| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Mar 10, 2021 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS.VIOLATION #35498426X ISSUED ON 12-10-20 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01.FOR FAILURE TO MAINTAIN #35527494H | Jan 21, 2022 IN VIOLATION | $1,250 |
| Jan 8, 2021 | Construction CLASS - 2 SEC. 3307.2.1 FAILURE TO PROVIDE DOT PERMIT FOR CLOSING SIDEWALK. NOTEAT TIME OF INSPECTION OF A DEMOLITION OF A 2 STY BLDG IN PROGRESS. I OBSERVED THAT THE SIDEWALK WAS CLOSED DEPT RECORDS REVEALS NO DOT PERMI #35509222P | Dec 13, 2021 IN VIOLATION | $0 |
| Dec 10, 2020 | Construction CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE: ROOF & FLOORSINCLUDUBG JOIST HAS COLLAPSED. EXTERIOR WALL AT EXP#3 IS DETERIORATING& SIDING IS FALLING & MISSING IN AREA THROUGHOUT. AT SIDEWALK ALONG #35498426X | Aug 12, 2021 IN VIOLATION | $0 |
| Feb 10, 2020 | Construction CLASS - 1 ROOF AND FLOORS INCLUDING JOISTS HAS COLLAPSED. EXTERIOR WALL AT EXPOSURE#3 COLLAPSED. EXTERIOR SIDING DISINTEGRATING AT EXPOSURE#4. METAL CELLAR ACCESS DOORS AT PUBLIC SIDEWALK BENDED AND PRESENT TRIPPING HAZA #39017217P | Aug 12, 2021 IN VIOLATION | $625 |
| Jun 29, 2016 | Construction CLASS - 2 FAILURE TO MAINTAIN IN CODE-COMPLAINT MANNER DEFECTS.NOTED:1.EXP #1 EXTERIOR WALL HAVE VERTICAL/HORIZONTAL CRACKS & BUILDING.2.FRONT SIDEWALK SHED HAVE NO LIGHTING(DEAD BULBS).REM:COMPLY WITH NOTICE OF VIOLAT #35195483Y | Dec 5, 2016 WRITTEN OFF | $0 |
| Aug 22, 2015 | Construction CLASS - 1 FAILURE TO MAINTAIN BLDG WALL OR APPURTENANCES. NOTE: AT 3RD STY & PARAPET AREA AT EXP#1 ARE VERTICAL & HORIZONTAL CRACKS & BRICK WALL IS BULGING & IN DANGER OF FALLING ONTO PUBLIC SIDEWALK. REMEDY: MAINTAIN #35149191P | Oct 19, 2015 IN VIOLATION | $0 |
| Issued | Violation | Status |
|---|---|---|
| Nov 18, 2015 | FAIL TO CERTIFY CLASS 1 FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION #00192 | DOB VIOLATION - ACTIVE |
| Aug 22, 2015 | UNSAFE BUILDINGS #3032/15 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Nov 18, 2015 | AEUHAZ FTC-AEU-HAZ | Active |
| Issued | Class | Violation | Correct by |
|---|---|---|---|
| Jun 4, 2008 | B | SECTION 27-2038 ADMIN CODE: PROVIDE ADEQUATE LIGHTING FOR 60 WATT PUBLIC HALL ALL STORIES. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2038 ADMIN CODE: PROVIDE ADEQUATE LIGHTING FOR 2 STY. PUBLIC HALL NIGHT INSPECTION | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE SASHES OFWINDOWS FRONT ROOM 2ND STY. APT. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF CONCEALED CEILING LEAK, BATHROOM & REAR ROOM 2ND STY. APT. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR WALLS & CEILINGS, BATHROOM & REAR ROOM & CEILING KITCHEN 2ND STY. APT. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING WINDOW SILL OF WINDOW, REAR ROOM 2ND STY. APT. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING CERAMIC TILES AT WALLS, BATHROOM, 23ND STY. APT. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING CERAMIC TILES AT WALL PUBLIC HALL VESTIBULE. | Jul 9, 2008 |
| Jun 4, 2008 | A | SECTION 27-2027 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE RAIN LEADER REAR YARD GROUND TO 1ST STY. | Sep 7, 2008 |
| Jun 4, 2008 | A | SECTION 27-2027 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE GUTTER REAR YARD THROUGHOUT ROOF. | Sep 7, 2008 |
| Jun 4, 2008 | A | SECTION 27-2014 ADMIN. CODE AND DEPARTMENT RULES AND REGULATIONS: SCRAPE AND REMOVE RUST SCALES AND PAINT WITH TWO COATS OF PAINT THE REAR FIRE ESCAPES. | Sep 7, 2008 |
| Jun 4, 2008 | A | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE MAILBOXES VESTIBULE 1ST STY. PUBLIC HALL. | Sep 7, 2008 |
| Jun 4, 2008 | A | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCKING DEVICE ENTRANCE TO BUILDING. | Sep 7, 2008 |
| Jun 4, 2008 | A | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING DOOR STOP ENTRANCE DOOR TO 3RD STY. APT. | Sep 7, 2008 |
| Jun 4, 2008 | A | SECTION 27-2005 ADMIN. CODE: PROPERLY SECURE THE LOOSE HALL TOGGLE SWITCH 3RD STY. PUBLIC HALL. | Sep 7, 2008 |
| Jun 4, 2008 | B | SECTION 27-2010, 2011, 2012 ADMIN. CODE: REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE REAR YARD. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005,2007 ADMIN. CODE AND DEPARTMENT RULES AND REGULATIONS: REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES 2ND STY. REAR. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS REAR FIRE ESCAPES. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE UPPER SASH GLASS 3RD STY. PUBLIC HALL WINDOWS. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS ENTRANCE DOOR TO BUILDING. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005, 2007 ADMIN. CODE: REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ARTICALS 3RD STY. PUBLIC HALL. | Jul 9, 2008 |
| Jun 4, 2008 | A | SECTION 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING CLOSET REAR ROOM 2ND STY. APT. | Sep 7, 2008 |
| Jun 4, 2008 | A | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS WINDOW REAR ROOM 2ND STY. APT. | Sep 7, 2008 |
| Jun 4, 2008 | A | SECTION 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE SHOWER BODY 2ND STY. APT. BATHROOM. | Sep 7, 2008 |
| Jun 4, 2008 | A | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING CHAINS FRONT ROOM 2ND STY. APT. | Sep 7, 2008 |
| Jun 4, 2008 | C | SECTION 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES BATHROOM & KITCHEN 2ND STY. APT. ER1 | Jun 10, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING BALUSTERS ALL STYS. PUBLIC HALL. | Jul 9, 2008 |
| Jun 4, 2008 | B | SECTION 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING GLASS LOWER WINDOW SASH, 3RD STY. PUBLIC HALL. | Jul 9, 2008 |