4 floors · 13,075 sq ft · built 2007 · class H4 · owner of record: Paramount Estates, Llc
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 67 days | Keep the report on file (not filed with DOB) |
| Gas piping inspection (2029 cycle) Likely applies Local Law 152 · During 2029 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 13 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2029 in 1163 days | Next cycle year 2029 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Aug 31, 2026 | Unknown CLASS - 2 MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED ON THE ROOF, 4TH , 3RD, 2ND FLS THE HOT WATER TANK / MECHANICAL RMS HAS NO REMOTE SHUTDOWN AT THE POINT OF EGRESS. B.C 1006.8.1 REMOT #39202458K | Nov 10, 2026 PENDING | $800 |
| Aug 31, 2026 | Construction CLASS - 1 ATOI OBSERVED HOT WATER HEATER ON THE ROOF INSTALLED WITH NO DISCHARGER PIPING INSTALLED COMING OUT OF THE PRV CONTRARY TO PC 504.6 ESTABLISHES THE REQUIREMENTS FOR DISCHARGE PIPING SERVING TEMPERATURE AND PRES #39202473Z | Nov 10, 2026 PENDING | $2,500 |
| Aug 31, 2026 | Elevators CLASS - 1 CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION #39202440M | Nov 10, 2026 PENDING | $1,250 |
| Aug 31, 2026 | Construction CLASS - 1 ATOI OBSERVED HOT WATER HEATERS INSTALLED IN THE ROOF MECHANICAL ROOM AND IN THE FLOOR MECHANICAL ROOMS WITH NO PERMITS ON FILE CHECKED BIS/DOBNOW ALL WORK MUST HAVE A PERMIT AND BE INSTALLED BY A LICENSED MAST #39202472R | Nov 10, 2026 PENDING | $2,500 |
| Aug 31, 2026 | Construction CLASS - 2 CLASS 2 AGG 1: WORK WITHOUT A PERMIT, IN VIOLATION OF NYC ADMINISTRATIVE CODE 28-105.1. PREVIOUSLY ISSUED VIOLATION REMAINS UNCORRECTED. DEVICE 4W11015 WAS REMOVED WITHOUT A DOB PERMIT HAVING BEEN OBTAINED AND #39202441Y | Nov 10, 2026 PENDING | $3,125 |
| Feb 17, 2026 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR SUMMONS 39124333X., FILE A CERTIFICATE OF CORRECTION #39177510R | Jun 16, 2026 DEFAULT | $6,250 |
| Feb 17, 2026 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR SUMMONS 39124332Y., FILE A CERTIFICATE OF CORRECTION #39177509J | Jun 16, 2026 DEFAULT | $6,250 |
| Jan 30, 2026 | Elevators CLASS - 2 : WORK WITHOUT A PERMIT. DEVICE 4W11015 WAS REMOVED WITHOUT A PERMIT BEING OBTAINED AND APPLICATION BEING FILED. REMEDY; FILE APPLICATION AND OBTAIN A PERMIT FOR THE WORK AND SCHEDULE A TEST APPOINTMENT WITH NY #39175426P | May 12, 2026 ADMIT/IN-VIO | $0 |
| Aug 25, 2025 | Construction CLASS - 2 OBSERVED ON THE 4TH FLOOR OPEN ENDED GAS LINE, FUTURE ON GAS LINE AND OPEN VENT LINE. ON 3RD AND 2ND FLOORS VENT CONNECTIONS TO HOT WATER HEATERS ARE NOT SEALED. ON THE ROOF PAINTED SPRINKLER HEAD. IN THE BASEM #39158209Y | Aug 14, 2026 DEFAULT | $6,250 |
| Aug 25, 2025 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRATIONS IN MECHANICAL ROOMS THROUGHOUT BUILDING . HOLES WILL A #39158216M | Jun 12, 2026 DEFAULT | $6,250 |
| Aug 19, 2025 | Elevators CLASS - 2 CLASS 2: BOTH STREET LEVEL AND 1ST FLOOR HOISTWAY DOORS ARE NOT SELF CLOSING. BOTH REQUIRED TO BE PUSHED TO FULLY CLOSED POSITION FROM THE LANDINGS, ADJUST. #39157540J | Oct 20, 2026 DEFAULT | $3,125 |
| Sep 9, 2024 | Construction CLASS - 1 NO FRESH ARE VENTILATION IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. AS PER E 4 OF THE FUEL GAS CODE GAS METER ROOM SHALL BE VENTED PROPERLY., REPAIR AND/REPLACE #39124333X | Jan 21, 2025 DEFAULT | $6,250 |
| Sep 9, 2024 | Construction CLASS - 1 OBSERVED COMBUSTIBLE STORAGE IN THE GAS METER ROOM AS WELL AS COMBUSTIBLE STORAGE IN ALL OF THE MECHANICAL ROOMS. AS PER E 3 OF THE FGC GAS METER ROOMS, WHEN PROVIDED, SHALL AT ALL TIMES BE KEPT CLEAR OF ALL RU #39124332Y | Jan 21, 2025 DEFAULT | $3,125 |
| Sep 9, 2024 | Construction CLASS - 2 OBSERVED PAINTED SPRINKLER CAPS AS WELL AS A PAINTED SPRINKLER HEAD. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATING CONDITION IN ACCORDANCE WITH THE ORIGINAL DES #39124334H | Nov 19, 2024 STIPULATION/IN-VIO | $0 |
