3 floors · 88,487 sq ft · built 1949 · class W1 · owner of record: Nyc Department Of Education
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 63 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 88,487 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 184 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 184 days | Annual filing |
| Gas piping inspection (2027 cycle) Likely applies Local Law 152 · During 2027 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 15 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2027 in 428 days | Next cycle year 2027 |
| Energy audit and retro-commissioning (2034) Likely applies Local Law 87 · Calendar year 2034 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 7474). Agency page | Dec 31, 2034 in 2985 days | Next due 2034 |
| Annual boiler inspection (2 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-01-21 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Mar 17, 2026 | Construction CLASS - 2 REISSUE ECB #35720915L. FAILURE TO MAINTAIN MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: AT (1ST FL) GYM, AUDITORIUM, CAFETERIA EMERGENCY LIGHTS NOT WORKING #35722552K | Apr 10, 2026 POP/IN-VIO | $0 |
| Mar 17, 2026 | Construction CLASS - 2 REISSUE ECB #35720914J. EXIT DOOR NOT SELF-CLOSING. NOTED: AT (1ST FL)EXIT 6 AND 8 (2ND FL)STAIR E/F DOORS ARE IN DISREPAIR/NOT CLOSING WHENTESTED. REMEDY: REPAIR/REPLACE DOOR. #35722553M | Apr 10, 2026 POP/IN-VIO | $0 |
| Mar 17, 2026 | Construction CLASS - 2 REISSUE ECB #35720916N. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: AT (3RD FL) STAIR C WIRE GLASS VIEW PANEL CRACKED. REMEDY: REPAIR AND/OR REPLACE. #35722551Z | Apr 10, 2026 POP/IN-VIO | $0 |
| Aug 19, 2025 | Boilers CLASS - 2 XOUND BURNHAM (MODEL#4FL 993) GAS FIRED BOILER IN CELLAR WITH DEFECTIVE MOTORIZED DAMPER CORRECT VIOLATING CONDITION SUBMIT CERTIFICATE OF CORRECTION #39157660Y | Aug 25, 2025 POP/IN-VIO | $0 |
| Aug 19, 2025 | Boilers CLASS - 2 FOUND BURNHAM (MODEL#4FL 993) GAS FIRED BOILER IN CELLAR WITH DEFECTIVE MOTORIZED DAMPER CORRECT VIOLATING CONDITION SUBMIT CERTIFICATE OF CORRECTION #39157670H | Aug 25, 2025 POP/IN-VIO | $0 |
| Jul 3, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: AT AUDITORIUM AT EXIT #11, 3 EMERGENCY EXIT LIGHTING, 2 AT CAFET #35720915L | Aug 15, 2025 POP/IN-VIO | $0 |
| Jul 3, 2025 | Construction CLASS - 2 EXIT DOOR NOT SELF-CLOSING. NOTED: EXIT #8, BOTH DOORS DO NOT OPEN/CLOSE PROPERLY NEEDS EXCESSIVE FORCE TO OPEN. AT CELLAR EXIT DOOR THAT LEADS TO THE COURTYARD IS ROTTED AND DO NOT CLOSE PROPERLY. REMEDY: REPA #35720914J | Aug 15, 2025 POP/IN-VIO | $0 |
| Jul 3, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 3RD FLOOR AT EXIT "C" WIRED GLASS VIEW PANEL IN THE DOOR IS CRACKED. REMEDY: REPAIR/REPLACE DOOR. #35720916N | Aug 15, 2025 POP/IN-VIO | $0 |
| Jun 21, 2022 | Boilers CLASS - 2 BOILER MOTORIZED DRAFT REGULATOR SEIZED UP/GAS PRESSURE GAUGE LINE NOT HARD PIPE WITH GAS COCK/BURNER RELAY FAULT SCREEN DEFECTIVE/BOILER FEED PUMP NOT KEEPING UP WITH WATER DEMAND;IE; GOES OFF ON LOW WATER;COR #39064435P | Jul 8, 2022 PENDING | $625 |
| Jun 21, 2022 | Boilers CLASS - 2 LOW WATER ALARM BELL DEFECTIVE/BURNER RELAY FAULT CODE SCREEN DEFECTIVE/GAS PRESSURE GAUGE LINE NOT HARD PIPE WITH GAS COCK/BOILER FEED PUMP NOT KEEPING UP WITH WATER DEMAND;IE; GOES OFF ON LOW WATER/VAC SYSTEM #39064434N | Jul 8, 2022 PENDING | $625 |
| May 15, 2019 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER: ILLUMINATION FOREXITS; EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006-1; 27-381. NOTED: @THE GYMNASIUM, EXIT LIGHT #9, AUDITORIUM RIGHT WALL, 1 LIGHT, #35423279Z | Sep 23, 2019 DEFAULT | $1,562 |
| Issued | Violation | Status |
|---|---|---|
| Feb 27, 2001 | LOCAL LAW 62/91 - BOILERS #24126 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Dec 15, 2025 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device | Active |
| Jul 25, 1994 | Boiler LL6291 | Active |
None open.
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 29, 2026, 2:55 PM ET. BBL 3074740001.