDARY BOILER ROOM DOOR NOT SELF CLOSING. POOR LIGHTING IN BOILER ROOM. | Open |
| Sep 30, 2026 | ECB | Boilers: FOUND FITZGIBBON OIL FIRED BOILER MODEL#99042 WITH CORRODED AND LEAKING BOILER BASE, SAFETY RELIEF VALVES DEFECTIVE , LEAKING AND LABELS NOT LEGIBLE, EXPOSED WIRES AT CONTROLS, OIL PUMP SET NOT TO RUN CONSTANT. | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 30, 2026, 4:36 PM ET. BBL 1021050001.