| Dec 14, 2020 | Construction CLASS - 2 WORK WITHOUT PERMIT. DEVICE # 4W1115 . BUILDING REMOVED WHEELCHAIR LIFT WITHOUT PERMIT, BEING OBTAINED AND APPLICATION BEING FILED. REMEDY; FILE APPLICATION AND OBTAIN PERMIT FOR WORK AND SCHEDULE TEST APPOINTM #39033401P | Feb 2, 2021 ADMIT/IN-VIO | $0 |
| Dec 14, 2020 | Elevators CLASS - 1 1. PROVIDE OR REPAIR OUTSIDE COMMUNICATION . 2. INSUFFICIENT OIL IN THE TANK . 3. NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLL #39033394X | Feb 2, 2021 ADMIT/IN-VIO | $0 |
| Issued | Violation | Status |
|---|---|---|
| Nov 20, 2021 | ELEVATOR #9027/711911 | DOB VIOLATION - ACTIVE |
| Mar 17, 2021 | FAIL TO CERTIFY CLASS 1 FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION #00435 | DOB VIOLATION - ACTIVE |
| Sep 6, 2019 | (OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST #07994 | DOB VIOLATION - ACTIVE |
| Sep 6, 2019 | (OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST #07995 | DOB VIOLATION - ACTIVE |
| Jan 26, 2018 | (OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST #09645 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Sep 18, 2025 | Gas Piping - LL152 FTF-PL-PER Cycle 1, Sub-cycle B (premises is in Community District 13) | Active |
| Oct 11, 2024 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction | Active |
| Mar 17, 2021 | AEUHAZ FTC-AEU-HAZ | Active |
| Issued | Class | Violation | Correct by |
|---|---|---|---|
| Mar 10, 2022 | I | §27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID R | — |
| Nov 29, 2024 | I | §27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID R | — |
| Nov 22, 2023 | I | §27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID R | — |
| Nov 6, 2019 | I | §27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID R | — |
| Nov 21, 2025 | I | §27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID R | — |
| Apr 20, 2021 | I | §27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID R | — |
| Nov 15, 2022 | I | §27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID R | — |
| May 8, 2026 | A | (A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS. | Aug 11, 2026 |
| Jun 13, 2025 | A | (A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS. | Sep 16, 2025 |
| Apr 17, 2024 | A | (A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS. | Jul 21, 2024 |
| Mar 31, 2023 | A | (A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS. | Jul 4, 2023 |
| Mar 10, 2022 | A | (A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS. | Jun 13, 2022 |
| Apr 20, 2021 | A | (A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS. | Jul 24, 2021 |
| Date | Source | What | Now |
|---|---|---|---|
| Aug 31, 2026 | ECB | Unknown: MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED ON THE ROOF, 4TH , 3RD, 2ND FLS THE HOT WATER TANK / MECHANICAL RMS HAS NO REMOTE SHUTDOWN AT THE POINT OF EGRESS. B.C 1006.8.1 REMOT | Open |
| Aug 31, 2026 | ECB | Construction: ATOI OBSERVED HOT WATER HEATER ON THE ROOF INSTALLED WITH NO DISCHARGER PIPING INSTALLED COMING OUT OF THE PRV CONTRARY TO PC 504.6 ESTABLISHES THE REQUIREMENTS FOR DISCHARGE PIPING SERVING TEMPERATURE AND PRES | Open |
| Aug 31, 2026 | ECB | Elevators: CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION | Open |
| Aug 31, 2026 | ECB | Construction: ATOI OBSERVED HOT WATER HEATERS INSTALLED IN THE ROOF MECHANICAL ROOM AND IN THE FLOOR MECHANICAL ROOMS WITH NO PERMITS ON FILE CHECKED BIS/DOBNOW ALL WORK MUST HAVE A PERMIT AND BE INSTALLED BY A LICENSED MAST | Open |
| Aug 31, 2026 | ECB | Construction: CLASS 2 AGG 1: WORK WITHOUT A PERMIT, IN VIOLATION OF NYC ADMINISTRATIVE CODE 28-105.1. PREVIOUSLY ISSUED VIOLATION REMAINS UNCORRECTED. DEVICE 4W11015 WAS REMOVED WITHOUT A DOB PERMIT HAVING BEEN OBTAINED AND | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 25, 2026, 3:57 AM ET. BBL 4088310001.