Manhattan · Block 1895 · Lot 23 · 10025

2891 Broadway

13 floors · 250 apartments · 88,332 sq ft · built 1911 · class D7 · owner of record: Trustees Of Columbia University

15open violations
$1,905ECB/OATH penalties owed
0HPD class C (immediately hazardous)
Overdueto Annual property registration

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

OverdueRegistration expired 2026-09-01
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 9 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 69 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 69 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 69 days
Annual
Annual boiler inspection (5 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-28 (Accepted). Agency page

Dec 31, 2026
in 69 days
4 of 5 without an accepted 2026 report yet
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 85 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 88,332 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 190 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 190 days
Annual filing
Energy audit and retro-commissioning (2035) Likely applies
Local Law 87 · Calendar year 2035
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 1895). Agency page

Dec 31, 2035
in 3356 days
Next due 2035
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $367,500 in late-filing or failure-to-file penalties. Agency page

On fileCycle 10 filing on record: SAFE (2025-06-03)

Open violations

ECB / OATH (8) · $1,905 owed
IssuedViolationHearingBalance
Dec 24, 2025Boilers CLASS - 2
I FOUND A FEDERAL FST-250 STEAM BOILER WITH ALL BOILER WIRE IS EXPOSED/ CORRECT ALL VIOLATING CONDITION/SUBMIT CERTIFICATE OF CORRECTION
#39171473J
Jan 5, 2027
DEFAULT
$1,280
Nov 16, 2023Construction CLASS - 2
AT TIME OF INSPECTION OBSERVED SIDEWALK SHED AND SUSPENDED SCAFFOLDING IN PLACE FOR FACADE REPAIR IN PROGRESS. ASKED SUPERVISOR FOR HIS FOREMEN CARD AND IT WAS NOT FROM RIGGER ON FILE.PROVIDE FOREMAN CARD FOR S
#39523453Z
Jan 25, 2024
IN VIOLATION
$625
Dec 9, 2022Local Law CLASS - 2
FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #906642.REMEDY:SUBMIT ACCEPTABLE REQUIRED TE
#37024831H
Feb 23, 2023
DEFAULT
$0
Jul 12, 2021Boilers CLASS - 2
SAFETY VALVE DISCHARGES NOT SUPPORTED-THREE ELECTRICAL BOXES IN BOILER ROOM OPEN-NO THERMOMETER ON HW PIPE AT MIXING VALVE-BAROMETRIC DAMPER NOT OPERATING FREELY-NO BODY DRAINS ON SAFETY VALVES; CORRECT VIOLATI
#39044240R
Aug 26, 2021
IN VIOLATION
$0
Jul 12, 2021Boilers CLASS - 2
AS PER ONE AO SMITH DURA MAX, DW-720 BOILER; BOILER NOT REGISTERED., MAINTAIN BOILER; REGISTER BOILER, CORRECT ALL VIOLATION CONDITIONS AND CALL FOR AN INSPECTION.
#39044241Z
Aug 26, 2021
IN VIOLATION
$0
May 17, 2019Boilers CLASS - 2
2 AO SMITH BOILERS NOT REGISTERED-SPILL SWITCH DISCON. #02-NO COMPOUND GAGES #S 02 & 03-FLUE PIPE METAL NOT CODE #S 02 & 03-DOM. HW TEMP. GAGE MISSING FROM PIPING-DEFECTIVE HW TEMP. GAGE BOILER#01-NO BODY DRAIN
#39003080X
Jul 11, 2019
STIPULATION/IN-VIO
$0
Aug 8, 2015Boilers CLASS - 2
B254,50A,4B.50A LOW WATER CUT OF NOT WIRED IN AKA FLOW SWITCH.
#32075605H
Sep 24, 2015
IN VIOLATION
$0
Aug 8, 2015Boilers CLASS - 2
B254,5A.50A OIL BURNER NOT REGISTERED
#32075606J
Sep 24, 2015
IN VIOLATION
$0
DOB (1)
IssuedViolationStatus
Feb 22, 2022NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
#00642
DOB VIOLATION - ACTIVE
DOB NOW Safety (1)
IssuedViolationStatus
Feb 22, 2022Facades FISPNRF
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
Active
HPD (6) · C 0 · B 3 · A 3
IssuedClassViolationCorrect by
Apr 29, 2026A(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.Aug 2, 2026
Jun 4, 2025A(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.Sep 7, 2025
Apr 1, 2024A(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.Jul 5, 2024
Apr 3, 2019B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES AT PUBLIC HALL, 6th STORYMay 8, 2019
Apr 3, 2019B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES AT PUBLIC HALL, 7th STORYMay 8, 2019
Jun 18, 2008BD26-10.01, 10.05 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS HOPPER PUB HALLS ALL STYS.Jul 23, 2008

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 22, 2026, 10:57 PM ET. BBL 1018950023.